easee 7,4kW Charging Station Instructions
- June 24, 2024
- easee
Table of Contents
easee 7,4kW Charging Station
Content
Technical documentation of residual current protection in accordance with IEC 60364, for charging station Easee Home and Easee Charge.
Summary
IEC 60364-7-722:2018 describes methods for residual current protection. The charging station uses the following method:
- The use of an RCD type A in conjunction with a residual direct current detecting device (RDC-DD) complying with IEC 62955.
Easee ASA declares that the charging station will disconnect the power supply if DC fault current exceeds 6 mA. In combination with an internal RCD Type A, this will provide equivalent or higher protection compared to an RCD Type B.
This document is a functional description of how the charging station achieves protection in accordance with IEC 60364:2018. The document contains excerpts from the technical documentation made available for TÜV Rheinland, and that has been used as the basis for testing and type certification in accordance with EN IEC 61851-1: 2019.
Residual current protection
The charging station has an internal RCD Type A in accordance with IEC 60947-2. The charging station contains equipment for the detection of DC residual currents (RDC-DD) in accordance with IEC 62955. Disconnection in the event of DC fault currents above 6 mA is ensured through a common switch, which breaks the control current to all the internal relays for simultaneous opening.
The internal DC fault protection is automatically tested at startup, between each charging session or at least every 24 hours. The disconnection times are faster than using a modular Type B device.
System| 50V < U0 ≤ 120V s| 120V < U0 ≤ 230V s| 230V < U0 ≤
400V s
---|---|---|---
AC| DC| AC| DC| AC| DC
TN| 0,8| a)| 0,4| 1| 0,2| 0,4
TT| 0,3| a)| 0,2| 0,4| 0,07| 0,2
IT| 0,8| a)| 0,4| 1| 0,3| 0,4
Table 1: Maximum disconnection times for fault currents above 5 IΔn
In cases where a ground fault is detected, the LED indicator on the charging station will turn red, all relays will open, thus isolating the output to the Type-2 connector. The RCD is reset by disconnecting the charging cable. When the Type-2 connector is not connected to both the charging station and the electric vehicle, all relay contacts are always open.
The disconnection times for ground faults comply with the requirements in IEC 60364-4-41, section 411.3.2.2, for TN-, TT-, and IT-supply systems. The disconnection time for IT supply in Table 1 is derived from Norwegian standard NEK 400, based on IEC 60364.
Technical design
Table 2 provides an overview of the main requirements for the standards used, and performance parameters.
Critical fault mode alarm
In the event of a voltage error on the vehicle, voltage error due to a ground fault, or relay error, the charging station will enter critical fault mode with audio and visual signals and will not be usable. The critical fault mode cannot be reset by the user but must be examined by Easee support.
In the event of a critical fault mode, the opening of relays will be ensured through two separate systems, thereby providing redundancy and increased safety before or during an ongoing charging session.
Temperature monitoring
The charging station is equipped with internal temperature sensors that initiate actions in response to unexpected temperature rises. Should the temperature exceed a predefined safety limit will the charging station automatically shut down to prevent overheating, and the user will receive a notification.
Technical performance and design parameters
Parameter | RCCB | RDC-DD | Easee |
---|---|---|---|
Standard | EN 60947-2 | IEC 62955 | EN 61008-2 + IEC 62955 |
Classification | Type A | RDC-MD (4.11.3) | Type A + RDC-DD |
AC trigger level | 15-30 mA | 30-60 mA | 15-30 mA |
DC trigger level | N/A | 3-6 mA | 3-6 mA |
Rated current | 10-32 A | 16-125 A | 32 A |
Rated voltage | 400 V | 400 V | 400 V |
Rated impulse voltage | 4 kV | 4 kV | 4 kV |
Break time 30 mA AC | 300 ms | N/A | <200 ms |
Break time 60 mA AC | 150 ms | 300 ms | <1a00 ms |
Break time 150 mA AC | 40 ms | 80 ms | <30 ms |
Break time 5 A DC | N/A | 80 ms | <30 ms |
Break time 6 mA DC | N/A | 10 s | <500 ms |
Break time 60mA DC | N/A | 300 ms | <100 ms |
Break time 200mA DC | N/A | 100 ms | < 30 ms |
Table 2: RCD Performance overview and key parameters
An RCD detection module is used to detect both AC and DC fault currents. An additional fault signal will be active if an internal error is detected in the module. Any of the three fault signals will cause all relays to open, thereby isolating the Type-2 connector from the input current, including the neutral conductor.
Function
The opening of relays in the event of a ground fault is designed as a dual-
channel system to provide redundancy and thereby increase reliability in case
of failure. A ground fault can be indicated by the sensor, whether it is a
fault current of 6 milliamperes direct current (DC), 30 milliamperes
alternating current (AC), or a fault in the sensor itself.
When such a fault is detected, signals are sent to both a Microcontroller Unit
(MCU) and a Complex Programmable Logic Device (CPLD). These two units will
immediately open all relays by disconnecting the 12-volt control voltage to
the relays. This is done through their own, separate breaking circuits, which
are connected in series and controlled completely independently of each other.
This means that in the event of a fault in the MCU unit or its software (SW),
the CPLD unit will still open the relays.
Similarly, if a fault occurs in the CPLD unit, the MCU unit will still ensure
that the relays are opened. This system ensures that a ground fault will
always lead to the relays being opened, even if one of the channels fails,
thereby significantly increasing safety.
The purpose of this document is to describe the ground fault protection for the charging station, to achieve safety levels in accordance with IEC 60364:2018. Easee asserts that the information in this document is correct. Beyond this, Easee ASA, or its subsidiaries, do not assume any responsibility related to the use of the information in the document.
No part of this publication may be republished, reproduced, transmitted, or
reused in any other form, by any means or in any format, for your own or
third-party use, unless otherwise agreed in writing with Easee or its
subsidiaries.
Any permitted use must always be in accordance with good practice and ensure
that no harm can be done to Easee, or by misleading the consumer.
Easee and Easee products, product names, trademarks, and slogans, whether registered or not, are the intellectual property of Easee and may not be used without Easee’s prior written permission. All other mentioned products and services may be trademarks or service marks of their respective owners.
April 2024 – Version 1.00
© 2024 by Easee ASA. All rights reserved.
CUSTOMER SUPPORT
Easee ASA
Vassbotnen 23
4033 Stavanger, Norway
www.easee.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>