ULINE H-6621 Industrial Dehumidifier User Manual

June 7, 2024
ULINE

ULINE H-6621 Industrial Dehumidifier User Manual
ULINE H-6621 Industrial Dehumidifier User Manual

TROUBLESHOOTING

OPERATING ISSUE CAUSES RECOMMENDATIONS
The unit is not working.
  • The breaker tripped.
  • The unit is plugged into a GFI protected circuit.
  • The unit is being run from a generator.
  • The extension cord is not the correct gauge for the distance run. (14 AWG up to 25′ and 12 AWG over 25′)

|

  • Reset breaker.
  • Remove from area. Excessive moisture will trip GFI.
  • Check output does not fluctuate, as the unit will not operate at low voltage.
  • Verify voltage while unit is starting. Start up will cause the highest current draw and largest voltage drop. Even if plugged directly to outlet, there can be a significant voltage drop. Never assume the voltage is okay without verifying.

The unit shuts down and displays an error code.|

  • ER 1: Overflow switch remaining closed for over two minutes.
  • Plugged or kinked drain hose.
  • Bad connection in pump circuit.
  • Defective condensate pump.
  • ER 2: Internal pressure switch indicates refrigerant pressure is too high.
  • Air filter is dirty or plugged. The coil is dirty.
  • Loose or faulty electrical connections to pressure switch.
  • Fan is not working.
  • Defective pressure switch.

|

  • Remove obstruction. Check
  • connections. Replace pump.
  • Clean or replace air filter. Clean coil.
  • Check connections.
  • Replace fan.
  • Replace pressure switch.

The unit continually ices up.

NOTE: Some ice buildup on the evaporator coil is normal, but airflow should not be blocked.

|

  • No warm air is blowing out of the back of the unit.
  • Air filter is dirty and airflow is obstructed.
  • Dirty evaporator coil.

|

  • Ambient temperature may be too low. Raise temperature with supplementary source.
  • Clean filter. Unit should have a minimum of 10″ clearance all around it.
  • Clean coil.

Unit moves some water, but not as much as expected.|

  • Air filter is dirty or airflow obstructed.
  • Evaporator coil dirty.
  • Restrictive or kinked exhaust ducting (if used).

|

  • Unit should have a minimum of 10″ clearance all around it. Clean air filter and ensure adequate airflow/space around unit.
  • Clean coil.
  • Straighten out ducting.

Fan does not run. Compressor runs briefly, but cycles on/off.|

  • Loose connection in fan circuit.
  • Fan obstructed and not turning.
  • Defective fan.
  • Defective control board.

|

  • Check connections.
  • Remove obstruction.
  • Replace fan.
  • Replace control board.

1-800-295-5510
uline.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals