165 VA Slc Shift Pinta Asennuskehys Instructions

June 10, 2024
SLC

Shift Pinta Asennuskehys
Instructions

165 VA Slc Shift Pinta Asennuskehys

Only to be installed by an authorized electrician
Power off before installing

Surface mounted

PIR Sensor
Sensor datasheet

Operating voltage AC220-240V
Power consumption 1W max
Microwave frequency
Transmission power
Detection angle 90°
Detection Area 2-3M Knob adjustable
Hold time 10S-7min Knob adjustable
Daylight sensor 10-2000Iux Knob adjustable
Stand-by DIM Level
Stand-by Period
Dimming Range
Microwave ON/OFF function
Installation Height Recessed recommended height is 2.5m
Minimum mounting distance recommended mounting distance should be more than

2m
Operating temperature(°C)| -20°C–40°C

Wiering diagram Detection range diagram

Settings

Factory settings

Detection Area| Hold Time| Daylight Sensor
100%| 10S| 10Iux

Detection area:
The detection area can be adjusted by the knob, clockwise adjustment increases the sensitivity, counterclockwise adjustment reduces the sensitivity, the maximum detection distance is 6 meters, the minimum detection distance is 2 meters.
Notice 1:The distance test is carried out under Ta25°C, 1.8 meters wall mounting installation height. The test result is based on the movement along the tangential direction of the sensor, and the detect distance can be adjusted by the dial switch.
Notice 2:Infrared sensor will be affected by temperature. Too high or too low temperature may affect the detect distance or even cause failure to sensor.
Hold time:
The hold time can be adjusted by the knob. Clockwise adjustment increases the hold time, counterclockwise adjustment reduces the hold time, the maximum hold time is 7min, and the minimum hold time is 10S.
Notice 1:The hold time counting should be started after the sensor is powered on and initialized.
Daylight sensor:
The light threshold can be selected through the Knob. Clockwise adjustment increases the light threshold, counterclockwise adjustment reduces the light threshold, the maximum light threshold is 2000lux, and the minimum light threshold is 10lux.
Notice 1:The light threshold may cause a large deviation in different lamps.

THE LIGHT GROUP AS | Tlf.: +47 38 00 21 01 | E-Mail: [email protected]
Mjavannsvegen 175 | 4628 | Kristiansand S | Norway
THE LIGHT GROUP GmbH | Phone: +49 511 807 486 10 | E-Mail: [email protected]
Am Schafbrinke 62 | 30519 | Hannover | Germany

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SLC User Manuals

Related Manuals