SALTO WRDx0E4 series Design XS Reader Installation Guide
- July 9, 2024
- SALTO
Table of Contents
SALTO WRDx0E4 series Design XS Reader
Specifications
- Model: WRDx0E4.. series, WRDx0E4..K series, WRDx0E4..V series
- Dimensions: 95.5mm x 95.5mm
- Installation Types: Standard electrical flush-mounted box
- Power Consumption:
- Reader: 150 mA
- Reader + Keyboard: 250 mA
- Cable Types and Maximum Distances:
- UTP Cat5e 2 pairs: 328ft (100m)
- UTP Cat5e 4 pairs : 820ft (250m)
- Twisted pairs AWG18: 1312ft (400m)
Product Usage Instructions
Installation:
- Prepare the standard electrical flush-mounted box for installation.
- Follow the provided template for accurate positioning of the XS Reader.
- Secure the XS Reader using the provided screws (PZ1 and TORX 10).
Electrical Characteristics:
- Ensure the operating temperature is within the specified range for your model.
- Connect the reader according to the cable types and distances mentioned in the specifications.
Maintenance:
- Regularly check the power consumption to ensure proper functioning.
- Keep the reader clean and free from dust accumulation.
FAQ
-
What cable type should I use for connecting the reader?
It is recommended to use UTP Cat5e cables with 2 pairs for shorter distances and twisted pairs AWG18 for longer distances. -
Can I connect a keyboard to the reader?
Yes, you can connect a keyboard to the reader, but ensure the total power consumption does not exceed 250 mA.
DIMENSION
Installation
Gang electrical standard box
Electrical characteristics
Operation conditions
Min. | Max. | Unit |
---|---|---|
Temperature WRD0M – WRD0MK | -35 | +66 |
-31 | +150 | °F |
Temperature WRD0J – WRD0GK – WRD0JK | -25 | +66 |
-13 | +150 | °F |
Humidity | 35 | 85 % |
RF characteristics
Min | Cen. | Max | Unit |
---|
RFID frequency
Bluetooth Smart 2.4 frequency
| 13.56
2.445
|
2.483
| Mhz
Ghz
Power Consumption Note 1
Min | Max | Unit |
---|---|---|
Reader | 150 | mA |
Reader+Keyboard | 250 | mA |
Note 1: Installer must take this data into account to dimension the
CU42xx power supply.
Readers only for use with the SALTO Control Units.
Cable type and mx. distances
Cable type| Reader| Reader
+ Keyboard
---|---|---
UTP Cat5e 2 pairs
AWG24
| 328ft
100m
| 196ft
60m
UTP Cat5e 4 pairs AWG24 +
SP224861/SP224895
| 820ft 250m| 492ft 150m
Twisted pairs
AWG18 Note2
| 1312ft
400m
| 918ft
280m
Installation example
Installation example: CU42xx:
Cable connection
B | Green |
---|---|
A | White |
Black | |
+V | Red |
Installation example CU42xx with RJ45
Installation example CU41xY:
Installation example CU41xY with RJ45:
SIGNALLING
Signal | Light | Time (sec) | Buzzer | Time (sec) |
---|---|---|---|---|
Card Rejection | Red | 1 | High pitched 50/50 | 1 |
Privacy or emergency status | Red 5x(50/50×3+off300) | 3 | High pitched | |
5x(50/50×3 + off 300) | 3 | |||
Standard opening | Green | 1 | Low pitched | 0,3 |
Standard locking | Red | 0,5 | Low pitched | 0,2 |
Open plus office | Green 400/200 | 2,4 | High pitched/Low pitched 400/200 | 2,4 |
CLR Button | Orange | Cont. | High pitched | Cont. |
Reset | Orange 50/100 | 450 msg | Low pitched 50/100 | 450 msg |
Read User Manual Online (PDF format)