alula HUBPLUS Wireless Alarm Panel Instruction Manual
- July 4, 2024
- alula
Table of Contents
alula HUBPLUS Wireless Alarm Panel
Connectivity Troubleshooting
Symptom | Troubleshooting Steps |
---|---|
Network Connectivity LED Off | Ethernet Connections |
- Ensure the Ethernet cable is fully inserted in both the panel and router/ modem.
Wi-Fi Connections
- Ensure the Wi-Fi card is properly installed, and the Power LED on the card is pulsing.
- Ensure the panel has been configured with the proper Wi-Fi credentials and the Wi-Fi LED on the expansion card is on solid. If the LED is blinking either the network is not in range, or the Wi-Fi credentials are incorrect (refer to System Setup – Step 5).
Cellular Connections
- Ensure the Cellular card is properly installed, and the Power LED on the card is pulsing.
- Inspect the LED on the expansion card.
- A solid LED indicates the panel is connected to the network.
- A flashing LED indicates the panel has found a tower, and is attempting to connect to the network. Wait until the LED is solid. If the LED has been double flashing for more than ten minutes, try power cycling the panel.
Alula Platform or Central Station Connectivity LED Off|
- Ensure the Network Connectivity LED is on. If it is off, see the network connectivity troubleshooting section above.
- Ensure port UDP 1234 is open in the router/modem settings.
- Ensure the panel is registered to an account with Alula and the account is active.
System Firmware Update LED Off| 1. Ensure port UDP 1235 is open in the router/modem settings. The panel and peripherals will not be able to receive firmware updates if this port isn’t available or is already in use.
System Maintenance
System testing should be performed after installation is completed and whenever a problem occurs.
Smoke and CO alarms should be tested after installed and weekly by pressing the test button on the alarm. The panel will indicate it has properly received a test signal by sounding a temporal three sound for a Smoke alarm or a temporal four sound for a CO alarm.
Critical functions and communication links of the system are automatically monitored and exercised to detect trouble conditions
User Information – Definitions
Report Delay : Consult with your installer to determine if your system is
configured with a communicator delay. A communicator delay will prevent a
report to the central station if the control panel is disarmed within _____
seconds (default is 30 seconds) after an intrusion alarm is triggered. Note
that fire-type alarms and Carbon Monoxide alarms are normally reported without
a delay.
Exit Delay: The period of time allowed, after Arming a security system,
to exit the entry/exit door without tripping an alarm. Note: Enabling silent
exit doubles the exit delay time.
Entry Delay: The door used to enter the premise will start an entry delay
when tripped. You will hear entry delay beeps when you trip the sensor: this
will allow you time to disarm the system. Entering a user code will disarm the
system.
Entry Delay Progress: Three beeps every four seconds and three beeps
every two seconds during the last ten seconds of entry delay.
Exit Delay Progress: Two beeps every two seconds and two beeps every
second during last ten seconds of exit delay time.
System Acknowledgment: Sounders will sound one beep to confirm disarm,
two beeps to confirm stay arming and four beeps to confirm away arming.
Exit Delay Restart: The feature will recognize when you arm the system,
leave your house and then quickly re-enter. If this happens, the system will
restart your exit delay to give you the full exit delay again.
Auto Stay Arming: Determines whether the system automatically arms
down to Stay if you arm the system to Away without exiting the system
entry/exit door. This feature will not be enabled when arming from a keyfob.
Arming Level – Disarm: In this level, only 24-hour sensors are
active.
Arming Level – Stay: Perimeter sensors are active. Interior sensors
are not active.
Arming Level – Away: Perimeter and interior sensors are active.
Panic Alarm: To trigger panic alarm from Keypad, press and hold stay and
away buttons at the same time.
Alarm Abort: If the panel beeps three times after disarming an alarm,
then the alarm is aborted.
Alarm Cancel Report: If an alarm has previously been transmitted, a
cancel signal will be transmitted when the alarm system is disarmed. The panel
will sound two beeps three seconds after disarming when sending a cancel
message.
Alarm Memory: After canceling an alarm, press status on Keypad to view
alarm memory.
Duress Code: The user uses a unique code, which disarms the system and
transmits a “Duress” alarm to the monitoring center.
Cross Zoning : Refers to two different sensors that must be tripped
within two minutes of each other to report an alarm to the central station.
When motion is detected by the first sensor, it starts a two minute timer. If
the other sensors trip within two minutes, an alarm report will be sent to the
central station.
Swinger Shutdown: This setting determines how many times the sensor will
go into alarm during a single arming period. Once the sensor is in swinger
mode it will not be active again until the alarm is canceled.
Note: Swinger shutdown does not affect Fire and Carbon Monoxide sensors.
Fire Alarm Verification: The panel immediately reports to the central station when a smoke alarm goes into alarm. With this option on, if a single smoke alarm goes into alarm, the panel will not report for 60 seconds unless another smoke alarm goes into alarm. If the first smoke alarm is cleared of an alarm within the first 60 seconds, no report will be sent to the central station unless it or a second smoke alarm goes into alarm within 5 minutes.
User Information – Testing the System
Before testing alarms, contact your central station and tell them you are
testing the system.
Central station phone number ___
System account number ____
Test door/window sensors by first closing all doors and windows that have
sensors. Verify the display on the keypad or mobile app indicates the system
is in the ready state. Trip each sensor by opening the door or window and
verify it shows open at the keypad or on the mobile app.
Test smoke alarms by pressing the test button until smoke alarm sounds.
Check mobile app activity to verify fire walk test signal was reported. (The
sirens will play one cycle of the temporal 3 siren pattern when a smoke test
is pressed).
Test CO alarmss by pressing the test button until CO alarm sounds. Check
mobile app activity to verify CO test signal was reported. (The sirens will
play one cycle of the temporal 4 siren cadence when a CO test is pressed.)
Test glassbreak sensors using a glass break sound tester to trip sensor.
Testing Panic Alarms: Panic alarms will be reported to the central
station and will cause the panel siren to sound. Ensure your central station
knows you are testing the system. Press the panic button and verify the system
goes into alarm. To test panic alarms on the RE656 Keypad and RE652 PINPad,
press and hold the stay and away arming buttons to trigger a panic alarm.
Test panel communication by verifying the alarms you tripped were
reported to and received by the central station.
When finished, remember to tell the central station you are done testing the system.
WARNING
HIS UNIT INCLUDES AN ALARM VERIFICATION FEATURE THAT WILL RESULT IN A DELAY OF
THE SYSTEM ALARM SIGNAL FROM THE INDICATED CIRCUITS. THE TOTAL DELAY (CONTROL
UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60 SECONDS. NO OTHER SMOKE
DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS.
All equipment necessary for the transmission of alarm, trouble, supervisory and other signals located at the residence shall have a secondary power capacity of 24 hours.
Specifications
PHYSICAL
Housing Body Dimensions Housing Base Dimensions Weight with Battery Mounting
Fastener| 8.9 x 8.9 x 1.5 inches (22.6 x 22.6 x 3.8 cm)
8.2 x 1.3 x 2.7 inches (20.8 x 3.3 x 6.7 cm)
26.8 ounces (760 grams)
6 or #8 screws (not provided)
ENVIRONMENTAL
Operating Temperature
Storage Temperature
Maximum Humidity| 32 to 120 °F (0 to 49 °C)
-4 to 86 °F (-20 to 30 °C)
85% non-condensing relative humidity
PANEL SPECIFICATIONS
Radio Frequencies
Power Supply Part Number Input
Output
Battery Part Number Backup Specifications
Battery Charger Current Draw Tamper Indications Sensors
Interface Devices
Maximum Number of Users Siren| 433.92MHz, 2.4GHz
RE012-6 (US), RE012-7 (AUS), RE012-8 (CE)
100-240VAC, 50/60 Hz, 0.5A
12VDC, 1A
RE029
24 hours minimum (4 hours minimum for RE6130)
6VDC, 2.5Ah, NiMH
25mA (Trickle), 95mA (Fast) 150mA (Normal), 300mA (Alarm) Cover opening and
Wall removal
Up to 96 Connect+ Compatible Wireless Security Zones
Up to 8 PINPads (RE652), up to 8 keypads (RE656) and/or mobile devices, up to
8 Touchpads
49
Meet/exceed UL required 85dBA at 10 feet performance requirements
CERTIFICATIONS
HUB-PLUS-AC-V, HUB-PLUS-AC-A| FCC, IC
Specifications subject to change without notice.
TRADEMARKS
-
Alula, Connect+, Connect+Pro, Connect-FLX, Connect-XiP and AlulaConnect are trademarks owned by Alula Holdings, LLC. Verizon is a trademark of Verizon Trademark Services LLC. AT&T is a trademark of AT&T Intellectual Property II, L.P. Wi-Fi is a trademark of
The Wi-Fi Alliance. Z-Wave is a registered trademark of Silicon Labs. -
All trademarks, logos, product names, service names and brand names are the property of their respective owners.
-
All trademarks, logos, product names, service names and brand names used in this document are for identification purposes only.
Use of these trademarks, logos, product names, service names and brand names does not imply endorsement.
FCC NOTICE
This device complies with Part 15 of the FCC rules. Operation is subject to
the following two conditions:
- This device may not cause harmful interference.
- This device must accept any interference that may be received, including interference that may cause undesired operation. Changes or modifications not expressly approved by Alula could void the user’s authority to operate this equipment.
NOTE : This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
—Reorient or relocate the receiving antenna.
—Increase the separation between the equipment and receiver.
—Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
—Consult the dealer or an experienced radio/TV technician for help.
FCC ID: U5X-HUBPLUS
Contains FCC ID: RI7ME310G1WW
Contains FCC ID: 2AC7Z-ESP32WROOM32E
Contains FCC ID: U5X-RE934Z
ISED
This device contains licence-exempt transmitter(s)/receiver(s) that comply
with Innovation, Science and Economic Development Canada’s licence-exempt
RSS(s). Operation is subject to the following two conditions:
- This device may not cause interference.
- This device must accept any interference, including interference that may cause undesired operation of the device.
CAN ICES-003(B)
IC: 8310A-HUBPLUS
Contains IC: 5131A-ME310G1WW
Contains IC: 21098-ESPWROOM32E
Contains IC: 8310A-RE934Z
RF Exposure Notice
In order to comply with FCC and ISED RF Exposure requirements, a minimum
separation distance of 20 cm must be maintained between the device and all
persons during normal operation.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>