ICON PROCESS CONTROLS TVL Series Tank Level Display and Controller Owner’s Manual
- July 4, 2024
- ICON PROCESS CONTROLS
Table of Contents
ICON PROCESS CONTROLS TVL Series Tank Level Display and Controller
Specifications
General
- Display: Displayed Values Stability Transmission Parameters Protection Class
Input Signal Supply
- Standard Voltage: Current: 4-20mA 0-20mA 0-5V 0-10V 85 – 260V AC/DC 16 – 35V AC, 19 – 50V DC*
Output Signal Supply
- Standard Voltage: Passive current output * 2 x Relays (5A) 1 x Relay (5A) + 4-20mA 24VDC 4-20mA (Operating Range Max. 2.8 – 24mA)
Performance
- Accuracy: According to IEC 60770 – Limit Point Adjustment Non-Linearity Hysteresis Repeatability
Temperatures
- Operating Temperatures
Materials Wetted
- Housing: Polycarbonate
Part Number
- TVL-550-1821
- TVL-550-1829
Product Usage Instructions
Basic Requirements
- Do not use the unit in areas threatened with excessive shocks, vibrations, dust, humidity, corrosive gasses, and oils.
- Do not use the unit in areas where there is a risk of explosions.
- Do not use the unit in areas with significant temperature variations, or exposure to condensation, or ice.
- The manufacturer is not responsible for any damages caused by inappropriate installation, not maintaining the proper environmental conditions, and using the unit contrary to its assignment.
- If there is a risk of a serious threat to safety in case of unit malfunction, additional independent systems should be used.
- The unit uses dangerous voltage; ensure it is switched off and disconnected from power before troubleshooting.
- Avoid disassembling, repairing, or modifying the unit yourself.
- Defective units should be submitted for repairs at an authorized service center.
Front Panel Description
- The front panel includes features like Alarm LED indicators, an Infrared Receiver, a Bright Large Display, Programming Buttons, and Function Push Buttons.
Wiring Diagram
- Refer to the wiring diagram for proper installation. Ensure correct connections based on the relay configuration and sensor input/output requirements.
WIRE INSTALLATION
- To prevent interference in industrial installations, follow appropriate measures to ensure the unit operates correctly.
FAQ
Q: Can I repair the unit myself if it malfunctions?
A: No, do not attempt to repair or modify the unit yourself.
Defective units should be submitted for repairs at an authorized service
center.
Q: What should I do if the unit is exposed to extreme temperatures?
A: Do not use the unit in areas with significant temperature variations, exposure to condensation, or ice. Ensure proper environmental conditions for optimal performance.
- Read the user’s manual carefully before starting to use the unit.
- Producer reserves the right to implement changes without prior notice.
Symbol Explanation
This symbol denotes especially important guidelines concerning the installation and operation of the device. Not complying with the guidelines denoted by this symbol may cause an accident, damage or equipment destruction.
Basic Requirements
User Safety
- Do not use the unit in areas threatened with excessive shocks, vibrations, dust, humidity, corrosive gasses, and oils.
- Do not use the unit in areas where there is a risk of explosions.
- Do not use the unit in areas with significant temperature variations, or exposure to condensation or ice.
- The manufacturer is not responsible for any damages caused by inappropriate installation, not maintaining the proper environmental conditions, and using the unit contrary to its assignment.
- If in the case of a unit malfunction, there is a risk of a serious threat to the safety of people or property additional, independent systems and solutions to prevent such a threat must be used.
- The unit uses dangerous voltage that can cause a lethal accident. The unit must be switched off and disconnected from the power supply before starting the installation of troubleshooting (in the case of malfunction).
- Do not attempt to disassemble, repair, or modify the unit yourself. The unit has no user-serviceable parts.
- Defective units must be disconnected and submitted for repairs at an authorized service center.
Specifications
General
Display| LED | 4 x 20mm High | Red | Adjustable Brightness
Displayed Values| -999 ± 9999 | -99999 ± 999999*
Stability| 50 ppm | °C
Transmission Parameters| 1200…115200 bit/s, 8N1 / 8N2
Protection Class| NEMA 4X | IP67
Input Signal | Supply
Standard| Current: 4-20mA | 0-20mA | 0-5V | 0-10V
Voltage| 85 – 260V AC/DC | 16 – 35V AC, 19 – 50V DC*
Output Signal | Supply
Standard| 2 x Relays (5A) | 1 x Relay (5A) + 4-20mA
Voltage| 24VDC
Passive current output *| 4-20mA | (Operating Range Max. 2.8 – 24mA)
Performance
Accuracy| 0.1% @ 25°C One Digit
Accuracy According to IEC 60770 – Limit Point Adjustment | Non-Linearity |
Hysteresis | Repeatability
Temperatures
Operating Temperatures| -40 – 158°F | -40 – 70°C
Materials | Wetted
Housing| Polycarbonate
Part Number| Input| Output
---|---|---
TVL-550-1821| 4-20mA| 2 Relay
TVL-550-1829| 4-20mA| 4-20mA + 1 Relay
Front Panel Description
Function of Push Buttons
Symbol used in the manual : [ESC/MENU]
- Functions:
- Enter to main menu ( press and hold for at least 2 seconds.)
- Exit the current Screen and Enter to the previous menu (or measure mode)
- Cancel the changes made in the parameter being edited
Symbol used in the manual : [ENTER]
- Functions:
- Start to edit the parameter
- Enter into the sub-menu
- Confirmation of changes made in the parameter being edited
Symbol used in the manual : [ ] [ ]
- Functions:
- Change of the present menu
- Modification of the parameter value
- Change of the display mode
Wiring Diagram
One RELAY CONFIGURATION One 4-20mA OUTPUT
2 RELAY CONFIGURATION
WIRE INSTALLATION
- Insert screwdriver and push wire locking mechanism open
- Insert wire
- Remove screwdriver
- Due to possible significant interference in industrial installations, appropriate measures assuring the correct operation of the unit must be applied.
- The unit is not equipped with an internal fuse or power supply circuit breaker.
- For this reason, an external time-delay cut-out fuse with a small nominal current value must be used (recommended bipolar, max. 2A) and a power supply circuit breaker located near the unit.
- In the case of using a monopolar fuse, it must be mounted on the phase cable.
Programming 4-20mA Input
Calculating 4-20mA Input
SENSOR TYPE | 20mA Set Point |
---|---|
Submersible | Range of sensor / Specific Gravity = 20mA |
Ultrasonic | Tank Height |
Radar | Tank Height |
Programming Relays RS485 Modbus Programming
THE MODBUS PRO TOCOL HANDLING
- Transmission parameters: 1 start bit, 8 data bits, 1 or 2 stop bits (2 bits are sent, 1 and 2 bits are accepted when received), no parity control
- Baud rate: selectable from 1200 to 115200 bits/second
- Transmission protocol : MODBUS RTU compatible
- The device parameters and display value are available via the RS-485 interface, as HOLDING-type registers (numeric values are given in U2 code) of Modbus RTU protocol. The registers (or groups of the registers) can be read by the 03h function and written by 06h (single registers) or 10h (group of the registers) according to Modbus RTU specification. Maximum group size for 03h and 10h functions can not exceed 16 registers (for single frame).
- The device interprets the broadcast messages but then does not send the answers.
LIST OF REGISTERS
Register | Write | Range | Register description |
---|---|---|---|
01h | No | -999 ÷ 9999 | Measurement value (no decimal point) |
02h | No | 0h, A0h, 60h | The status of the current measurement; 0h – data |
valid; A0h – top border of the measurement range is exceeded; 60h –
bottom border of the measurement range is exceeded;
03h| Yes| 0 ÷ 3| “ Pnt ” parameter in the “ InPt ” menu (decimal point
position) 0 – “ 0 ”; 1 – “ 0.0 ”; 2 – “ 0.00 ”; 3
– “ 0.000 ”
04h| Yes| see descr.| State of the relays and alarm LED (binary format) (1 –
on, 0 – off): 00000000 000e00ba a – relay R1; b – relay R2; e
– alarm LED;
If written, only a , and b bits are important (others are ignored) these bits allow the user to control the relays via the RS-485 interface
05h1| Yes| 0h ÷ 1800h| State of active current output, expressed in 1/256 mA
units – it means that the high byte expresses the integer part and the low
byte fractional part of the desired output current.
Yes| 2CCh÷1800h| State of passive current output, expressed in 1/256 mA units
– it means that the high byte expresses the integer part and the low byte
fractional part of the desired output current.
Yes| 0h ÷ 1600h| State of active voltage output, expressed in 1/512 V units –
it means that high byte express integer part, and low byte fractional part of
desired output voltage.
06h| No| -999 ÷ 9999| Peak (drop) value (no decimal point)
10h| Yes| 0 ÷ 5| “ tyPE ” parameter in the “ InPt ” menu (nominal
input range). 0 – 0-20 mA range; 1 – 4-20 mA range; 2 – 0-10 V
range; 3 – 2-10 V range; 4 – 0-5 V range; 5 – 1-5 V range
11h| Yes| 0 ÷ 5| “ CHAr ” parameter in the “ InPt ” menu
(characteristic type) 0 – linear; 1 – square; 2 – square root;
3 – user-defined; 4 – volume characteristics of a cylindrical tank in
the vertical position; 5 – volume characteristics of a cylindrical tank in
the horizontal position
12h| Yes| 0 ÷ 5| “ FiLt ” parameter in the “ InPt ” menu (measurement
filtering rate)
RS485 Modbus Programming
Register | Write | Range | Register description |
---|---|---|---|
13h | Yes | 0 ÷ 3 | “ Pnt ”parameter in “ InPt ” menu (the copy of 03h |
register, decimal point position) 0 – “ 0 ”; 1 – “ 0.0 ”;
2 – “ 0.00 ”; 3 – “ 0.000 ”
14h| Yes| -999 ÷ 9999| “ Lo C ” parameter in “ InPt ” menu, no decimal
point included
15h| Yes| -999 ÷ 9999| “ Hi C ” parameter in the “ InPt ” menu, no
decimal point included
16h| Yes| 0 ÷ 999| “ Lo r ” parameter in the “ InPt ” menu, in 0.1%
17h| Yes| 0 ÷ 199| “ Hi r ” parameter in the “ InPt ” menu, in 0.1%
19h| Yes| 0 ÷ 9999| “ t h1 ” parameter in the “ InPt ” menu, no
decimal point included
1Ah| Yes| 0 ÷ 9999| “ t h2 ” parameter in the “ InPt ” menu, no
decimal point included
1Bh| Yes| 0 ÷ 9999| “ t h3 ” parameter in the “ InPt ” menu, no
decimal point included
1Ch| Yes| 0 ÷ 9999| “ t d ” parameter in the “ InPt ” menu, no decimal
point included
1Dh| Yes| 0 ÷ 9999| “ t Sn ” parameter in the “ InPt ” menu, no
decimal point included
1Eh| Yes| 0 ÷ 9999| “ t Sh ” parameter in the “ InPt ” menu, no
decimal point included
20h2| Yes| 0 ÷ 199| Device address
21h| No| 21F0h| Device identification code (ID)
22h3| Yes| 0 ÷ 7| “bAud” parameter in “rS” menu (baud rate);
0 – 1200 baud; 1 – 2400 baud; 2 – 4800 baud; 3 – 9600 baud;
4 – 19200 baud; 5 – 38400 baud; 6 – 57600 baud; 7 – 115200 baud
23h4| Yes| 0 ÷ 1| “mbAc” parameter in “rS” menu (permission to write
registers via RS-485 interface); 0 – write denied ; 1 – write allowed
24h| Yes| see descr.| Parameters of “ SECU ” menu (binary format (0 – „
oFF ”, 1 – „ on ”): bit 0 – “ A r1 ” parameter; bit 1 – “
A r2 ” parameter
25h| Yes| 0 ÷ 5| “rESP” parameter in “rS” menu (additional response
delay);
0 – no additional delay; 1 – ” 10c ” option; 2 – ” 20c ” option;
3 – ” 50c ” option; 4 – ” 100c ” option; 5 – ” 200c ” option;
27h| Yes| 0 ÷ 99| “mbtO” parameter in “rS” menu (maximum delay between received frames); 0 – no delay checking;
1 ÷ 99 – maximum delay expressed in seconds
2Dh| Yes| 1 ÷ 8| “ Bri ” parameter (display brightness);
1 – the lowest brightness; 8 – the highest brightness
2Fh| Yes| 0 ÷ 1| “ Edit ” parameter (numerical parameters edit mode);
0 – „ dig ” mode; 1 – „ SLid ” mode
30h| Yes| -999 ÷ 9999| “ SEtP ” parameter in “ rEL1 ” menu, no decimal
point included
31h| Yes| -999 ÷ 999| “ HySt ” parameter in “ rEL1 ” menu, no decimal
point included
32h| Yes| 0 ÷ 5| “ modE ” parameter in the “ rEL1 ” menu:
0 – “ no ” mode; 1 – “ on ” mode; 2 – “ of ” mode; 3 – “ in ” mode;
4 – “ out ” mode; 5 – “ mod ” mode
33h| Yes| 0 ÷ 999| The “t on” parameter in the “rEL1” menu, expressed in tenth of seconds or tenth of minutes depends on the “unit” parameter – register no. 35h)
RS485 Modbus Programming
Register | Write | Range | Register description |
---|---|---|---|
34h | Yes | 0 ÷ 999 | The “toFF” parameter in the “rEL1” menu, expressed |
in a tenth of seconds or tenth of minutes depends on the “unit” parameter
– register no. 35h)
35h| Yes| 0 ÷ 1| “unit” parameter in the “rEL1” menu:
0 – seconds; 1 – minutes
36h| Yes| 0 ÷ 2| “AL” parameter in the “rEL1” menu: 0 – no
changes; 1 – on; 2 – off
37h| Yes| -999 ÷ 9999| “ SEt2 ” parameter in “ rEL1 ” menu, no decimal
point included
38h| Yes| -999 ÷ 9999| “ SEtP ” parameter in “ rEL2 ” menu, no decimal
point included
39h| Yes| -999 ÷ 999| “ HySt ” parameter in “ rEL2 ” menu, no decimal
point included
3Ah
| ****
Yes
| ****
0 ÷ 5
| “ modE ” parameter in the “ rEL2 ” menu:
0 – “ no ” mode; 1 – “ on ” mode; 2 – “ of ” mode; 3 – “ in ” mode;
4 – “ out ” mode; 5 – “ mode ” mode
3Bh| Yes| 0 ÷ 999| “t on” parameter in the “rEL2” menu, expressed in
a tenth of seconds or tenth of minutes depending on the “unit” parameter –
register no. 3Dh)
3Ch| Yes| 0 ÷ 999| “toFF” parameter in the “rEL2” menu, expressed in
the tenth of seconds or tenth of minutes depending on the “unit” parameter
– register no. 3Dh)
3Dh| Yes| 0 ÷ 1| “unit” parameter in the “rEL2” menu:
0 – seconds; 1 – minutes
3Eh| Yes| 0 ÷ 2| “AL” parameter in the “rEL2” menu: 0 – no
changes; 1 – on; 2 – off
3Fh| Yes| -999 ÷ 9999| “ SEt2 ” parameter in “ rEL2 ” menu, no decimal
point included
50h| Yes| 0 ÷ 1| “ modE ” parameter in “ HOLd ” menu (type of detected
changes):
0 – peaks; 1 – drops
51h| Yes| 0 ÷ 9999| “ PEA ” parameter in “ HOLd ” menu (minimum
detectable change, no decimal point included)
52h| Yes| 0 ÷ 199| “ Time ” parameter in the “ HOLd ” menu, maximum
peaks’ (or drops’) display time expressed in seconds
53h| Yes| 0 ÷ 1| “ HdiS ” parameter in the “ HOLd ” menu:
0 – “ rEAL ” mode; 1 – “ HOLd ” mode
54h| Yes| 0 ÷ 1| “ H r1 ” parameter in “ HOLd ” menu :
0 – “ rEAL ” mode; 1 – “ HOLd ” mode
55h| Yes| 0 ÷ 1| “ H r2 ” parameter in “ HOLd ” menu:
0 – “ rEAL ” mode; 1 – “ HOLd ” mode
58h1| Yes| 0 ÷ 1| “ HOut ” parameter in the “ HOLd ” menu:
0 – “ rEAL ” mode; 1 – “ HOLd ” mode
70h5| Yes| -999 ÷ 1999| The value of the „ X ” coordinate of point no.
1 of the user-defined characteristic, expressed in 0.1%
71h5| Yes| -999 ÷ 9999| The value of the „ Y ” coordinate of point no.
1 of the user-defined characteristic, no decimal point included
72h5 ÷ 95h5| Further pairs of „ X ” – „ Y ” coordinates of points
no. 2 ÷ 19 of the user-defined characteristic
RS485 Modbus Programming
Register | Write | Range | Register description |
---|---|---|---|
96h5 | Yes | -999 ÷ 1999 | The value of the „ X ” coordinate of point **no. |
20 of the user-defined characteristics, expressed in 0.1%
97h5| Yes| -999 ÷ 9999| The value of the „ Y ” coordinate of point no.
20 of the user-defined characteristics, no decimal point included
A0h1| Yes| 0 ÷ 3| “ Omod ” parameter in the “ OUtP** ” menu (active
current output mode)
0 – current output disabled; 1 – current output enabled with 4÷20mA
mode; 2 – current output enabled with 0÷20mA mode;
3 – current output controlled via RS-485 interface
Yes| 0 ÷ 2| “ Omod ” parameter in “ OUtP ” menu (passive current
output mode) 0 – current output disabled; 1 – current output enabled
with 4÷20mA mode; 2 – current output controlled via RS-485 interface
Yes| 0 ÷ 5| “ Omod ” parameter in “ OUtP ” menu (active voltage output
mode) 0 – voltage output disabled; 1 – voltage output enabled with
0÷5V mode; 2 – voltage output enabled with 1÷5V mode; 3 –
voltage output enabled with 0÷10V mode; 4 – voltage output enabled
with 2÷10V mode; 5 – voltage output controlled via RS-485 interface
A1h1| Yes| -999 ÷ 9999| “ OUtL ” parameter in “ OUtP ” menu, no
decimal point included
A2h1| Yes| -999 ÷ 9999| “ OUtH ” parameter in the “ OUtP ” menu, no
decimal point included
A3h1| Yes| 0 ÷ 999| “ Lo r ” parameter in the “ OUtP ” menu, for
active current output and active voltage output, expressed in 0.1%
Yes| 0 ÷ 299| “ Lo r ” parameter in the “ OUtP ” menu for passive
current output, expressed in 0.1%
A4h1| Yes| 0 ÷ 199| “ Hi r ” parameter in the “ OUtP ” menu for active
and passive current output, expressed in 0.1%
Yes| 0 ÷ 99| “ Hi r ” parameter in the “ OUtP ” menu for active
voltage output, expressed in 0.1%
A5h1| Yes| 0 ÷ 3| “ AL ” parameter in the “ OUtP ” menu (active
current output value on critical exception): 0 – no change; 1 – 22.1
mA; 2 – 3.4 mA; 3 – 0 mA
Yes| 0 ÷ 2| “ AL ” parameter in the “ OUtP ” menu (passive current
output value on critical exception): 0 – no change; 1 – 22.1 mA; 2
– 3.4 mA
Yes| 0 ÷ 5| “ AL ” parameter in the “ OUtP ” menu (active voltage
output value on critical exception): 0 – no change; 1 – 11 V; 2 –
5.5; 3 – 1.2 V; 4 – 0.6 V; 5 – 0 V
- these registers are active only if the device is equipped with current or voltage output
- after writing to register no 20h the device responds with an “old” address in the message.
- after writing to register no 22h the device responds with the new baud rate.
- the value of the “mbAc” parameter is also connected to write to this register, so it is possible to block writes, but impossible to unblock writes via the RS-485 interface, The unblocking of the writes is possible from the menu level only.
- the pairs of „X -Y” coordinates may be defined for any free point. The pair is “free” (it means that a particular point is not defined) if the „X” coordinate of this point is equal to 8000h. After writing both X and Y coordinates the point is defined and used in the calculation of the result. The coordinates of any point can be changed at any time.
TRANSMISSION ERRORS DESCRIPTION
- If an error occurs while writing or reading of single register, then the device sends an error code according to Modbus RTU specifications (example message no 1).
Error codes:
- 01h – illegal function (only functions 03h, 06h and 10h are available),
- 02h – illegal register address
- 03h – illegal data value
- 08h – no write permission ( see: “mbAc” parameter)
- A0h – exceed of upper border of input range
- 60h – exceed of lower border of input range
- A0h and 60h codes can appear only during reg. 01h is reading by 03h function (read of a single register).
EXAMPLES OF QUERY/ANSWER FRAMES
- Examples apply for device with address 1. All values are represent hexadecimal.
Field description:
- ADDR Device address on Modbus network
- FUNC Function code
- REG H, L Starting address (address of the first register to read/write, Hi and Lo byte)
- COUNT H, L No. of registers to read/write (Hi and Lo byte)
- BYTE C Data byte count in answer frame
- DATA H, L Data byte (Hi and Lo byte)
- CRC L, H CRC error check (Hi and Lo byte)
Read of the displayed value (measurement), SRP-N118 device address = 01h:
ADDR | FUNC | REG H, L | COUNT H, L | CRC L, H |
---|---|---|---|---|
01 | 03 | 00 | 01 | 00 |
a) The answer (we assume that the measured result is not out of range)
ADDR | FUNC | BYTE C | DATA H, L | CRC L, H |
---|---|---|---|---|
01 | 03 | 02 | 00 | F |
- DATA HL – displayed value = 255, no decimal point.
- Decimal point position can be read from reg. 03h
b) The answer (if an error occurs).
ADDR | FUNC | ERROR | CRC L, H |
---|---|---|---|
01 | 83 | 60 | 41 |
ERROR – error code = 60h, the bottom border of the measurement range is exceeded
Read of device ID code
ADDR | FUNC | REG H, L | COUNT H, L | CRC L, H |
---|---|---|---|---|
01 | 03 | 00 | 21 | 00 |
The answer:
ADDR | FUNC | BYTE C | DATA H, L | CRC L, H |
---|---|---|---|---|
01 | 03 | 02 | 21 | F0 |
DATA – identification code (21F0h)
Change of the device address from 1 to 2 (write to reg. 20h)
ADDR | FUNC | REG H, L | DATA H, L | CRC L, H |
---|---|---|---|---|
01 | 06 | 00 | 20 | 00 |
- DATA H – 0
- DATA L – new device address (2)
The answer (the same as the message):
ADDR | FUNC | REG H, L | DATA H, L | CRC L, H |
---|---|---|---|---|
01 | 06 | 00 | 20 | 00 |
Change of baud rate of all devices connected to the net (BROADCAST message).
ADDR | FUNC | REG H, L | COUNT H, L | CRC L, H |
---|---|---|---|---|
00 | 06 | 00 | 22 | 00 |
- DATA H – 0
- DATA L – 4, new baud rate 19200 baud
- The device does not reply to BROADCAST-type messages.
Read registers 1, 2, and 3 in one message (example of reading many registries in one frame):
ADDR | FUNC | REG H, L | COUNT H, L | CRC L, H |
---|---|---|---|---|
01 | 03 | 00 | 01 | 00 |
COUNT L – the count of being read registers (max.16)
The answer:
ADDR | FUNC | BYTE C | DATA H1,L1 | DATA H2,L2 | DATA H3,L3 | CRC L, H |
---|---|---|---|---|---|---|
01 | 03 | 06 | 00 | 0A | 00 | 00 |
- DATA H1, L1 – reg. 01h (10 – displayed value ”1.0”),
- DATA H2, L2 – reg. 02h (0 – no errors),
- DATA H3, L3 – reg. 03h (1 – decimal point position ” 0.0”).
- There is no full implementation of the Modbus Protocol in the device. The functions presented above are available only.
DEFAULT AND USERS SETTINGS LIST
Parameter| Description| Default value|
User’s value| Dec. page
---|---|---|---|---
Parameters of relay R1 operation (“rEL1” menu)
SEtP| Relay R1 threshold| 20.0| | 29
SEt2| Relay R1 second threshold| 40.0| | 29
HYSt| Hysteresis of relay R1| 0.0| | 29
modE| The operation mode of relay R1| on| | 29
t on| Turn on a delay of relay R1| 0.0| | 30
toFF| Turn off the delay of relay R1| 0.0| | 30
unit| Unit of “t on” , and “toFF” parameters of relay R1| SEC| | 30
AL| Reaction to critical situation of relay R1| oFF| | 30
Parameters of relay R2 operation (“rEL2” menu)
SEtP| Relay R2 threshold| 40.0| | 29
SEt2| Relay R2 second threshold| 60.0| | 29
HYSt| Hysteresis of relay R2| 0.0| | 29
modE| The operation mode of relay R2| on| | 29
t on| Turn on the delay of relay R2| 0.0| | 30
toFF| Turn off the delay of relay R2| 0.0| | 30
unit| Unit of “t on” , and “toFF” parameters of relay R2| SEC| | 30
AL| Reaction to critical situation of relay R2| oFF| | 30
Configuration of measurement input (“input” menu)
tYPE| Input mode| „4-20”| | 31
CHAr| Conversion characteristic mode| Lin| | 31
FiLt| Filtering ratio| 0| | 31
Pnt| Decimal point position| 0.0| | 31
Lo C| Minimum displayed value (for nominal range)| 000.0| | 32
Hi C| Maximum displayed value (for nominal range)| 100.0| | 32
t h1| Height (length) first part of the tank| 00.00| | 32
t h2| Height (length) second part of the tank| 00.00| | 32
t h3| Height (length) third part of the tank| 00.00| | 32
t d| Tank diameter| 00.01| | 32
t Sn| Distance between sensor and bottom of the tank| 00.00| | 32
t Sh| Height of the sensor| 20.00| | 32
Lo r| Extension of the bottom of the nominal input range| 5.0 (%)| | 35
Parameter| Description| Default value|
User’s value| Dec. page
---|---|---|---|---
Hi r| Extension of the top of the nominal input range| 5.0 (%)| | 35
Current output configuration (“OUtP” menu)
Omod| Current output mode| „4-20” (mA)| | 37
OUtL| Display value for 4 mA current output| 0.0| | 37
OUtH| Display value for 20 mA current output| 100.0| | 37
Lo r| Extension of the bottom of the nominal output range| 5.0 (%)| | 38
Hi r| Extension of the top of the nominal output range| 5.0 (%)| | 38
AL| Current output value on critical exception| 22.1 (mA)| | 38
Display Parameters
bri| Display brightness| bri6| | 38
Configuration of peaks detection function (“HOLd” menu)
modE| Kind of detected changes| norm| | 39
PEA| Minimum detected change| 0.0| | 39
Time| Maximum time of peak displaying| 0.0| | 39
HdiS| The type of displayed value| HOLd| | 39
H r1| Source of relay R1, and LED R1 control| rEAL| | 39
H r2| Source of relay R2, and LED R2 control| rEAL| | 39
HOut| Source of current output control| rEAL| | 39
Settings of access to the configuration parameters (“SECu” menu)
A r1| Permission to changes of relay R1 threshold without the user password
knowledge| on| | 39
A r2| Permission to changes of relay R2 threshold without the user password
knowledge| on| | 39
RS 485 interface configuration (menu “rS”)
Address| Device address| 0| | 40
bAud| Baud rate| 9.6| | 40
MBA| Permission to changes of configuration registers| on| | 40
MB to| Maximum delay between received messages| 0| | 40
rESP| Additional delay of answer transmission| Std| | 40
Configuration of numerical parameters edition
Edit| Numerical parameters edit mode| dig| | 41
24-0222 © Icon Process Controls Ltd.
Documents / Resources
| ICON
PROCESS CONTROLS TVL Series Tank Level Display and
Controller
[pdf] Owner's Manual
TVL Series Tank Level Display and Controller, TVL Series, Tank Level Display
and Controller, Display and Controller, Controller
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>