Altronix eFlow4NV Series Power Supply-Chargers Installation Guide
- June 3, 2024
- Altronix
Table of Contents
More than just power.™ eFlow102NV Series
Power Supply/Chargers
Installation Guide
eFlow4NV Series Power Supply-Chargers
Models Include:
eFlow102NV/ eFlow102NXV
- 10A @ 12VDC
eFlow102N8V/eFlow102NX8V
- 10A @ 12VDC
- Eight (8) Fused Outputs
eFlow102N16V/ eFlow102NX16V
- 10A @ 12VDC
- Sixteen (16) Fused Outputs
eFlow102N8DV/ eFlow102NX8DV
- 10A @ 12VDC
- Eight (8) PTC Protected Outputs
eFlow102N16DV/ eFlow102NX16DV
- 10A @ 12VDC
- Sixteen (16) PTC Protected Outputs
Overview:
Altronix eFlow102NV power supply/chargers convert a 220VAC (working range
198VAC – 256VAC), 50/60Hz input to a 12VDC nominal output (see Power Supply
Configuration Reference Chart and Specifications).
eFlow102NV Series Power Supply Configuration Reference Chart:
European Conformity
Stand-by Specifications:
Battery| Burg. Applications 4 hr. Stand-by/
15 min. Alarm| Fire Applications 24 hr. Stand-by/
5 min. Alarm| Access Control Applications Stand-by
---|---|---|---
7AH| 0.4A/10A| N/A| 5 Mins./10A
12AH| 1A/10A| 0.3A/10A| 15 Mins./10A
40AH (for eFlow102NXV refer to Fig. 8, pg. 10)| 6A/10A| 1.2A/10A| Over 2
Hours/10A
65AH (for eFlow102NXV refer to Fig. 8, pg. 10)| 6A/10A| 1.5A/10A| Over 4
Hours/10A
Specifications:
Input:
- 220VAC (working range 198VAC – 256VAC), 50/60Hz.
Output:
- For output voltage and supply a current reference to the eFlow102NV series Power Supply Configuration Reference Chart, pg. 2.
- Auxiliary output rated @ 1A (unswitched).
- Overvoltage protection.
Fuse Ratings:
- Refer to eFlow102NV Series Power Supply Configuration Reference Chart, pg. 2.
Battery Backup:
- Built-in charger for sealed lead acid or gel-type batteries.
- Maximum charge current 1.54A.
- Automatic switch over to stand-by battery when
AC fails. Transfer to stand-by battery power is instantaneous with no interruption.
Fire Alarm Disconnect:
- Supervised Fire Alarm disconnect (latching or nonlatching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
Supervision:
- AC fails supervision (form “C” contacts).
- Battery fail and presence supervision (form “C” contacts).
- Low power shutdown. Shuts down DC output terminals if battery voltage drops below 71-73% (depending on the power supply). Prevents deep battery discharge.
Visual Indicators:
- Green AC Power LED indicates 220VAC present.
- AC input and DC output LED indicators.
Additional Features:
- Short circuit and overload protection.
- The unit is complete with a power supply, enclosure, battery leads, and cam lock.
Enclosure Dimensions (approximate H x W x D):
eFlow102NV, eFlow102N8V, eFlow102N8DV, eFlow102N16V, eFlow102N16DV: 13.5” x
13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
eFlow102NXV, eFlow102NX8V, eFlow102NX8DV, eFlow102NX16V, eFlow102NX16DV: 15.5”
x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA
70/NFPA 72/ANSI, The Canadian Electrical Code, Part 1, and with all local
codes and authorities having jurisdiction.
The product must be located indoors within the protected premises.
-
Mount the unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level, and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 11-12). Secure enclosure to earth ground.
-
Connect unswitched AC power (220VAC 50/60Hz) to terminals marked [L, N] (Fig. 1a, pg. 5).
Use 14 AWG or larger for all power connections. Secure green wire leads to earth ground lug.
Keep power-limited wiring separate from non-power-limited wiring (220VAC 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user-serviceable parts inside.
Refer installation and servicing to qualified service personnel.
For Fire Alarm applications the outputs are “Special Applications” only, see the list (refer to Appendix A, pg. 12). -
Measure output voltage before connecting devices. This helps avoid potential damage.
-
Connect devices to be powered:
a. For eFlow102NV/eFlow102NXV connect devices to terminals marked [– DC +] (Fig. 1h, pg. 5).
b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3a & 3b, pg.
- or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 4a & 4b, pg. 6)
carefully observing correct polarity.
For auxiliary device connection: this output will not be affected by Low Power Disconnect or Fire Alarm Interface. Connect the device to terminals marked [+ AUX –] (Fig. 1f, pg. 5).
-
For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect the battery to terminals marked [– BAT + ] (Fig. 1g, pg. 5). Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included). Use batteries – Castle CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or BAZR2 batteries of an appropriate rating.
-
Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 5) supervisory relay outputs.
-
To delay AC reporting for 2 hrs. set the DIP switch [AC Delay] to OFF position (Fig. 1c, pg. 5). To delay AC reporting for 1 min. set DIP switch [AC Delay] to ON position (Fig. 1c, pg. 5).
Note: Must be set to ON position for Burglar Alarm Applications. -
To enable Fire Alarm Disconnect set the DIP switch [Shutdown] to the ON position (Fig. 1c, pg. 5).
To disable Fire Alarm Disconnect set the DIP switch [Shutdown] to the OFF position (Fig. 1c, pg. 5). -
Trigger terminals are end of a line resistors supervised (10k ohms). Opening or shorting trigger terminals will cause [DC] output to shut down (Fig. 1d, pg. 5).
-
Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Fig. 1e, pg. 5).
-
For Access Control Applications: mount tamper switch (Altronix model TS112 or equivalent) at the top of the enclosure. Slide the tamper switch bracket onto the edge of the enclosure approx. 2” from the right side (Fig. 5, pg. 7 or Fig. 7, pg. 9).
Connect tamper switch wiring to the Access Control Panel input or the appropriate reporting device.
Wiring:
Use 18 AWG or larger for all low-voltage power connections.
Note: Take care to keep power-limited circuits separate from non-power-limited
wiring (220VAC, Battery).
Maintenance:
The unit should be tested at least once a year for the proper operation as
follows:
Output Voltage Test: Under normal load conditions, the DC output voltage
should be checked for proper voltage level eFlow102NV: 12VDC nominal rated @
10A max.
Battery Test:
Under normal load conditions check that the battery is fully charged, and
check the specified voltage (12VDC @ 13.2) both at the battery terminal and at
the board terminals marked [– BAT +] to ensure that there is no break in the
battery connection wires.
Note: Maximum charging current under discharges is 1.54A.
Note: Expected battery life is 5 years, however, it is recommended to
change batteries in 4 years or less if needed.
LED Diagnostics:
Power Supply/Charger
Red (DC) | Green (AC/AC1) | Power Supply Status |
---|---|---|
ON | ON | Normal operating condition. |
ON | OFF | Loss of AC. Stand-by battery supplying power. |
OFF | ON | No DC output. |
OFF | OFF | Loss of AC. Discharged or no stand-by battery. No DC output. |
Power Distribution Module
Green (AC) | Power Distribution Module Status |
---|---|
ON | Normal operating condition. |
OFF | No Power Output. |
Terminal Identification:
Power Supply/Charger
Terminal Legend | Function/Description |
---|---|
L, N | Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral (non- |
power-limited) (Fig. 1a, pg. 5).
– DC +| 12VDC nominal @ 10A continuous output (power-limited output) (Fig. 1h,
pg. 5).
Trigger EOL Supervised| Fire Alarm Interface trigger input from a short or
FACP. Trigger inputs can be normally open and normally closed from an FACP
output circuit (power-limited input) (Fig. 1d, pg. 5).
NO, GND RESET| FACP interface latching or non-latching (power-limited) (Fig.
1e, pg. 5).
+ AUX –| Auxiliary power-limited output rated @ 1A (unswitched) (Fig. 1f, pg.
5).
AC Fail NC, C, NO| Indicates loss of AC power, e.g. connect to audible device
or alarm panel. The relay is normally energized when AC power is present.
Contact rating 1A @ 30VDC (power-limited) (Fig. 1b, pg. 5).
Bat Fail NC, C, NO
| Indicates low battery condition, e.g. connect to the alarm panel. The relay
is normally energized when DC power is present. Contact rating 1A @ 30VDC.
A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg.
5).
– BAT +| Stand-by battery connections. Maximum charge current 1.54A (non-
power-limited) (Fig. 1g, pg. 5).
Power Distribution Module
Terminal Legend PD8/PD8CB | Terminal Legend PD16W/PD16WCB | Function/Description |
---|---|---|
1P to 8P | 1P to 16P | Positive DC power outputs. |
1N to 8N | 1N to 16N | Negative DC power outputs. |
Trouble/Time Limited Warning of Stand-by Batteries:
The Time Limited Warning circuit must be connected for local or remote
annunciation with an Amber or Red LED to indicate DC Trouble (low battery,
loss of battery, or when 95% of the stand-by battery has been depleted).
Connect the circuit to the Batt Fail relay contacts to an appropriate input of
a Burglar Alarm or Access Control Panel. The following figure shows the
circuitry needed for local annunciation.
Fig. 2 – Battery Trouble Indication
Wire one leg of a power-limited power source to the indicating lamp. Wire the
second leg of the power source to the indicating lamp in series with the
battery fail relay contact terminals marked [BAT FAIL – C, NO] (Fig. 2, pg.
6).
Power Distribution Module(s):
Fig. 3a – PD8 Power Distribution Board
Non-Power-Limited Outputs | Fig. 3b – PD8CB – Power Distribution Board
Power-Limited Outputs
---|---
Fig. 4a – PD16W Power Distribution Board
Non-Power-Limited Outputs | Fig. 4b – PD16WCB – Power Distribution Board
Power-Limited Outputs
CAUTION: The power supply board is factory set for 12VDC. Use only one
(1) 12VDC stand-by battery.
Keep power-limited wiring separate from non-power-limited. Use minimum 0.25″
spacing.
7AH Rechargeable batteries are the largest batteries that can fit in this
enclosure.
A UL-Listed external battery enclosure must be used if using 12AH, 40AH, or
65AH batteries.
NEC Power-Limited Wiring Requirements for eFlow102NV Models:
Power-limited and non-power-limited circuit wiring must remain separated in
the cabinet. All power-limited circuit wiring must remain at least 0.25” away
from any non-power-limited circuit wiring. Furthermore, all power-limited
circuit wiring and non-power-limited circuit wiring must enter and exit the
cabinet through different conduits.
One such example of this is shown below. Your specific application may require
different conduit knockouts to be used. Any conduit knockouts may be used. For
power-limited applications the use of conduit is optional. All field wiring
connections must be made employing suitable gauge CM or FPL jacketed wire (or
equivalent substitute).
An optional battery enclosure must be mounted adjacent to the power supply.
Note: Refer to the wire handling drawing below for the proper way to
install the CM or FPL jacketed wire (Fig. 6a).
- Outputs are non power-limited: eFlow102NV, eFlow102N8V, eFlow102N16V.
Outputs are Class 2 power-limited: eFlow102N8DV, eFlow102N16DV.
CAUTION: The power supply board is factory set for 12VDC. Use only one
(1) 12VDC stand-by battery.
Keep power-limited wiring separate from non-power-limited. Use minimum 0.25″
spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this
enclosure.
A UL-listed external battery enclosure must be used if using 40AH or 65AH
batteries.
NEC Power-Limited Wiring Requirements for eFlow102NX Models:
Power-limited and non-power-limited circuit wiring must remain separated in
the cabinet. All power-limited circuit wiring must remain at least 0.25” away
from any non-power-limited circuit wiring. Furthermore, all power-limited
circuit wiring and non-power-limited circuit wiring must enter and exit the
cabinet through different conduits.
One such example of this is shown below. Your specific application may require
different conduit knockouts to be used. Any conduit knockouts may be used. For
power-limited applications the use of conduit is optional. All field wiring
connections must be made employing suitable gauge CM or FPL jacketed wire (or
equivalent substitute).
The optional UL Listed battery enclosure must be mounted adjacent to the power
supply via Class 1 wiring methods.
For Canadian installations use shielded wiring for all connections.
Note: Refer to the wire handling drawing below for the proper way to
install the CM or FPL jacketed wire (Fig. 8a).
- Outputs are non power-limited: eFlow102NXV, eFlow102NX8V, eFlow102NX16V.
Outputs are power-limited: eFlow102NX8DV, eFlow102NX16DV.
Enclosure Dimensions (BC300):
eFlow102NV, eFlow102N8V, eFlow102N8DV, eFlow102N16V, eFlow102N16DV 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
Enclosure Dimensions (BC400): eFlow102NXV, eFlow102NX8V, eFlow102NX8DV, eFlow102NX16V, eFlow102NX16DV 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Appendix A – UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with eFlow102NV
output.
System Sensor Smoke Detector/Base| Detector Type| Max Stand-by
Current (mA)| Alarm Current (mA)
---|---|---|---
B112LP| Base| 0.12| 36
B114LP| Base| |
B404B| Base| |
DH100ACDC| Photoelectric| 0.15| 0.70
DH100ACDCLP| Photoelectric| 0.15| 0.70
DH100ACDCLPW| Photoelectric| 0.15| 0.70
DH400ACDCI| Ionization Duct| 25| 95
DH400ACDCP| Photoelectric Duct| 25| 95
1112/24/D| Ionization| 0.05| 50
1424| Ionization| 0.10| 41
1451 (w/B402B Base)| Ionization| 0.10| 39
2112/24ATR| Photoelectric| 0.50| 60/70
2112/24AITR| Photoelectric| 0.50| 60/70
2112/24/D| Photoelectric| 0.05| 50
2112/24T/D| Photoelectric w/135o Thermal| 0.05| 50
2112/24TSRB| Photoelectric w/135o Thermal Supervisory Relay| 15| 45
2312/24TB| Photoelectric| 0.12| 50
2412 (12 volts)| Photoelectric| 0.12| 77
2424| Photoelectric| 0.10| 41
2451| Photoelectric| 0.10| 39
2451TH (with/B402B Base)| Photoelectric| 0.10| 39
2W-MOD| Loop Test/Maintenance Mod.| 30| 50
4W-B (12/24 volt)| Photoelectric I3| 0.05| 23
4WT-B (12/24 volt)| Photoelectric I3 w/Therm| 0.05| 23
4WTA-B (12/24 volt)| I3 Photo w/Therm/Sounder| 0.05| 35
4WTR-B (12/24 volt)| I3 Photo w/Therm/Relay| 0.05| 35
4WITAR-B (12/24 volt)| I3 Photo w/Isolated Therm/Sounder/Relay| 0.05| 50
2W-MOD2| I3 Loop Test/Maintenance Mod.| 0.05|
RRS-MOD| I3 Reversing Relay/Sync Module| 0.05|
6424| Projected Beam| 10| 28.4
Beam 1224(S)| Projected Beam| 17| 38.5
- Contact manufacturer for current draws.
A.2 Relays
Table A-2 below lists relays compatible with eFlow102NV output.
Manufacturer | Model | Current (mA) |
---|---|---|
System Sensor | EOLR-1 | 30 |
eFlow Power Supply/Chargers can be
Controlled and Monitored while Reporting
Power/Diagnostics from Anywhere
over the Network…
LINQ2 – Network Communication Module
LINQ2 provides remote IP access to real-time data from eFlow power
supply/chargers to help keep systems up and running at optimal levels. It
facilitates fast and easy installation and set-up, minimizes system downtime,
and eliminates unnecessary service calls, which helps reduce the Total Cost of
Ownership (TCO) – as well as creates a new source of Recurring Monthly Revenue
(RMR).
Features:
- UL is Listed in the U.S. and Canada.
- Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN.
- Monitor real-time diagnostics: DC output voltage, output current, AC & battery status/service, input trigger state change, output state change, and unit temperature.
- Access control and user management: Restrict read/write, Restrict users to specific resources
- Two (2) integral network controlled Form “C” Relays.
- Three (3) programmable input triggers: Control relays and power supplies via external hardware sources.
- Email and Windows Dashboard notifications
- The event log tracks history.
- Secure Socket Layer (SSL).
- Programmable via USB or web browser – includes operating software and 6 ft. USB cable.
LINQ2 Mounts Inside any eFlow Enclosure
Notes:
………………………..
Models Include:
Model| Input 220VAC,
50/60Hz| Output| Auxiliary Power-Limited Output (unswitched)| Ripple Voltage
---|---|---|---|---
12VDC| 24VDC
eFlow102NV,
eFlow102NV8, eFlow102N8DV, eFlow102N16V, eFlow102N16DV| 2.1A| 10A| –| 1A|
760mV
eFlow102NXV,
eFlow102NX8V, Flow102NX8DV, eFlow102NX16V, eFlow102NX16DV
Overview:
The eFlow102NV series power supply/chargers convert a 220VAC, 50/60Hz input to
a 12VDC output.
Stand-by Specifications:
Battery| Burg. Applications 4 hr. Stand-by/15 min. Alarm| Fire Applications 24
hr. Stand-by/5 min. Alarm| Access Control Applications Stand-by
---|---|---|---
7AH| 0.4A/10A| N/A| 5 Mins./10A
12AH| 1A/10A| 0.3A/10A| 15 Mins./10A
40AH| 6A/10A| 1.2A/10A| Over 2 Hours/10A
65AH| 6A/10A| 1.5A/10A| Over 4 Hours/10A
Battery Backup:
- Built-in charger for sealed lead acid or gel-type batteries.
- Maximum charge current 1.54A.
- Automatic switch over to stand-by battery when AC fails.
Transfer to stand-by battery power is instantaneous with no interruption.
LED Diagnostics:
Red (DC) | Green (AC/AC1) | Power Supply Status |
---|---|---|
ON | ON | Normal operating condition. |
ON | OFF | Loss of AC. Stand-by battery supplying power. |
OFF | ON | No DC output. |
OFF | OFF | Loss of AC. Discharged or no stand-by battery. No DC output. |
Installing Company: ___ Service Rep. Name:
Address: _____ Phone #:
Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow102NV
Series, Rev. 102NVRP052213 for complete instructions. This sheet is to be
removed, framed, and posted next to the unit.
Rev. 102NVRP052213