PUR Whole Home Ultraviolet Water Disinfection System Owner’s Manual

June 6, 2024
PUR

PUR Logo

PUR Whole Home Ultraviolet Water Disinfection System

PUR Whole Home Ultraviolet Water Disinfection System

Safety Precautions

WARNING: The installation of this system must be in accordance with all provincial/state and/or local laws and regulations regarding plumbing and electrical services. Installation by a certified plumber is recommended. Always comply with the following warnings and safety instructions, to prevent bodily harm, injury or property damage.
DANGER: The lamp inside the unit emits ultraviolet light that can cause permanent damage to skin and eyes. Never look at the lamps when unit is operating.

  • Never attempt to operate your UV system unless it has first been properly grounded, to avoid creating an electric shock hazard.

  • To prevent an electric shock, do not plug the UV system into any socket that has not been equipped with a Ground Fault Circuit Interrupter (GFCI).

  • Always unplug the power cord before attempting to install, clean or perform other routine maintenance on the unit.

  • Always stop the inlet water flow before performing any maintenance on the unit.

  • Do not attempt to service this unit unless you are an accredited service technician, as personal injury could result and/or system operation could be detrimentally affected.

  • Never operate this unit in an oxygen-rich environment, or within 6 feet (2 meters) of any oxygen source.

  • If temperatures should fall below freezing (0°C / 32°F), drain all water from the unit, drain and disconnect all plumbing lines, and cap the inlet and outlet ports.

  • Do not attempt to install, operate, clean or perform routine maintenance on your UV system unless you have first read and understand all of the warnings and safety instructions that are contained in this manual and on the labels that are affixed to the system.

  • Do not attempt to operate the UV system if it has been visibly damaged. Inspect it carefully to ensure it is free of
    physical damage before using.

  • Do not operate if the system is wet or if there are visible leaks.

  • The UV system is electrically certified for indoor applications only and should not be exposed to outdoor elements.

  • Always install and operate the unit in an environment where both the air and water temperatures will normally range between 36°F (2°C) and 104°F (40°C).

This Class B system or component conforms to NSF/ANSI Standard 55 and CSA B483.1 for the supplemental bactericidal treatment of disinfected public drinking water or other drinking water that has been tested and deemed acceptable for human consumption by the state or local health agency having jurisdiction. The system is only designed to reduce normally occurring non- pathogenic nuisance microorganisms. Class B systems are not intended for treatment of contaminated water.

Product Overview

The PUR® Ultraviolet (UV) Water Disinfection System has been engineered to rigid standards, and has been quality inspected at the factory prior to packaging. Please review this manual in its entirety for a detailed system explanation, and ensure that the follow-ing components accompany this system. To ensure system performance, all replacement components should be purchased directly from an authorized dealer or online at www.ghpgroupinc.com. The use of components purchased from other sources will void the warranty, and will potentially cause the system to function in a lesser capacity than intended.

Product Overview 01

Product Overview 02

Item

| Description| QTY
---|---|---
A| Power Cord|

1

B

| Electronic Controller| 1
C| UV Lamp|

1

D

| Quartz Sleeve| 1
E| Stainless Steel UV Reaction Chamber|

1

F

| Owners Manual| 1

G

| Flow Restrictor| 1
H| Wall Screws|

2

I

| Wall Anchors| 2
J| VuCap®|

1

K

| UV Cylinder Mounting Clamps| 2
L| Retaining Nut|

1

M

| Quartz Sleeve Sealing O-Ring|

1

WARNING: Lamps must be replaced after 12 months of operation to ensure proper disinfection of your water. Clean the Quartz Sleeve frequently for optimum performance.
A minimum 5 μ nominal pre-filter is recommended upstream (before) the UV system installation point. As UV system efficiencies are dictated by penetration of the UV light through the water column, particulate matter within the water column could decrease the disinfection capacity, and potentially create a harmful condition. Filtration systems sold separately.

Tools Required for Installation

Tools Required for Installation

About Your System

Specifications

Model Number:

| PUV15S|

PUV25S

---|---|---
**Flow Rate GPM US (LPM)***|

7.4 (28.2)

|

12.3 (46.6)

Dimensions| Controller|

8” x 3” x 2” (20.3 cm x 7.6 cm x 5.1 cm)

Chamber Diameter|

3.5” (8.9 cm)

|

3.5” (8.9 cm)

Chamber Length|

17.25” (43.8 cm)

|

27.88” (70.8 cm)

I/O Port Size|

3/4” FNPT – 1.0” MNPT

System Operating Pressure|

15-125psi (103-862kPa)

Electrical| Voltage|

100-240, 50/60Hz

Power Consumption (W)|

21

|

35

Lamp Watts (W)|

17

|

30

Chamber Material|

304SS

  • NSF/ANSI 55 class B maximum rated flow System tested and certified by NSF International against NSF/ANSI Standard 55 and CSA B483.1 for disinfection performance, class B.

Conditions for Operation

Water quality will impact the performance of your UV system, and the following levels should be utilized as a guideline for pre-treatment requirements of the influent water supply prior to UV treatment:

  • Iron…………………………………………. < 0.3 ppm (0.3 mg/L)
  • Turbidity …………………………………. < than 1 NTU
  • Tannins …………………………………… < 0.1 ppm (0.1 mg/L)
  • Manganese………………………………. < 0.05 ppm (0.05mg/L)
  • Hardness ………………………………… < 120 ppm (7 grains per gallon)
  • UV Transmittance ………………….. > 75%

If you are using untreated surface water or untreated groundwater as your source of supply, the suitability of the water supply for potable applications must be confirmed by the provincial/state and/or local health agency that has jurisdiction.
If the test results indicate that: (1) any of the above contaminant levels are being exceeded, or (2) any prevailing drinking water health standards are not being met, additional pre-treatment options must be installed that will eliminate all contaminants posing health risks. Non-municipal water should be tested on an ongoing basis to ensure treatment efficiency.

Installation Instructions

Accessibility, Orientation & Fittings

Install your UV system in a location that provides ample space for accessing and removing the lamp and quartz sleeve from the UV chamber. A minimum distance equivalent to the length of the UV reaction chamber (stainless steel cylinder) plus 6-12″ (15-30cm) is required to ensure adequate clearance. As the UV system generates heat during use, ensure that no combustible items come into contact with, or are in proximity to the system. It is recommended that you maintain at least 6″ (15 cm) of clear wall space on all sides of the UV for cooling purposes. This will prolong the operating life of the system. Mount electronic controllers where they will not get wet during maintenance or from condensation from copper pipes, etc.

Optional Bypass Line and Drain Valve

The diagram below shows the installation of a typical disinfection system and the optional components that may be used for the installation. The use of a bypass assembly is recommended in case the system requires off-line maintenance. To prevent possible contamination of water in the plumbing, which may pose a health hazard, do not use the bypass line and valve if your source of supply is untreated surface or ground water. If your source of supply is treated municipal water, use of the bypass line and valve will permit uninterrupted water supply in the event of a system malfunction. The installation of a drain valve, while not required, will allow the service technician to drain the system of water prior to conducting any service on the unit.

Horizontal Installation

Horizontal Installation

Optional Vertical Installation
  • PUR® UV systems may be installed vertically with the outlet port at the top of the system, to eliminate any trapped air, and the inlet port at the base, as shown in the diagram.
  • Ensure the Controller is kept dry and away from any potential condensation. Use drip loops so moisture does not run down lamp harness or power cord and into the Controller. The Electric Controller must remain dry.
  • Prior to installation, remove protective caps from inlet and outlet ports of the UV reaction chamber.

Optional Vertical Installation

Horizontal Installation

Horizontal Installation 02

Vertical Installation

Vertical Installation

System Installation

WARNING: When handling the UV lamps and quartz sleeves, soft gloves or a cloth should always be used to prevent oil deposits on the surface. Oil deposits from your hands can create hot spots on the surface which may lead to premature lamp failure.

  1. Determine a suitable location and ensure mounting of the UV system in the correct orientation can be completed. In order to install/remove the UV lamp and quartz sleeve from the stainless steel chamber, ensure the minimum clearance is double the overall length of the unit.
    System Installation 01

  2. Attach the mounting clamp to the installation structure using an appropriate screw type for both the weight and material of the surface.
    System Installation 02

  3. Position the UV reactor chamber into the mounting clamp and secure.
    System Installation 03

  4. Install all inlet/outlet plumbing to the system (inclusive of all pre-filtration and valve set-ups described above).
    NOTE: In order to meet NSF 55 certification the flow restrictor that is included with the UV system must be used to control the flow of water through the UV chamber. The flow restrictor is designed to thread onto either the inlet or outlet ports using Teflon sealing tape for the NPT fittings. In most settings, the system should have a manual shut off valve at the input. The water flows in the direction of the arrow located on the flow restrictor label.

  5. Mount the Electronic Controller in a dry location close to the UV reaction chamber. Install power cord and lamp harness using drip loops to prevent moisture from travelling along cable and into Controller.
    System Installation 04

  6. Ensure the quartz sleeve is intact and that the o-ring, VuCap® retaining ring and retaining nut are in position and tightened. Do not overtighten the retaining nuts.
    System Installation 05

  7. Connect the four pins of the UV lamp to the UV lamp plug on the Controller.
    System Installation 06

  8. Insert the UV lamp into the quartz sleeve and secure the VuCap® protective cover.
    System Installation 07
    System Installation 08

  9. Slowly open the supply valves before and after the UV system and ensure there are no water leaks.

  10. Connect the Electronic Controller to the power outlet, and ensure that both the Controller display (indicates lamp life remaining) and the green LED illuminate.
    The glow from the UV lamp should also be visible through the VuCap® but note it may not be visible in high ambient lighting.
    System Installation 09

Your UV disinfection system is now ready for use.
If your system is only being used seasonally, it must be stored properly for the winter.
Disconnect your system from the power source and drain all water from the system.
Before placing the system back in service, disinfection of the household plumbing system is strongly recommended.

In-House Water Distribution System Disinfection

The following procedure is recommended for installations of the UV disinfection system in a whole house treatment application. For systems installed on a municipally treated water system, plumbing system disinfection is at the discretion of the user. To disinfect the distribution system, carry out the following steps. Ensure that the UV system remains on during the entire process.

  1. Familiarize yourself with the various shut-off valves on your system. It is important to understand which combinations of valve positions allow you to isolate the UV system.

  2. Shut off the main water supply, ahead of any filter housing, and depressurize the household water lines.
    NOTE: Individual plumbing set-up may vary, so images are included as a visual reference only.

  3. Close the valves necessary to isolate the UV Prefilters.
    System Installation 10
    Remove the filter cartridge closest to the UV. Fill the sump with 1-2 cups of household chlorine bleach (5.25%).
    System Installation 11
    System Installation 12

  4. Re-install the sump (without filter) and slowly re-pressurize the system. Open each faucet and allow cold water to run until you can smell chlorine in the water. Shut off the faucet and repeat with all other household faucets including hot water. Be sure to include all exterior faucets, shower heads, and dishwasher/washing machine lines within this process.
    System Installation 13

  5. Allow the solution to remain in the lines for 30 min tes minimum.
    System Installation 14

  6. Re-install the pre-filter cartridge, and flush each individual water line as above until no chlorine odor is detected.
    System Installation 15

It is critical to ensure that the water distribution system is fully flushed of all residual chlorine prior to use. EXTREME CAUTION SHOULD BE EXERCISED as the level of chlorine in the system is approximately 25-50 times greater than that observed in municipally treated water. This is required for the disinfection of the household lines. It is extremely important that proper flushing procedures be followed from all taps prior to use.
NOTE: The introduction of a chlorine disinfection solution to a hot water heater that has been used with untreated hard water or water with excessive iron, manganese or other organic contaminants may lead to oxidization of these materials. If you feel that these conditions may apply to your installation, a thorough flushing of the hot water tank should be done to eliminate the oxidized material from entering the distribution lines.

Operation & Maintenance

The UV system should remain turned on continuously to ensure protection of your water system. During normal operation of the system, the green Controller power LED light will be illuminated and the display will indicate the number of days remaining until lamp replacement is required. During periods of non- use, it is normal for the temperature of the water in the stainless steel chamber to rise. Simply flushing the water line will alleviate this condition. During humid conditions, sweating or small water droplets may be noticed on the surface of the UV reaction chamber. The formation of condensation during high humidity conditions is normal. Do not allow condensation to drip onto the Controller. The following instructions have been provided to assist with general maintenance of the system; UV lamp replacement and quartz sleeve cleaning/replacement. All other system repairs should be completed by a licensed plumber/service technician.
WARNING: Never attempt to service the UV system unless you are an accredited service technician, as the performance of the system could be adversely affected.

Lamp Installation and Replacement

WARNING: The lamp heats up after continuous use and can burn your skin if touched. Disconnect power from the wall outlet and allow lamp to cool for at least 5 minutes before removing. Do not operate the UV lamp outside of the UV Chamber. The lamp in the unit emits powerful Ultraviolet light that can cause permanent damage to skin and eyes. Never look at the lamp when the unit is turned on. Handle the UV lamp by the ends only. Do not touch the glass surface of the UV lamp with your fingers. If the surface of the lamp becomes dirty, use a clean lint-free cloth and isopropyl alcohol to remove any dirt.

Your UV disinfection system is equipped with a visible/audible lamp failure indicator. In the event of UV lamp failure, the red LED light will flash and a beeping sound will be audible from the Electronic Controller of the unit. The lamp life countdown timer will stop decrementing when in alarm mode. Please note that if these conditions occur and you are on a non-municipal supplied water source, you should immediately stop using the water for potable applications until the lamp is replaced and disinfection of all distribution lines is completed.

The ultraviolet lamp has an approximate life of one year (9000 hours). The UV lamp will continue to operate past 9000 hours, however, the UV output decreases rapidly beyond 9000 hours and the UV lamp may no longer provide adequate disinfection of your water supply. The built in 365 day countdown timer displays the number of days remaining until lamp replacement is required. When countdown timer reaches 0 days an intermittent audible alarm will be activated and the Controller display will indicate alarm A3. In order to allow time to obtain a replacement UV lamp, the audible alarm can be silenced for 7 days by pressing and holding button on Controller for 2-5 seconds. After 7 days, alarm will sound again if lamp has not been replaced. This can be done a maximum of 4 times which allows up to 28 days to obtain a replacement UV lamp. After 4 times, the alarm can no longer be silenced until a replacement lamp is installed and the lamp life alarm is reset to 365 days.

Replacement UV lamps and quartz sleeves are available from an authorized dealer. Use only PUR® approved lamps and sleeves to ensure system performance. Replacement lamps and quartz sleeves are sold under the following model numbers:

Model Number:

| Controller|

Lamp/Sleeve Combo

---|---|---

PUV15S

|

BA-40S

|

PUVLQS17S

PUV25S

|

BA-40S

|

PUVLQS30S

  1. Depressurize UV chamber by turning off the inlet water supply and open valve downstream of system. Then close outlet valve.
    System Installation 16

  2. Unplug the Controller from the electrical outlet.
    System Installation 17

  3. Allow at least 5 minutes for lamp to cool before removing.
    System Installation 18

  4. Remove the VuCap® from the UV chamber and carefully disconnect the UV lamp from the lamp connector harness.
    System Installation 19

  5. Carefully remove the UV lamp from the quartz sleeve by gently rotating the lamp free. Be sure to hold the lamp only by the ceramic ends.

  6. Carefully insert the new UV lamp into the quartz sleeve and attach the lamp connector harness to the UV lamp.

  7. Re-pressurize the system by slowly opening the water inlet valve.
    System Installation 20

  8. Check the system for any leaks.

  9. Plug Controller into the electrical outlet.
    System Installation 21

  10. Ensure that the UV lamp is operating – the green power LED light should be illuminated, the red lamp failure LED light should be off and no audible alarm should be active.

  11. The display will show the number of days until lamp replacement is required. If a new lamp was installed, press and hold the button on the Controller for 10 seconds to reset the lamp-life countdown.

  12. Allow UV lamp to warm up for a minimum of 2 minutes before flushing water through the UV chamber.

Quartz Sleeve Installation and Replacement

Any mineral deposits or sediment build-up on the quartz sleeve will affect the system performance by decreasing the UV light transmitted through the quartz sleeve into the water column.
The proper maintenance and replacement of the pre-filtration required for the UV system will reduce the accumulation of mineral and sediment residue on the quartz sleeve. The quartz sleeve may be cleaned with a commercially available, non-abrasive, acidic scale remover and a lint free cloth. Cleaning of the quartz sleeve should be done on a regular basis to ensure maximum system performance. The amount of cleaning required will vary depending upon local water conditions and system pre-filtration.
All traces of the cleaning solution must be fully removed from the the quartz sleeve before it is reinstalled in the system. Care should be taken to prevent any cleaning fluid from coming into contact with the inside surface of the quartz sleeve.

  1. Depressurize UV chamber by turning off the inlet water supply and open valve downstream of system. Then close outlet valve.
    System Installation 22

  2. Unplug the Controller from the electrical outlet.
    System Installation 23

  3. Allow at least 5 minutes for lamp to cool before removing.
    System Installation 24

  4. Remove the VuCap® from the UV chamber and carefully disconnect the UV lamp from the lamp connector harness.

  5. Carefully remove the UV lamp from the quartz sleeve by gently rotating the lamp free. Be sure to hold the lamp only by the ceramic ends.

  6. Drain water from the Stainless Steel UV Chamber.

  7. Remove the retaining nut securing the quartz sleeve into the UV chamber.

  8. Remove the quartz sleeve sealing O-ring.

  9. Remove the quartz sleeve and clean as noted above.
    System Installation 25

  10. Insert quartz sleeve into the UV chamber. Quartz sleeves should be replaced every 3 years for optimal performance.

  11. Insert UV lamp into the quartz sleeve and attach the connector.

  12. Slowly refill the UV chamber by opening the water supply just enough to fill the chamber with water.
    System Installation 26

  13. Check the system for any leaks.

  14. Apply power to the UV system.
    System Installation 27

  15. Ensure that the UV lamp is operating by verifying the Controller green LED indicator is on and display is operational.

Troubleshooting Guide

Problem

| Possible Cause|

Solution

---|---|---
Warm water output| Water sitting in UV reaction chamber and heating up due to infrequent use| Run tap for a short period of time.
Unit leaking water| Misaligned or cross-threaded connections on inlet/outlet ports| Reinstall to ensure a solid connection with ports. Inlet/outlet threads on UV chamber are NPT type and require thread sealant.
Excessive water pressure| Install pressure regulator ahead of system.
Water hammer* causing pressure spikes| Install a water hammer arrestor in system.
Improperly sealed quartz sleeve o-ring| Re-align, apply o-ring grease and re- tighten retaining nut.
No power to UV lamp when system is plugged in| GFCI wall socket is tripped| Reset, following manufacturer’s instructions provided with the outlet.
Check socket with other appliances.
Ensure UV chamber is grounded.

Ensure all electrical ports/connections are dry.

System has power but UV lamp is not coming on (visible/audible alarm activated)| Lamp not installed correctly| Ensure lamp is installed correctly with electrical fitting (must be snug).
Lamp failure| Replace UV lamp.
System is vibrating| Not mounted securely| Secure fasteners.
Water hammer* causing vibrations| Install a water hammer arrestor in system.
Excessive heat generated| Not being allowed sufficient space for cooling| Clear space for cooling (min. 6-12” / 15-30 cm clearance around unit).
Operated in an excessive ambient temperature| Unplug unit until temperature is within ambient operating conditions.
Water temperature is too high| Ensure treatment is on cold water side only (prior to heating of water).

*Water hammer: Sudden closure of a control valve or stopping of a pump produces excessive pressure surges in a pipeline. These pressure surges can cause significant damage to equipment and/or appliances directly attached to the water line. Water hammer is usually noted due to the characteristic banging sounds when valves on the line are suddenly closed. Water hammer conditions must be immediately remedied, and damage to systems as a result of this condition are not covered under warranty.
Should service be required or you have any questions regarding how to use your PUR product, please contact Customer Service at:
1-877-447-4768 or [email protected]
Manufactured and warranted by GHP Group Inc.
USA: 6440 W. Howard St. Niles, IL 60714-3302
Canada: 271 Massey Rd. Guelph, Ontario, N1K 1B2

NSF Data Tags

You must attach the following Class B tag to the UV system.

Class B System:
This system conforms to NSF/ANSI Standard 55 and CSA B483.1 for the supplemental bactericidal treatment of disinfected public drinking water or other drinking water that has been tested and deemed acceptable for human consumption by the state or local health agency having jurisdiction. The sys- tem is only designed to reduce normally occurring non-pathogenic nuisance microorganisms. Class B systems are not intended for the disinfection of contaminated water.| Always install and operate the unit in an environment where both air and wa- ter temperature will normally range between 36°F (2°C) and 104°F (40°C). See instruction manual for use conditions.
Lamp should be replaced every year (9000 Hrs.) Electronic Controller has built in 365 day countdown timer.
---|---

Warranty

Limited Warranty

This limited warranty is extended to the original retail purchaser of this filtration system and warrants against any defect in material and workmanship for a period of one (1) year from the date of retail sale. GHP Group, Inc., at its option, will either provide replacement parts or replace the unit, when properly returned to the retailer where purchased within one (1) year of retail purchase. (Shipping costs, labor costs, etc. are the responsibility of the purchaser.)

Duties of the Owner

This filtration system must be installed and operated in accordance with the written instructions furnished with this system. This warranty shall not excuse the owner from properly maintaining this unit in accordance with the instructions. A bill of sale, canceled check or payment record must be kept to verify purchase date and establish warranty period. Original carton should be kept in case of warranty return of the unit.

What is Not Covered?
  1. Damage caused by misuse, installation or use contrary to the owner’s manual and safety guidelines.
  2. Use of this product where water is microbiologically unsafe or of unknown quality.
  3. Damage caused by a lack of normal maintenance and cleaning.
  4. Use of non-OEM parts or accessories.
  5. Damage caused in transit. Freight charges on warranty parts or products to and from the factory shall be the responsibility of the owner.

THIS LIMITED WARRANTY IS GIVEN TO THE PURCHASER IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF MERCHANTABILITY OF FITNESS FOR A PARTICULAR PURPOSE. THE REMEDY PROVIDED IN THIS WARRANTY IS EXCLUSIVE AND IS GRANTED IN LIEU OF ALL OTHER REMEDIES. IN NO EVENT WILL GHP GROUP. INC. BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states/provinces do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states/provinces do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you.

Claims Handled as Follows

  1. Contact your retailer and explain the problem.
  2. If the retailer is unable to resolve the problem, contact our Customer Service Dept. detailing the system model, the problem, and proof of date of purchase.
  3. A representative will contact you. DO NOT RETURN THE UNIT TO GHP GROUP, INC. unless instructed by our Representative, or with written authorization. This warranty gives you specific legal rights and you may also have other rights that vary from state/province to state/province.
Product Registration

To register your product, please visit: ghpgroupinc.com/product- registration.html and complete within (14) days of purchase.

Warning: This Product can expose you to chemicals including Diisononyl phthalate (DINP) which is known to the State of California to cause cancer and Mercury Compounds which is known to the State of California to cause reproductive harm.
For more information go to www.p65Warnings.ca.gov

Warning

In the event of a broken UV lamp, there may be possible exposure to mercury.
There are no known health hazards from mercury within an intact UV lamp.
After handling the electrical power cord, please wash your hands.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

PUR User Manuals

Related Manuals