EnerSys NexSys Batteries Introducing Instruction Manual
- May 15, 2024
- EnerSys
Table of Contents
NexSys® TPPL ATEX
Instruction Manual
Introduction
Valve regulated lead acid (VRLA), Thin Plate Pure Lead (TPPL) NexSys® TPPL batteries are certified to ATEX standards (increased safety concept Ex e) for use in hazardous areas where there is a risk of explosion, due to gas or dust. These batteries are part of the following equipment groups and categories:
- Group I, category M2/Mb
- Group II, categories 2 and 3 (Zone 1 2G/Gb, Zone 2 3G/Gc)
- Group III, categories 2 and 3 (Zone 21 2D/Db and Zone 22 3D/Dc)
Relative to conventional ATEX batteries, the patented ventilation design of
EnerSys battery trays may make it possible for a higher capacity battery to be
selected for a given truck manufacturer’s available battery compartment.
Unlike conventional batteries with liquid electrolyte, NexSys® TPPL ATEX
batteries are valve-regulated lead-acid batteries with immobilised
electrolyte. Instead of a vent plug, a valve is used to regulate the internal
gas pressure, preventing the ingress of oxygen from the air and allowing the
escape of excess charging gasses.
Operating VRLA batteries require similar safety precautions as vented
batteries, specifically there are risks associated with electrical, corrosive
and explosive hazards. Battery valves must never be removed. These batteries
do not require topping up with distilled or demineralised water.
This manual should be used in conjunction with the manual for standard NexSys®
TPPL batteries which is available on
www.enersys.com.
Upon receipt, batteries should be in perfect condition and free from any
damage. If any damage is noted or accessories are missing, please contact your
supplier immediately.
ATEX-certified NexSys batteries are designed for use in battery-powered
applications (such as electric counterbalance, reach and pallet trucks) within
hazardous areas. EnerSys cells and connectors have an IP (ingress protection)
of 65; creates of 23 (when lids fitted).
The use of electrical equipment, such as DC-DC convertors, low voltage alarms
and EnerSys’ Wi-iQ units, is prohibited unless certified for use in hazardous
areas and fi tted outside the battery.
Conformity
NexSys® TPPL ATEX batteries conform with the relevant provision of ATEX
Directive 2014/34/EU.
Conformity has been demonstrated with reference to the following
documentation:
ATEX | IECEx | Certificate Description |
---|---|---|
SIRA 01ATEX3022X | SIRA IECEx 07.0065X | Batteries up to 68.8 kWh |
SIRA 03ATEX3090U | SIRA IECEx 07.0064U | DIN-size NexSys (and Gel) cells |
Notes:
- ATEX certificates apply to the EU whilst IECEx certificates relate to the rest of the world (except North America).
- Quality assurance notification: SIRA 01 ATEX M103.
The applicable rating data for NexSys® TPPL ATEX batteries is as follows:
- Nominal capacity C₅: See type plate
- Nominal voltage: See type plate
- Discharge current: C₅/5h
- Rated temperature: 30°C
These cells comply with the following clauses:
EN/IEC 60079-0 clause 23.3 (Cell types), 23.6 (Interchangeability), 23.8
(Leakage)’ 23.9 (Connections), 23.10 (Orientation) and 23.11 (Replacement of
cells or batteries), and EN/IEC 60079-7 clause 5.6 (classification), 5.6.3.1
(Types of permissible batteries), 5.6.3.3 (cells), 5.6.3.4 (connections) and
6.6.3 (shock test).
When they are assembled into a battery, the remaining clauses of EN/IEC
60079-7 need to be addressed with particular reference to clauses EN/IEC
60079-0 clause 23.2 (Batteries), 23.4 (Cells in a battery), 23.5 (Rating of a
battery), 23.11(Replacement of cells or batteries), and EN/IEC 60079-7 clause
5.6.3.2 (Battery containers), 5.6.4 (Charging of cells and batteries), 6.6.2
(insulation resistance) and 6.6.4 (ventilation).
The cells covered by this certificate shall be installed in series, in a
suitable battery enclosure, together with cells of the same electrochemical
system, cell design and rated capacitance that is manufactured by EnerSys. The
battery enclosure shall provide protection from mechanical impact;
The cells shall be installed in a vertical orientation, with the electrical
connectors at the top.
This equipment includes non-conducting parts that may generate an ignition-
capable level of electrostatic charges under certain extreme conditions. The
user shall ensure that the equipment is not installed in a location where it
may be subjected to external conditions (such as high-pressure steam) which
might cause a build-up of electrostatic charges on nonconducting surfaces.
Additionally, cleaning of the equipment shall be done only with a damp cloth;
The cells shall have a certified service temperature range of -20°C to +60°C,
which shall be taken into account when used in a battery. Battery operating
conditions take precedence.
Condition of use
Do not charge in a hazardous area
An example of NexSys® TPPL ATEX label
Safety
| • Pay attention to the operating instructions and keep them close to the
battery.
• Work on batteries must only be carried out by skilled personnel!
---|---
| • Use protective glasses and wear safety clothing when working on batteries.
• Adhere to the current accident prevention rules in the country where the
battery is used or EN 62485-3, EN 50110-1.
| • No smoking!
• Do not expose batteries to naked flames, glowing embers or sparks, as it may
cause the battery to explode.
• Avoid sparks from cables or electrical apparatus as well as electrostatic
discharges.
| • Acid splashes into the eyes or on the skin must be washed immediately with
an abundance of clean water. After abundant flushing consult a doctor
immediately!
• Clothing contaminated by acid should be washed in water.
| • Risk of explosion and fire.
• Avoid short circuits: do not use non-insulated tools, do not place or drop
metal objects on top of the battery.
• Remove rings, wristwatches and articles of clothing with metal parts that
might come into contact with the battery terminals.
| • Electrolyte is highly corrosive.
• In the normal operation of this battery a contact with acid isn’t possible.
If the cell containers are damaged, the immobilized electrolyte (absorbed in
the separator) is corrosive like the liquid electrolyte.
| • Batteries are heavy. Ensure secure installation!
Use only suitable handling equipment.
• Lifting hooks must not damage the cells, connectors or cables.
• Do not place batteries in direct sunlight without protection. Discharged
batteries can freeze. For that reason, always store in a frost-free zone.
| • Dangerous electrical voltage!
• Avoid short circuits: NexSys batteries are capable of high short circuit
currents.
• Caution – metal parts of the battery are always live: do not place tools or
other objects on the battery!
| • Pay attention to the hazards that can be caused by batteries.
Any work carried out on the battery must comply with EN 60079-19 and EnerSys®
operating instructions. All defective parts must be replaced by EnerSys
supplied parts. No attempt should be made to repair faulty parts. Failure to
adhere to this will render the warranty and certification null and void.
Always remember that the battery is a source of power. Even when fully
discharged, sufficient energy re mains in the battery to cause serious damage.
The battery is designed to be used within the intended surrounding area
conditions.
The materials used are not known to react with any of the explosive
atmospheres with which they may come in contact with. If unsure, please
contact EnerSys.
The apparatus does not cause injury or harm when used as specified in this
manual and the standard NexSys® TPPL battery manual.
The apparatus does not produce ignition-capable electrical sparks or arcs when
used in compliance with this instruction manual. The apparatus has been
designed not to produce potential ignition sources from electromagnetic,
acoustic, optical or other external energy sources.
Individual cells contain sulphuric acid. These cells are constructed from
materials that are resistant to acid attack.
Follow the safety practices below:
- Never charge NexSys® TPPL ATEX battery in a zoned controlled area unless special conditions, defined by equipment manufacturers, are met.
- Never disconnect a battery under load in a zoned area.
- Never open the battery cover (if present) in a zoned area.
- Always use certified DC plugs for connection to the battery.
- Never use the battery if damaged or bare cables are visible.
- Never use the battery if the DC plugs are damaged.
- Never attempt to service the battery: call your recommended authorised service centre.
- Any servicing carried out must be in accordance with ATEX directives.
- Never mix cells of different types or capacities within one battery.
Service
Your local authorised service engineer provides help and support. This handbook gives guidelines of a general nature; the engineer will help you to interpret your needs in relation to your particular requirements. Your engineer can answer the questions that are beyond the scope of this manual. Please do not hesitate to call your local service centre if you have any questions relating to your battery.
Handling
As NexSys® TPPL ATEX batteries are heavy, always use the appropriate equipment when attempting to handle batteries. When lifting and handling NexSys® TPPL ATEX batteries, use the appropriate, approved lifting equipment and keep the battery in an upright position. Due to the wide range of types of electric vehicles, of designs of battery containers, of equipment used and in methods of battery changing, it is not possible to give detailed instructions on the procedures to be followed when changing the batteries on a specific electric vehicle. The manufacturer of the vehicle or the battery changing equipment must supply the correct method and procedure.
Taking delivery of your battery
Remove all packaging and carefully examine the complete battery to ensure that there is no physical damage. Should the battery not be put in service immediately, please refer to storage guidelines (section 9).
Commissioning
NexSys® TPPL ATEX batteries are supplied in a charged condition. Check the following:
- The cleanliness of the battery and the vehicle’s battery compartment.
- Ensure systems are in place to prevent your battery being connected to the improper charging equipment. Ensure all connections are correct and that positive and negative polarities, which are clearly indicated on plugs, are respected. Improper connection may result in damage to the battery, vehicle or charger.
- Ensure that any charging equipment is suitable for use with NexSys® TPPL ATEX batteries.
- Charge the battery before first use.
- Should there be any uncertainty regarding the nature of the hazardous area, please contact the equipment representative.
Operation
6.1 Operational safety
Batteries should be used in accordance with the EN 62485-3 standard (“Safety
requirements for secondary batteries and battery installations – Part 3”) and
Directive 1999/92/EC (“Minimum requirements for improving the health and
safety protection of workers potentially at risk from explosive atmospheres”).
6.2 Operating conditions
The ATEX-approved operating temperature range is -20°C to 40°C.
The lifetime of the battery depends on a number of operating conditions, in
particular the operating temperature and depth of discharge. Optimal battery
life is obtained with the battery at a temperature between +15°C and +35°C to
maximise performance and battery life. High temperatures shorten the life of
the battery, low temperatures reduce the available capacity.
Operating at a depth of discharge of 60% or less will maximise the battery
lifetime. The maximum permissible discharge is 80% of C₅ nominal capacity.
From new, the battery reaches its full capacity after approximately three
charge/discharge cycles.
6.3 Discharging
The valves on the top of the battery must not be sealed or covered. Electrical
connections (e.g. plugs) must only be connected or disconnected in the open
circuit condition (without load). Discharges over 80% of the rated capacity
are categorised as deep discharges and are not acceptable as they
significantly reduce the life expectancy of the battery. Discharged batteries
MUST be recharged immediately and MUST not be left in a discharged condition.
Note: The following statement only applies to partially discharged
batteries.
Discharged batteries can freeze. Limit the discharge to a maximum of 80% depth
of discharge (DOD). The cycle life of the battery will depend on the DOD; the
higher the DOD, the shorter the cycle life. The presence of a discharge
limiter on the vehicle is necessary.
When discharged with currents in the range of I₁ to I₅, the following energy
cut-off settings must be used:
- 60% DOD 1.96V
- 80% DOD 1.92V
At lower currents please seek advice from EnerSys.
6.4 Charging
Note: Never recharge a NexSys® TPPL ATEX battery in a zoned area unless
special conditions, defined by equipment manufacturers, are met.
NexSys® TPPL ATEX batteries must be charged using appropriate EnerSys
chargers. Using nonspecified chargers will invalidate the warranty. NexSys®
TPPL ATEX batteries are suitable for both standard duty and heavy-duty
applications. In standard duty applications the charger (0.2-0.25 charging
rate) will recharge the battery from 80% depth of discharge in approximately
six hours.
Short opportunity charges are allowed (one opportunity charge is permitted
between main charges with a maximum energy throughput of 100% C₅)
Charging Rate| From 80% Depth of Discharge to Full Charge| From 60% Depth of
Discharge to
Full Charge| From 40% State of Charge to 80% State of Charge
---|---|---|---
0.25 C₅| 5.5 hours| 4.75 hours| 1.6 hours
0.20 C₅| 6.25 hours| 5.25 hours| 2 hours
Under normal circumstances NexSys® TPPL ATEX batteries have extremely low gas
emissions. For safety purposes, when calculating gas emission levels, use 1.5A
/ 100Ah C₅. Provision must be made for venting of the charging gases. When
charging, doors, battery container covers (when present) and the covers of
battery compartments must be opened or removed. Ventilation openings must not
be sealed or covered. Electrical connections (e.g. plugs) must only be
connected or disconnected under open circuit condition. To charge the battery,
connect it to the charger ensuring the charger is switched off. Ensure
positive and negative polarities are correct. NexSys® TPPL ATEX batteries must
receive their full charge at least once a week.
6.5 Equalising charge
NexSys®, NexSys® + and Lifespeed iQ™ chargers will automatically provide an
equalising charge, following a normal full charge (conditions embedded into
the charging profile).
Maintenance
As the electrolyte is immobilised its density cannot be measured. Never remove
safety valves from cells. In case of accidental damage to valves, contact
EnerSys® for replacement.
7.1 Daily
Recharge the battery after every discharge. Check the condition of the plugs,
cables and that all insulation covers are in place and in good condition. If
any damage is visible, take the battery out of service immediately and place
it in a safe area outside the hazardous zone. Do not attempt to repair NexSys®
TPPL ATEX battery unless qualified to do so. Call EnerSys or your authorised
service representative for assistance.
7.2 Weekly
Visually inspect the battery for signs of dirt and mechanical damage to all
component parts. Pay attention to the battery charging plugs and cables.
7.3 Quarterly
It is recommended to carry out voltage readings at the end of charge as well
as to measure and record:
- The voltage of the complete battery
- The voltage of each cell
If significant changes from earlier measurements or differences between cells
are found, please contact EnerSys service.
If the runtime of the battery is not as expected, check the following:
- That the required application matches the battery capacity
- The settings of the charger
- If necessary, the settings of the discharge limiter on the vehicle.
7.4 Annually
Remove dust from the battery. Test all connections (sockets, cables and
contacts). The insulation resistance of the truck and the battery must be
checked by an electrical specialist in accordance with EN 1175-1 at least once
per year. Tests on the insulation resistance of the battery must be conducted
in accordance with EN 1987-1. The minimum insulation resistance must be 50Ω
per Volt of nominal voltage and the minimum battery resistance must not be
below 1kΩ regardless of voltage (ref. EN 62485-3 standard).
The integrity of crates should also be monitored to ensure that lifting
equipment has not caused any damage. Any lifting hole present on the tray must
be checked for potential damage. No sign of any deformation should be visible.
Care of the battery
The battery should always be kept clean and dry to prevent tracking currents.
Cleaning must be done in accordance with the ZVEI code of practice “The
Cleaning of Vehicle Traction batteries”. Any liquid in the battery tray must
be extracted and disposed of in the correct manner. Damage to the insulation
of the tray should be repaired after cleaning, to ensure that the insulation
value complies with EN 62485-3 and to prevent tray corrosion.
Should it be necessary to remove cells, please contact EnerSys service.
Storage
Batteries are dispatched from the manufacturer in a fully charged condition.
The state of charge will decrease with the storage time. Due to parasitic
chemical reactions all batteries lose their stored energy when allowed to
stand on open circuit. The rate of self-discharge is non-linear and increases
with decreasing state of charge. High temperatures greatly reduce storage life
as they increase the rate of self-discharge. If the truck/vehicle is not going
to be used for periods in excess of 48 hours, the ignition key must be removed
and any auxiliary equipment (such as lights, beacons, on-board computer, etc)
must be switched off.
The standard storage time for a battery not installed on a truck is one month
without the need to recharge. The maximum storage time is 6 months at 20°C
provided the battery is fully charged when put into storage and that other
equipment that could cause the battery to discharge is disconnected. It is
advisable to conduct an inspection and open circuit voltage check after three
months and implement a refresh charge if necessary.
Faults
If faults are found on the battery or the charger, EnerSys service should be called in without delay. The measurements taken in point 7.3 will facilitate fault finding and their correction. A service contract with EnerSys will make it easier to detect and correct faults and ensure the battery performs at its best.
Back to the manufacturer!
Batteries with this sign must be recycled.
Batteries which are not returned for the recycling process must be disposed of
as hazardous waste!
ABOUT ENERSYS®
EnerSys, the global leader in stored energy solutions for industrial
applications, manufactures and distributes energy systems solutions and motive
power batteries, specialty batteries, battery chargers, power equipment,
battery accessories and outdoor equipment enclosure solutions to customers
worldwide.
Energy Systems, which combine enclosures, power conversion, power distribution
and energy storage, are used in the telecommunication, broadband and utility
industries, uninterruptible power supplies, and numerous applications.
Motive Power batteries and chargers are utilized in electric forklift trucks
and other industrial electric powered vehicles requiring stored energy
solutions. Specialty batteries are used in aerospace and defense applications,
large over-the-road trucks, premium automotive, medical and security systems
applications.
EnerSys also provides aftermarket and customer support services to its
customers in over 100 countries through its sales and manufacturing locations
around the world. With the recent NorthStar acquisition, EnerSys has
solidified its position as the market leader for premium Thin Plate Pure Lead
batteries which are sold across all three lines of business.
More information regarding EnerSys can be found at
www.enersys.com.
EnerSys EMEA
EH Europe GmbH
Baarerstrasse 18
6300 Zug
Switzerland
Please refer to the website address for details of your nearest EnerSys
office: www.enersys.com
© 2022 EnerSys. All rights reserved. Trademarks and logos are the property of
EnerSys and its affiliates unless otherwise noted.
Subject to revisions without prior notice. E.&O.E.
EMEA-EN-IU-NEX-ATEX-0222
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>