EnerSys Perfect Plus Water Less ATEX Batteries Instruction Manual
- June 3, 2024
- EnerSys
Table of Contents
- Introduction
- Safety
- Service
- Handling
- Taking delivery of your battery
- Commissioning
- Recommended maintenance
- Annually
- Discharge
- Recharge
- Measurement of specific gravity
- Temperature
- Surrounding area conditions
- Effect of explosive atmosphere on materials
- Protection against other hazards
- Hazards arising from different ignition sources
- Withstanding attack by aggressive substances
- Care of the battery
- Storage
- Malfunctions
- Aquamatic water refilling system (optional accessory)
- Electrolyte circulation system (optional accessory)
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Instructions for use
Hawker®
Perfect Plus ™ /
Water Less ®
ATEX certified batteries
Instructions for use Hawker® Perfect PlusTM / Water Less® ATEX
Motive power batteries Ex certified increased safety “e”
Operation and Instruction Manual
Introduction
These Hawker® ATEX certified batteries are certified for use in areas with risks of explosion due to gas or dust.
- Explosion group I Category M2/Mb mining
- Explosion group II Category 2 and 3 [Zone 1 2G/Gb, Zone 2 3G/Gc (Gas)]
- Explosion group III Category 2 and 3 [Zone 21 2D/Db, Zone 22 3D/Dc (Dust)]
They should be in perfect condition and free from any damage. If any damage is noted or accessories missing please contact your supplier within the first 24 hours of receiving this product. Ex traction batteries are designed for use in battery powered applications within hazardous areas : such as electric counter balance, reach and pallet trucks also floor sweepers and other cleaning equipment. The cells and connectors comply with IP (ingress protection) 65, the crates with IP23. The patented ventilation design makes it possible for these traction batteries to fit within existing DIN and British standard crate sizes, offering the same capacity, as specified, by the truck manufacturer.
Standard
Motive power Hawker Atex certified batteries comply with the ATEX Directive
2014/34/EU.
Conformity has been demonstrated with reference to the following documentation
:
EC type-examination certificates:
ATEX
• SIRA 01ATEX3016U
• SIRA 01ATEX3019U
• SIRA 01ATEX3022X
• SIRA 01ATEX3025X| IECEx
• SIRA IECEx 07.0061U
• SIRA IECEx 07.0062U
• SIRA IECEx 07.0065X
• SIRA IECEx 07.0066X| Description
• Flooded BS cell
• Flooded DIN cell
• Batteries up to 68.8 kWh
• Batteries above 68.8 up to 153.6 kWh
---|---|---
ATEX certificates apply to the EEx and IECEx certificates apply to the rest of
the world except North America (USA and Canada).
Quality Assurance Notification:
Sira 01 ATEX M103
Condition of use
Do not charge in a hazardous Area
Example of battery labelling
Rating Data
1. Nominal capacity C5 | : See type plate |
---|---|
2. Nominal voltage | : 2.0 V x No of cells |
3. Nominal discharge current | : C5/5h |
4. Nominal S.G. of electrolyte* | : 1.29 kg/l |
5. Rated temperature | : 30°C |
6. Nominal electrolyte level
*Will be reached within the first 10 cycles| : up to electrolyte level mark ”max.”
| • Pay attention to the operating instructions and keep them close to the
battery.
• Work on batteries must only be carried out by skilled personnel!
---|---
| • Use protective glasses and wear safety clothing when working on batteries.
• Adhere to the current accident prevention rules in the country where the
battery is used or
EN 62485-3, EN 50110-1.
| • No smoking!
• Do not expose batteries to naked flames, glowing embers or sparks, as it may
cause the battery to explode.
| • Acid splashes in the eyes or on the skin must be washed with water. In
case of accident
consult a doctor immediately!
• Clothing contaminated by acid should be washed in water.
| • Risk of explosion and fire, avoid short circuits!
• Caution: Metal parts of the battery are always live.
Do not place tools or other metal objects on the battery!
| • Electrolyte is highly corrosive.
| • Batteries and cells are heavy. Ensure secure installation!
• Use only suitable handling equipment e.g. lifting gear in accordance with
VDI 3616.
| • Dangerous electrical voltage!
| • Pay attention to the hazards that can be caused by batteries.
Ignoring the operation instructions, repair with non-original parts or using additives for the electrolyte will render the warranty void. All the failures, malfunctions or defects of the battery, charger any other accessories, must be notified to our After Sales Service.
Safety
Always remember that the battery is a source of power, even when fully discharged there remains sufficient energy in the battery to cause serious damage.
Follow these safety codes
- Never charge a Ex battery in the zoned controlled area.
- Never disconnect the battery in a zoned area. Isolate circuits before disconnecting the battery outside a zoned area.
- Never open the battery cover in a zoned area.
- Always use certified DC plugs for connection to the battery.
- Never use the battery if damaged or bare cables are evident.
- Never use the battery if the DC plugs are damaged.
- Never attempt to repair the battery: Call your recommended authorised service centre.
- Close vent plugs lids firmly when topping the batteries electrolyte has been completed.
Service
Your local authorised service engineer provides local help and support. This handbook gives guidelines of a general nature; our engineer will help you to interpret your needs in relationship to your particular requirements. Your authorised engineer can answer the questions that are beyond the scope of this manual and obtain specialist help should it be required. Your battery is an expensive investment and designed for use in a zoned area, it is our aim to help you obtain the best possible results from it. Please do not hesitate to call your local service centre if you have any questions relating to the battery.
Handling
Lead acid Ex batteries are very heavy. Always use approved moving equipment when attempting to change batteries. When lifting and handling the Ex batteries use the correct approved lifting equipment and keep the battery in an up right position. Due to the wide variation in types of electric vehicles, designs of battery containers, equipment used and methods of battery changing, it is not possible to give detailed instructions on the procedures to be followed when changing the batteries on an electric vehicle. The manufacturer of the vehicle or the battery changing equipment must supply the correct method and procedure.
Taking delivery of your battery
Do not carry out any of the following procedures in a zoned area. The possibility of the battery being connected in the wrong polarity is prevented by visibly marking the polarities adjacent to the connection plug with an identification colour (Positive Red and Negative Blue). The possibility of the insulation on the overall battery voltage leads being cut to expose the conductor is prevented by sleeving the insulation with cable retention (i.e. spiral wrap). Please ensure that the battery containers are always upright so that the electrolyte is not spilled. Remove all packing material and carefully examine the containers, etc. to ensure that there is no physical damage. If the battery is not used at receipt, please refer to (17) storage.
Commissioning
For commissioning of unfilled batteries, see separate instructions. The level
of the electrolyte must be checked. If it is below the anti-surge baffle or
the top of the separator it must first be topped up to this height with
purified water (IEC 62877-1:2016). The charger cables must be connected to
ensure a good contact, taking care that the polarity is correct. Otherwise
battery, vehicle or charger could be damaged. Wipe over the tops and sides of
the cells and container with a damp cloth to remove dust, water or spilt
sulphuric acid. Cell cleanliness can not be too highly stressed. Check that
all connections are tight.
The specified torque loading for the pole screws is 25 + 2Nm (screw M10). Make
sure that the cells are readily accessible for testing and topping up if the
automatic watering facility is not fitted. This will make regular maintenance
hassle free. Check that the battery compartment is well drained and ventilated
and that there is no risk of metal objects dropping through the top
ventilation of the battery. Check that the battery sits quite firmly and
securely in its housing, use suitable packing to prevent any movement when the
vehicle is in motion. The cables should be flexible and of sufficient length
to prevent any strain being imposed either on the cable or the certified
terminals to which the cables are connected. Smear any steel runners or
supports, which support the battery container with petroleum jelly. This will
keep down the possibility of rust and acid corrosion and extend the life of
these components.
If a new Ex battery is to be used in an application where there is uncertainty
about the zoned area please contact your local factory inspector.
Never directly connect an electrical appliance (for example: warning beacon)
to some cells of the battery. This could lead to an imbalance of the cells
during the recharge, i.e. a loss of capacity, the risk of insufficient
discharge time, damage to the cells and this may EFFECT THE WARRANTY OF THE
BATTERY.
The battery is then charged as in item (8). The electrolyte should be topped
up to the specified level with purified water (item 6.).
Recommended maintenance
Every day:
Recharge the battery after discharge.
-
Remember never charge an Ex battery in a zoned area
even if approved charging equipment is available. Always check that the charger is operating correctly. -
Check the electrolyte levels at the end of charge and top up if necessary ( respect max level). The correct level is to the top of the level indicator.
Hawker® Perfect Plus™
If too much water is added, the expansion during recharge will cause the
electrolyte to overflow, therefore weakening the strength of the electrolyte.
If insufficient water is added the top of the plates will be come exposed,
reducing the performance and life of the battery.
Use approved distilled or demineralised water only.
The `Standard’ of purity of water required for topping up is given in IEC
62877-1:2016.
Suppliers of topping up water, topping up devices or automatic water filling
systems can be obtained from your local supplier or service depot. Note that
topping up water must only be held in and dispensed from non-metallic
containers.
Never top up with acid. Should it be felt that an acid adjustment is required,
please consult your local service depot.
Weekly:
- Please note any cells that are taking too much or too little water, if this occurs please contact your local service depot.
- Check all connections and take off leads for any frayed or worn insulation. If frayed wires or worn insulation is noted take the battery out of service immediately and place in a safe area that is outside the zoned area. Do not attempt to repair a Ex battery. Call your local service depot.
- Check that all insulators and vent plugs are in place and that the battery plugs are of sound condition.
Ensure that the top of the battery is clean and dry. Dirt and moisture can provide tracking paths for the electricity and potentially cause a spark in a zoned area. Should there be any corrosion of the metal container, scrape this off and neutralise the area with a solution of water and baking soda, or diluted ammonia, and protect the part from further corrosion by painting it with acid proof paint.
Monthly:
At the end of the charge the voltages of all cells should be measured with the
charger switched on, and recorded. After charging has been completed, the
electrolyte density, electrolyte temperature as well as the filling level of
all cells are to be measured and recorded. If significant changes from earlier
measurements or differences between the cells are found further testing and
maintenance by the service department should be requested. This should be done
following a complete charge and minimum of 2 hours rest time.
Measure and record:
- total voltage
- voltage per cell
- if the voltage readings are irregular, also check the S.G. of each cell
If significant changes from earlier measurements or differences between the cells or bloc batteries are found, please contact Ener Sys Service.
- If the discharge time of the battery is not sufficient, check:
- That the work required is compatible with the battery capacity
- The settings of the charger
- The settings of the discharge limiter.
Hawker® Perfect Plus and Water Less®
Check the electrolyte level and top up if necessary (respect maximum level according to drawing above).
Water Less topping up intervals
PzM Variant | **Water topping up intervals*** |
---|---|
1 shift operation | 3 shift operation** |
4Weeks | PzM/PzMB plus 50Hz |
8 Weeks | PzM/PzMB plus HF |
13 Weeks | PzM/PzMB plus EC*** & HF |
80% DOD, 5 operating days per week, and average battery temperatures of 20°C
- +/- 1 week in the most common applications at 20°C
** this number of cycles can be reduced if operating 3 shift and with high battery temperatures!
*** Electrolyte Circulation
Annually
In accordance with EN 1175-1 at least once per year, the insulation resistance
of the truck and the battery must be checked by an electrical specialist. The
tests on the insulation resistance of the battery must be conducted in
accordance with EN 1987 part1. The insulation resistance of the battery thus
determined must not be below a value of 50 per Volt of nominal voltage, in
compliance with EN 62485-3. For batteries up to 120V nominal voltage the
minimum value is 1000.
Proceed to the maintenance, including the measurement of electrolyte S.G. at
the end of charge. The filter of the air pump has to be checked during the
annual maintenance and eventually to be cleaned or replaced. Earlier
replacement of the filter is necessary if, for undefined reasons (no leaks in
the air pipes) the defect signal of the air mixing system on the charger or on
the battery (on DC air pump or remote signal) is illuminated. During the
annual maintenance, check the correct operation of. the air pump.
Discharge
Be sure that all ventilation holes are not sealed or covered. Electrical connections (e.g. plugs) must only be made or broken in the open circuit condition. To achieve the optimum life for the battery, operating discharges of more than 80% of the rated capacity should be avoided (deep discharge). This corresponds to an electrolyte specific gravity of 1.14 kg/l at 30°C at the end of the discharge. Discharged batteries must be recharged immediately and must not be left discharged. This also applies to partially discharged batteries. It is recommended that the battery is discharged evenly and the use of tappings across a part of the battery is discouraged. To overcome this problem a D.C.- D.C. converter must be used to allow auxiliary loads to be supplied from the whole battery. Note: The D.C.-D.C. converter must be certified for use in a zoned area as well as the auxiliary equipment. Battery performance is directly related to temperature. Batteries are rated at 30ºC. Where the battery temperature is lower than this, the available performance is reduced. Additional capacity is therefore required when the batteries are to be used in areas of low ambient temperatures (e.g. cold stores).
Recharge
Note: Never recharge an Ex battery in a zoned area.
Only direct current must be used for charging. All charging procedures in
accordance with DIN 41773-1 and DIN 41774 are permitted. Only connect the
battery assigned to a charger, suitable for the size of battery, in order to
avoid overloading of the electric cables and contacts, unacceptable gassing
and the escape of electrolyte from the cells. In the gassing stage the current
limits given in EN 62485-3 must not be exceeded. If the charger was not
purchased together with the battery it is best to have its suitability checked
by the manufacturers service department. When charging, proper provision must
be made for venting of the charging gases. Doors, battery container lids and
the covers of battery compartments must be opened or removed. During the
charge the battery must be removed from the closed battery compartment on the
truck. The ventilation must comply to EN 62485-3 standard. The vent plugs
should stay on the cells and remain closed. With the charger switched off
connect up the battery, ensuring that the polarity is correct. (positive to
positive, negative to negative). Now switch on the charger. When charging the
temperature of the electrolyte rises by about 10°C, so charging should only
begin if the electrolyte temperature is below 43°C.
The electrolyte temperature of batteries should be at least +10°C before
charging otherwise a full charge will not be achieved. The charge is
considered as finished when the specific gravity of the electrolyte and the
battery voltage have remained constant for two hours.
Batteries fitted with electrolyte mixing (option): If the warning light on the
pump controller is illuminated or if a defect signal on the electrolyte
circulation system appears, check that the piping system is connected and
examine the piping circuit for leaks or defects. (see 6. Maintenance)
The air pipe should never be removed during charge. Excessive charging reduces
battery life, increases water loss from the battery and wastes electricity. It
is important to ensure that charger gassing times are not extended without
prior consultation from your supplier.
The length of the D.C. cable between the charger and battery affects the
voltage drop back to the control unit of the charger. The cable should not be
extended without prior consultation with the charger manufacturer and supplier
of your Ex battery. In situations where the battery is generally only very
lightly discharged, it may be an option to recharge the battery at less
frequent intervals, perhaps every second day. In such circumstances please
seek the advice or your local service engineer.
Do not disconnect battery until the charger has been switched off.
Your local area service centre must approve any managing charging system
otherwise the warranty may be invalidated.
Equalizing
Some chargers have an equalising facility; either a manual operation or an
automatic control.
For full operational procedures for the charger see manufactures instruction.
But remember never charge an Ex battery in a zoned area at any time.
Equalising charges are used to safeguard the life of the battery and to
maintain its capacity. They are necessary after deep discharges, repeated
incomplete recharges and charges to an IU characteristic curve. Equalising
charges are carried out following normal charging. The charging current must
not exceed 5 A/100 Ah of rated capacity (end of charge). Watch the
temperature!
Measurement of specific gravity
To take a hydrometer reading the bulb is squeezed, the end of the rubber tube
is dipped into the electrolyte and the bulb is gently released so as to draw
up sufficient liquid so that the float moves freely. The hydrometer must be
held in a vertical position and there should be no pressure on the rubber
bulb. When reading the hydrometer to measure the specific gravity, the liquid
level shows the value on the scale, which is printed on the float. After
reading, the rubber bulb should be squeezed to return the electrolyte to the
cell.
The rated specific gravity (S. G.) of the electrolyte is related to a
temperature of 30°C and the nominal electrolyte level in the cell in fully
charged condition. Higher temperatures reduce the specified gravity of the
electrolyte, lower temperatures increase it. The temperature correction factor
is -0.0007 kg/l per °C, e.g. an electrolyte specific gravity of 1.28 kg/l at
45°C corresponds to an S.G. of 1.29 kg/l at 30°C.The electrolyte must conform
to the purity regulations in IEC 62877-2:2016.
Temperature
An electrolyte temperature of 30°C is specified as the rated temperature.
Higher temperatures shorten the life of the battery, lower temperatures reduce
the capacity available. 55°C is the upper temperature limit and is not
acceptable as an operating temperature.
The temperature on surface must never exceed 80°C in explosive area. Charging
should only begin if the electrolyte temperature is below 43°C. If electrolyte
temperature reaches 55°C during the charge, wait for the cooling before to use
the battery in the explosive area. If a hot battery is detected it should be
taken out of the controlled zoned area and allowed to cool to ambient
temperature.
An investigation should be carried out into why the battery is getting hot
before it is placed back into service. Possible reasons why the battery might
be getting hot is that there might be a fault in the equipment that the
battery is powering or a fault could have occurred within the cells of the
battery. In the case of a suspected battery problem contact your local service
centre.
Surrounding area conditions
The apparatus is designed to cope with the intended surrounding area conditions.
Effect of explosive atmosphere on materials
The materials selected are not known to react with any explosive atmospheres to which the apparatus may be subjected.
Protection against other hazards
The apparatus does not cause injury or harm when used as specified in the installation and operation manual.
Hazards arising from different ignition sources
The apparatus does not produce ignition capable electrical sparks or arcs. The apparatus has also been designed not to produce potential ignition sources from electromagnetic, acoustic, optical or other such external energy sources.
Withstanding attack by aggressive substances
The individual cells contains sulphuric acid: These cells and enclosure which make up the apparatus are constructed from materials that are resistant to acid attack see manufactures data sheet.
Care of the battery
The battery should always be kept clean and dry to prevent tracking currents. Any liquid in the battery tray must be extracted and disposed of in the prescribed manner. Damage to the insulation of the tray should be repaired after cleaning, to ensure that the insulation value complies with EN 62485-3. and to prevent tray corrosion. If it is necessary to remove cells it is best to call in our service department for this.
Storage
If batteries are taken out of service for a lengthy period they should be stored in the fully charged condition in a dry, frostfree room. To ensure the battery is always ready for use a choice of charging methods can be made:
- a monthly equalising charge as in point 8, or
- float charging at a charging voltage of 2.27 V x the number of cells.
The storage time should be taken into account when considering the life of the battery.
Malfunctions
If malfunctions are found on the battery or the charger our service department should be called in without delay. The measurements taken in point 6.3. will facilitate fault finding and their elimination. A service contract with us will make it easier to detect and correct faults in good time.
Aquamatic water refilling system (optional accessory)
1. Application
The water refilling system is used to automatically maintain the nominal
electrolyte levels. The charging gasses escape through the vent on each cell.
2. Function
A valve and a float together control the topping up process and maintain
the correct water level in each dell. The valve allows the flow of water into
each cell and the float closes the valve when the correct water level has been
reached. For faultfree operation of the water refilling system, please note
the instructions below:
- If manual connection is used the battery should only be connected to the filling system once a week.
- If automatic coupling is used (with a magnetic valve controlled by the charging apparatus) the charger main switch selects the correct moment for filling. Note: In this case we recommend a water refilling at least once a week to ensure the right level of the electrolyte.
- In multiple shift and warm ambient temperature operations, it may be necessary to have shorter topping up intervals.
Manual or automatic connection
The battery should be topped up shortly before completion of a full charge,
as at this point the battery has reached a defined operational state resulting
in satisfactory electrolyte circulation. Filling takes place when the
connector (7) from the tank is connected to the coupling (6) on the battery.
Filling time
Filling time depends on the utilisation rate and the corresponding battery
temperature. Generally speaking, the top up process takes a few minutes and
can vary according to the battery range; after this, if manual filling is
being used, the water supply to the battery should be turned off.
1. tank
2. outflow connector with ball valve
3. plug with magnetic valve
4. plug with ball valve
5. flow control| 6. coupling
7. connector
8. battery charger
9. charger main switch
---|---
Working pressure
The water refilling system should be installed in such a way that a water
pressure of 0.2 to 0.6 bar is obtained (with at least 2 m height difference
between the upper edge of the battery and the lower edge of the tank). Any
deviation from this means that the system will not function properly.
Purity
The topping up water must be purified. The water used to refill the
batteries must have a conductance of not more than 30 µS/ cm. The tank and
pipes must be cleaned before operating the system.
Pipe system on the battery
The pipe system to the individual battery cells must follow the battery’s
electrical circuit. This reduces the risk of current leakage in the presence
of electrolytic gas causing an explosion (EN 62485-3). A maximum of 10 cells
may be connected in a series. The system should not be modified in any way.
Working temperature
In winter, batteries fitted with Aquamatic should only be charged or
refilled in a room temperature above 0 °C.
Flow control
A flow indicator built into the water supply pipe to the battery monitors
the filling process. During filling the water flow causes the built-in disc in
the flow indicator to turn. When all the plugs are closed the disc stops,
indicating that the filling process is complete.
Electrolyte circulation system (optional accessory)
1. Application
The electrolyte circulation system is based on the principle of pumping air
into the individual battery cells. This system prevents electrolyte
stratification and the battery charge is optimised using a charge factor of
1.07. The electrolyte circulation is particularly beneficial for heavy duty
use, short charge times, boost or opportunity charging and in high ambient
temperatures.
2. Function
The electrolyte circulation consists of a pipe system fitted in the cells. An
Aeromatic diaphragm pump is fitted in the charger or separately mounted on the
battery or vehicle. This diaphragm pump sends a low rate airflow into each
cell which creates a circulating air stream inside the cell box. The air
stream is continuous or pulsed depending on the battery voltage and pump type.
The air supply is adjusted in accordance to the number of cells in the
battery. The pipe system to the individual battery cells must follow the
existing electrical circuit. This reduces the risk of current leakage in the
presence of electrolytic gas causing an explosion (EN 62485-3).
3. Maintenance of air filter
Depending on the working conditions, the pump air filter should be changed at
least once a year. In work areas with high levels of air-pollution, the filter
should be checked and replaced more frequently.
4. Repair and maintenance
The system must be checked for leakage. The Hawker charger will display an
error message to indicate leakage. Sometimes in the case of leakage the
characteristic charging curve is switched over to the characteristic standard
curve (without electrolyte circulation).
In case of faulty parts, contact EnerSys service. Only EnerSys original spare
parts may be used, as these are designed for the pump air supply and will
ensure correct functioning of the pump.
Disposal and back to the manufacturer!
Always dispose of the battery container and cells through your local service
depot. Do not attempt to dismantle the battery or the cells in any way. Once
the product has failed and is no longer repairable store outside the Zoned
area until removed for reclaim.
Batteries with this sign must be recycled.
Batteries which are not returned for the recycling process must be disposed of
as hazardous waste!
When using motive power batteries and chargers, the operator must comply
with the current standards, laws,rules, and regulations in force in the
country of use! ****
Publication No. EMEA-EN-IO-HAW-WL-0921 / Subject to revisions without prior notice. E. &O.E.
EnerSys® , the global leader in stored energy solutions for industrial applications, manufactures and distributes Reserve Power and Motive Power batteries, battery chargers, power equipment, battery accessories and outdoor equipment enclosure solutions to customers worldwide.
Motive Power batteries and chargers are utilized in electric forklift trucks and other commercial electric powered vehicles. Reserve Power batteries are used in the telecommunication and utility industries, uninterruptible power supplies, and numerous applications requiring stored energy solutions including medical, aerospace and defense systems. With the recent Alpha acquisition, EnerSys® provides highly integrated power solutions and services to broadband, telecom, renewable and industrial customers.
Outdoor equipment enclosure products are utilized in the telecommunication,
cable, utility, transportation industries and by government and defense
customers.
The company also provides aftermarket and customer support services to its
customers from over 100 countries through its sales and manufacturing
locations around the world.
EnerSys EMEA
EH Europe GmbH Baarerstrasse 18 6300 Zug Switzerland
Please refer to the website address for details of your nearest EnerSys
office: www.enersys.com
© 2022 EnerSys. All rights reserved. All trademarks and logos are the property
of or licensed to EnerSys and its affiliates unless otherwise noted.