ICON PROCESS CONTROLS R7C Gold Electrode ORP Sensor Transmitter Instruction Manual
- July 18, 2024
- ICON PROCESS CONTROLS
Table of Contents
R7C Gold Electrode ORP Sensor Transmitter
“`html
Specifications:
-
Electrode Types: R7C (Gold Electrode), R7G (Platinum
Electrode) -
Output Options: 4-20mA 2-Wire, 4-20mA + RS485
-
Preamp: Integral Preamp for 2-wire 4-20mA and RS485 direct
sensor to controller connection
Product Usage Instructions:
Installation and Setup:
1. Only authorized personnel should carry out installation,
setup, and operation.
2. Ensure the power cable is physically separated from the power
supply during initial wiring connection or repair.
Safety Information:
– Do not use tools to avoid damaging the product.
– De-pressurize and vent the system before installation or
removal.
– Always confirm chemical compatibility before use and do not
exceed maximum temperature or pressure specifications.
– Always wear appropriate Personal Protective Equipment (PPE)
during installation and service.
Preparation before Measurement:
1. Prepare electrode maintenance by unscrewing the protective
bottle cap and immersing the electrode bulb and liquid interface in
the measured liquid.
2. Use a standard buffer reference solution with a known ORP
value and wash the sensing electrode with distilled water before
use.
Product Features:
– High performance industrial pH sensor for harsh
applications.
– Combines all measurement functions in one compact body.
– Offers various output options for calibration and
communication.
– Digital output allows longer distances without compromising
accuracy.
FAQ:
Q: How often should the electrode maintenance be
performed?
A: Electrode maintenance should be performed before each
measurement to ensure accurate readings.
Q: Can the product be used in high-temperature
environments?
A: Always confirm that the product specifications are not
exceeded, including maximum temperature limits, to prevent
damage.
“`
ProCon® — R7 Series with
ORP Sensor Transmitter Operating Manual
Direct 4-Wire
M12 Quick Connection
¾” NPT Connection
R7C
Gold Electrode
R7G
Platinum Electrode
24-0186 © Icon Process Controls Ltd.
1
ProCon® — R7 Series with
ORP Sensor Transmitter Operating Manual
Preface
Please read this manual carefully before use. Only properly skilled authorized
personnel should carry out installation, setup and operation. Ensure that the
power cable is physically separated from the power supply during the initial
wiring connection or repair. For example,
Warning | Caution | Danger
Indicates a potential hazard. Failure to follow all warnings may lead to
equipment damage, injury, or death.
Note | Technical Notes
Highlights additional information or detailed procedure.
1. Apparent damage to the sensor
2. The sensor does not work properly or provides specified measurements
3. The sensor has been stored for a long time in an environment where the
temperature exceeds 70°C
Hand Tighten Only
Over tightening may permanently damage product threads and lead to failure of
the retaining nut.
Safety Information
Do Not Use Tools
Use of tool(s) may damage produced beyond repair and potentially void product
warranty.
De-pressurize and vent system prior to installation or removal Confirm chemical compatibility before use DO NOT exceed maximum temperature or pressure specifications
Personal Protective Equipment (PPE)
Always utilize the most appropriate PPE during installation and service of
Truflo products.
DO NOT alter product construction
ALWAYS wear safety goggles or face-shield during installation and/or service
Preparation before measurement
Important
Be sure to calibrate your sensor prior to use. Please refer to the operating
instructions of your ProCon® Controller for calibration details.
Connect the wires from the sensor to the appropriate ProCon® controller. All
ProCon® pH sensors come with an internal PT1000 temperature electrode. Refer
to sensor wiring diagram of controller.
Prepare electrode maintenance before measurement When using the electrode, the
protective bottle at the top shall be screwed off and placed at a place where
it is not easy to touch. Then, the protective bottle cap shall be removed and
the electrode bulb and liquid interface shall be immersed in the measured
liquid.
ORP Sensor Calibration SimplCal®
1. Use a standard buffer reference solution with known ORP value. (always use
a fresh buffer solution) 2. Unscrew the sensor protection cap and wash the
sensing electrode with distilled water. Carefully wipe any excess water with a
soft paper
towel and gently wipe the gold/platinum sheet to keep it clean. 3. Select the
calibration mode in the controller (See manual for ProCon® SimplCal® for step
by step simple instruction) 4. Insert the sensor into the first reference
solution ensure the sensor tip is covered. 5. Stir 6. Wait for the reading to
stabilize (60 seconds) 7. Press the Enter button on the ProCon® Controller 8.
Wait until the DONE is display on screen 9. Once the sensor has been
calibrated rinse with distilled water. Carefully wipe any excess water with a
soft paper towel and gently wipe
the gold/platinum sheet to keep it clean. In order to ensure a fast response
time, the electrode glass should always be kept wet. After the calibration is
completed and the electrode is properly cleaned, store the sensor in a 3mol
KCI Potassium Chloride solution. NOTE: After use it is important to inspect
the sensor to ensure there are no deposits and the gold/platinum is clean. If
needed the sensor can be washed with a dilute HCL acid wash. It is not
recommended to store the sensor in distilled , or deionized water.
24-0186 © Icon Process Controls Ltd.
2
ProCon® — R7 Series with
ORP Sensor Transmitter Operating Manual
High performance industrial pH sensor for harsh applications
The ProCon® P14 series offers the ultimate combination of durability,
functionality and long-term performance; exactly what is required for
industry’s most complex applications. The Nexus® reference eliminates
reference poisoning. The sensors are available in flat planar or bulb style
design.
All measurement functions are combined in one compact body — measuring
electrode, temperature sensor and an inner reference chamber. The 2-wire
4-20mA, 4-wire or 4-20mA + RS485 output options simplify calibration and
communication with remote displays and controllers..
? M12 Quick Connection ? 4-20mA Output ? Temperature Compensated ? Nexus® Solid KCl Reference ? PP or PPS Body Materials ? RS 485 Modbus Communication ? No Preamp Required ? ¾” NPT Connection
PREEMPT THE PREAMP
Enhanced chip technology allows for remote calibration as well as diagnostic
data
Digital output — longer distances without compromising accuracy.
Integral Preamp 2-wire 4-20mA, RS485 direct sensor to controller connection (no preamp)
Nexus® technology · Solid KCI infused reference junction · Eliminates
reference poisoning/leaching · Extended life expectancy
2 Durable Sensors Designed for the Toughest ORP Environments
R7C
Gold Electrode
R7G
Platinum Electrode
24-0186 © Icon Process Controls Ltd.
3
ProCon® — R7 Series with
ORP Sensor Transmitter Operating Manual
Smart Sensor Technology
Advanced electronic circuity stores ORP data for automatic sensor recognition
and trouble-free calibration when connected to the ProCon® Controller.
Outputs
1. 4-20mA 2-Wire 2. 4-20mA + RS485
Both the measuring and reference electrodes are encapsulated within the non-
porous advanced KCl infused polymer known as Nexus®.
Less Calibration and Maintenance
Most sensors require on-going recalibration and are prone to premature failure
due to what is known as gradient drift, or sensor drift.
The Nexus® series is a solid reference material. Poisoning or leaching of the
reference electrolyte that occurs in standard sensor is greatly reduced.
The Nexus reference helps to eliminate the need for ongoing maintenance or
cleaning requirement due to fouling or film build up removal which occurs with
many process applications with traditional pH sensors.
Faster Response-Longer Lasting
The solid Nexus® reference provides for faster response time to changing ORP
values since there is no requirement for a junction.
? Double junction reference extends sensor life and protects against poisoning
ions
? Durable gold/platinum electrode enhances performance and increased
reliability
? Operates in sub-zero temperatures down to 14°F (-10°C)
? Advanced electronic diagnostics provides excellent repeatability and
reliability
Standard pH Gel Type Nexus® Solid Reference
Reference Poisoning
Reference Sensor
Nexus® Reference
Solid Nexus® KCl infused Junction
Electrode (Gold/Platinum)
Gold/Platinum electrode technology results in an industrial sensor with
unequalled durability and reliability (Gold: -2000mV 500mV, Platinum: 500mV
2000mV)
Direct D500 Controller with SimplCal® Auto Calibration
M12 Quick Connection
Direct 4-Wire
Typical Uses
R7C (Gold)
· Highly Acidic · Reducing Environments (Cyanide) · Below 500mV
R7G (Platinum)
· High Oxidation · Chlorinated (Pools, Spas) · Potable Water · Above 500mV
Gold Electrode (R7C)
Platinum Electrode (R7G)
Nexus® Solid Reference
¾” NPT
24-0186 © Icon Process Controls Ltd.
4
ProCon® — R7 Series with
ORP Sensor Transmitter Operating Manual
Specifications
Measurement Range
ORP
-1000mV 1000mV
Output Signal — No Preamp Required
2 Wire Loop Powered | 4-20mA + RS 485 Direct Sensor Output
Accuracy
± 1mV
Operating Temperature
14 to 176°F | -10 to 80°C | Automatic Temperature Compensation
Maximum Pressure
145 Psi | 10 bar
Design
Sensor body
PP Polypropylene (std) | Ryton® | PPS
Reference System
3.3 Mol Ag / AgCl / KCl Double Junction
pH electrode
Gold (R7C) | Platinum (R7G)
Reference
Solid Nexus®
Connection
3/4″ NPT
Measuring Electrode Resistance
< 500 M
Impedance Range
102 675 M
Temperature Compensation/Output- 4-20 + RS485 Model
Pt-1000 (Std)
Pt-100
Dimensions
24-0186 © Icon Process Controls Ltd.
5
ProCon® — R7 Series with
ORP Sensor Transmitter Operating Manual
Temperature Control
Temperature vs. Pressure
In-line Mounting
1. Avoid vertical installation. (air may be present)
2. Optimum installation 15° above
horizontal.
2
3. Process liquid should flow upward.
(for downward flow ensure backpressure is present in
order to avoid air within pipe)
Typical Application
1
22
2
3
534mV
24-0186 © Icon Process Controls Ltd.
6
ProCon® — R7 Series with
ORP Sensor Transmitter Operating Manual
Wiring — Flying Lead
4-20mA 2-wire
Blue: mA Brown: mA+
4-20mA 4-wire
Transparent: 4-20mA Black (thick): Ref White: Temperature Green: Temperature
Connects directly to ProCon® controller
Thicker Wire
Wiring — M12
4 Pin M12 Connection
4-20mA | 4 Pin
Color Blue Brown
Description
4-20mA 4-20mA +
4-20mA + RS485 Output
Red: 9-24VDC + Black: 9-24VDC Transparent: 4-20mA Black (thick): Ref Green: RS
485 A White : RS 485 B
Thicker Wire
4 Pin IO – Link Connection
M12 – Female
8 Pin M12 Connection
M12 – Female
4-20mA + Controller | 4 Pin
Color
White Green Black (Thick) Transparent
Description
Temperature Temperature
Reference 4-20mA
4-20mA + RS485 | 8 Pin
Color
Red Black Transparent Black (Thick) Green White
Description
9-24 VDC + 9-24 VDC –
4-20mA Reference RS485 A RS485 B
1
3
I-O Link | 4 Pin
4
Pin
Pin 1 Pin 2 Pin 3 Pin 4
Description 24 VDC +
GND 4-20mA
Model Selection
wwww.icwownwp.icrwowcnop.incro.ccnoopmnro.c|cosoamnle.c|sos@amilce|oss@napilcerosc@nopincro.ccnoopmnro.c|co9om 0n5.c-|4o96m 095–|9492608953–9426893-9283
Part Number R7G-P-D-1-F-M R7G-P-M-1-F-M R7G-P-S-1-F-M
R7G — General Purpose ORP Sensor
Material
Output
Type
PP
4-wire (for ProCon® display)
Flat
PP
4-20mA (2-wire, std)
Flat
PP
RS485 + 4-20mA
Flat
Connection M12 M12 M12
Last digit: “M” for M12 Connection (std) “B” Blind (J-Box) “D” Display (J-Box) “F” Flying Lead
Part Number R7C-P-D-1-F-M R7C-P-M-1-F-M R7C-P-S-1-F-M
R7C — Complex Environment ORP Sensor
Material
Output
Type
PP
4-wire (for ProCon® display)
Flat
PP
4-20mA (2-wire, std)
Flat
PP
RS485 + 4-20mA
Flat
Connection M12 M12 M12
Last digit: “M” for M12 Connection (std) “B” Blind (J-Box) “F” Flying Lead
24-0186 © Icon Process Controls Ltd.
7
ProCon® — R7 Series with
ORP Sensor Transmitter Operating Manual
Fittings
Part Number PSA-2 PSA-3 PSA-4 PSA-6 PSA-8
Easy Install Clamp On Pipe Saddles
Material
Size
Seal
Thread
PVC
2
PVC
3
PVC
4
PVC
6
PVC
8
FPM FPM FPM FPM FPM
¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT
Connection PVC PVC PVC PVC PVC
Part Number
TUPA-PV-5 TUPA-PP-5 TUPA-PF-5 TUPA-PV-7 TUPA-PP-7 TUPA-PF-7 TUPA-PV-1 TUPA-
PP-1 TUPA-PF-1 TUPA-PV-15 TUPA-PP-15 TUPA-PF-15 TUPA-PV-2 TUPA-PP-2 TUPA-PF-2
Material PVC PP PVDF PVC PP PVDF PVC PP PVDF PVC PP PVDF PVC PP PVDF
True Union Tee Fitting
Size 1/2 1/2 1/2 3/4 3/4 3/4 1 1 1 1 1/2 1 1/2 1 1/2 2 2 2
Seal FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM FPM (std) | EPDM
Thread ¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT ¾ NPT
Connection Socket | NPT
Butt | NPT Butt| NPT Socket | NPT Butt | NPT Butt| NPT Socket | NPT Butt | NPT
Butt| NPT Socket | NPT Butt | NPT Butt| NPT Socket | NPT Butt | NPT Butt| NPT
Part Number
CISSP020 CISSP030 CISSP040 CISSP060 CISSP080 CISSP100 CISSP120 CISSP140
CISSP160 CISSF020 CISSF030 CISSF040 CISSF060 CISSF080 CISSF100 CISSF120
CISSF140 CISSF160
Cast Iron Saddle Fitting
Material
Size
Cast Iron / SS / PVC
2″
Cast Iron / SS / PVC
3”
Cast Iron / SS / PVC
4”
Cast Iron / SS / PVC
6”
Cast Iron / SS / PVC
8”
Cast Iron / SS / PVC
10”
Cast Iron / SS / PVC
12”
Cast Iron / SS / PVC
14”
Cast Iron / SS / PVC
16”
Cast Iron/ SS/ PVDF
2”
Cast Iron/ SS/ PVDF
3”
Cast Iron/ SS/ PVDF
4”
Cast Iron/ SS/ PVDF
6”
Cast Iron/ SS/ PVDF
8”
Cast Iron/ SS/ PVDF
10”
Cast Iron/ SS/ PVDF
12”
Cast Iron/ SS/ PVDF
14”
Cast Iron/ SS/ PVDF
16”
Seal FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings FKM O-Rings
Part Number WAS-2 WAS-6
WPF-SS-2 WPF-SS-6
Weldolet® Pipe Adaptor
Material
Size
PVC PVC SS SS
2”-4” 6”-24” 2”-4” 6”-24”
Connection ¾ NPT ¾ NPT ¾ NPT ¾ NPT
24-0186 © Icon Process Controls Ltd.
8
ProCon® — R7 Series with
ORP Sensor Transmitter Operating Manual
Electrode preservation:
1. Clean the electrode correctly after use 2. Place the electrode in the
electrode storage bottle for storage 3. The solution in the protective bottle
is 3 mol/L KCI solution
Warranty
Icon Process Controls warrants this product to be free from significant
deviations in material and workmanship for a period of one year from the date
of purchase. If repair is necessary and has not been the result of abuse or
misuse within the warranty period, please return to Icon Process Controls and
amendment will be made without any charge. Icon Process Controls Customer
Service Center will determine if product problem is due to deviations or
customer abuse. Out of warranty products will be repaired on a charge basis.
Authorization must be obtained from Icon Process Controls Customer Service
Center to issue a RIR number before returning items for any reason. When
applying for authorization, please include the date and the reason of return.
Instruments must be carefully packed to prevent damage in shipment and insured
against possible damage or loss. Icon Process Controls will not be responsible
for any damage resulting from careless or insufficient packing. Warning:
Damage as a result of inadequate packaging is the user / distributor’s
responsibility.
by
Phone: 905.469.9283 · Sales: sales@iconprocon.com · Support:
support@iconprocon.com
24-0186 © Icon Process Controls Ltd.
9
ProCon® — R7 Series with
ORP Sensor Transmitter Operating Manual
Use with any of the following controllers — NO PREAMP REQUIRED
SINGLE INPUT
DUAL INPUT
FIVE INPUT
iconprocon.com
24-0186 © Icon Process Controls Ltd.
10