Searchline Excel Plus Device Type Manager
Introduction
The purpose of this document is to support the plant operators with commissioning, operation, configuration and diagnosis of the Searchline Excel Plus & Edge detector. The Searchline Excel Plus & Edge is an OpenPath Flammable Hydrocarbon Gas Detector (OPFHGD) certified for use in potentially explosive atmospheres. The advanced optical element design provides additional resistance to certain adverse effects of the operating environment, ensuring that your plant is compliant, your personnel are protected and your production process can deliver maximum uptime. The Searchline Excel Plus & Edge device can be configured and operated by a Device Type Manager (DTM) that provides an easy-to-use user interface for accessing device variables, configuration parameters and diagnostic information. The Searchline Excel Plus & Edge DTM offers the combination of FDT and EDDL technologies and a uniform user interface according to the FDT style guide. It is a full-featured DTM device that carries the standard EDD-Interpreter components to execute the EDD during runtime. Because it is using existing device descriptions, plant operators will experience a familiar operating concept in the DTM.
WARNING
For safety reasons this equipment must be operated by qualified personnel
only. Read and understand the instruction manual completely before operating
or servicing the equipment. For information regarding the Searchline Excel
Plus & Edge device, check the Searchline Excel Plus & Edge Technical Manual.
Every effort has been made to ensure the accuracy of this document, however,
Honeywell Analytics can assume no responsibility for any errors or omissions
in this document or their consequences.
Honeywell Analytics would greatly appreciate being informed of any errors or
omissions that may be found in the content of this document.
For information not covered in this document, or if there is a requirement to
send comments/corrections about this document, contact Honeywell Analytics
using the contact details given on the back page.
Honeywell Analytics reserve the right to change or revise the information
supplied in this document without notice and without obligation to notify any
person or organization of such revision or change. If information is required
that does not appear in this document, contact the local distributor/agent or
Honeywell Analytics.
Software Installation
2.1 Required software / software components
In order to be able to use the Searchline Excel Plus & Edge HART DTM and to go
online with the device user needs the following components:
- FDT Frame application (PACTware or some other FDT application supporting FDT 1.2.x)
- HART Communication DTM (it represents the communication means needed for connecting the field devices to the automation software). There are multiple options available for download on the Internet.
- Honeywell Analytics HART DTM Library
- Microsoft .NET Framework (.NET 2.0)
- HART modem (RS232 or USB interfaces of the companies Endress+Hauser, Microflex or MACTek) or HART multiplexer
This user manual describes the case of using PACTware as FDT frame application and HART Communication DTM. Screen images captured from FDT frame application are of PACTware 5.0.
2.2 Downloads
2.2.1 PACTware
- Go to http://www.pactware.com, select English language
- Select Service > Download Area
- Select a free-of-charge PACTware download link
- Follow the link and download PACTware 5.X
2.2.2 HART Communication DTM
- Search on the Internet for an appropriate version of the software.
2.2.3 Honeywell Analytics HART DTM Library
- Go to the Honeywell Analytics website www.sps.honeywell.com
- Search for Searchline Excel Plus or Searchline Excel Edge and select as appropriate
- Scroll to the Software section, download Searchline Excel Plus & Edge™ DTM Toolkit
2.2.4 HART modem or multiplexer driver
- User needs HART modem driver
- User needs HART multiplexer DTM library
- Contact the manufacturer to get the driver or DTM library
2.3 System requirements
2.3.1 System resources
Proper execution of the DTMs requires a standard PC with at least following
system resources:
- 1 GHz or faster 32-bit (x86) or 64-bit (x64) processor with at least 2 cores
- 1 GB RAM (32-bit) or 2 GB RAM (64-bit)
- Screen Resolution at least 1024×768 pixels
2.3.2 Operating systems
The DTM has been released under the following operating systems:
- Windows 10 (19-03)
2.3.3 Hard disk space
The Honeywell Analytics DTM Library HART requires approx. 50 MB hard disk
space.
2.4 Installing DTM setup
- Install the Frame Application PACTware (see §2.2.1)
- Install the HART Communication DTM (see §2.2.2)
2.5 Installing Honeywell Analytics HART DTM Library
-
Launch Setup.exe.
Structure and files similar to the following example shall appear: -
On the Welcome Screen, click Next.
-
Accept the License Agreement and click Next:
-
Adjust the installation path by clicking Browse.
-
Click on Install.
-
After the Setup Wizard finishes the installation, click on Finish.
Operation
3.1 Establish connection with the device
For the electrical cabling and connections, refer to the Searchline Excel Plus
& Edge Technical Manual.
In order to use other HART interfaces such as HART Multiplexer, refer to the
relevant manufacturer’s manual.
Follow the steps below for establishing the connection with the device using a
serial HART modem and HART Communication DTM:
-
Connect the device and the serial HART modem as described in the Searchline Excel Plus & Edge
Technical Manual (download at https://sps.honeywell.com/us/en/products/safety /gas-and-flamedetection/industrial-fixed/searchline-excel-plus). -
Connect the modem connector to the PC COM port (serial modem) or USB port (USB Modem).
-
Open the PACTware frame application.
-
On the right side of the screen, click on Device Catalog.
-
Select All Devices > Device
-
Select Update device catalog.
-
Right-click on HOST PC.
-
Select Add device.
-
Select Code Wrights GmbH > Driver.
-
Click on OK.
-
Right-click on COM3 HART Communication.
-
Select Add device.
-
Select Honeywell Analytics > Device.
-
Select Searchline Excel.
-
Right-click on COM3 HART Communication
-
Select Additional functions.
-
Select Change DTM address.
-
Set up the New address as needed and confirm.
-
Click on COM 3 HART Communication.
-
Select the COM3 Parameter tab.
-
Adjust Serial Interface as needed.
-
Right-click on Searchline Excel™ Plus/Edge.
-
Select Connect.
3.2 Changing parameters
-
Right-click on Searchline Excel™ Plus/Edge.
-
Select Parameter.
-
Select Online parameterization.
-
Select Login.
-
Change login profile to Engineer. CAUTION
For product and data security, it is important that the password for ‘Engineer’ profile access is changed from the default setting.
The password is 8 digit alphanumeric (case sensitive). A full 8 digit password should be used. -
Change Password. (set to eight zeroes by default):
3.3 Switching to INHIBIT mode
CAUTION
Switch the detector to INHIBIT MODE before adjusting parameters or performing
maintenance.
-
Select Device Settings.
-
Select Inhibit Mode.
-
Select Start Inhibit. ALTERNATIVELY:
-
Select Device Settings.
-
Select Inhibit Mode Setting.
-
Select Enter Inhibit Mode.
3.4 Viewing Event History
- Select Device Settings.
- Select Device Maintenance.
- Select Event History.
- Select the Log Type.
3.5 Setting Gas Reading Units
CAUTION
Do NOT use the “(1-ratio)*100%” option.
3.6 Saving the
Project
- Click on SAVE button in the bottom right corner of the screen.
Please Note:
While every effort has been made to ensure accuracy in this publication, no
responsibility can be accepted for errors or omissions. Data may change, as
well as legislation and you are strongly advised to obtain copies of the most
recently issued regulations, standards and guidelines. This publication is not
intended to form the basis of a contract.
Find out more
www.sps.honeywell.com
Contact Honeywell Analytics:
Europe, Middle East, Africa
Life Safety Distribution GmbH
Tel: 00800 333 222 44 (Freephone no.)
Tel: +41 (0)44 943 4380 (Alternative no.)
Middle East Tel: +971 4 450 5800 (Fixed Gas Detection)
Middle East Tel: +971 4 450 5852 (Portable Gas Detection)
gasdetection@honeywell.com
Americas
Honeywell Analytics Inc.
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
detectgas@honeywell.com
Asia Pacific
Honeywell Analytics Asia Pacific Co Ltd
Tel: +82 (0) 2 6909 0300
India Tel: +91 124 4752700
China Tel: +86 10 5885 8788-3000
analytics.ap@honeywell.com
Technical Services
EMEA: HAexpert@honeywell.com
US: ha.us.service@honeywell.com
AP: ha.ap.service@honeywell.com
www.sps.honeywell.com
08/2021
2017M1264 Issue 1 EN
© 2021 Honeywell Analytics
Documents / Resources
|
Honeywell Searchline Excel Plus Device Type
Manager
[pdf] User Manual
Searchline Excel Plus Device Type Manager, Searchline Excel Plus, Device Type
Manager
---|---