S S REGELTECHNIK KW-SD Condensation Control Switches User Guide

June 6, 2024
S S REGELTECHNIK

HYGRASREGe KW
HYGRASREG® KW- SD
Operating Instructions, Mounting & Installation
Condensation control switches including strap/with detached sensor head, with switching output

KW (IP)
KW- SD

S+S REGELTECHNIK GMBH
THURN-UND-TAXIS-STR. 22
90411 NURNBERG/ GERMANY
FON +49 (0)911/ 519 47-0
mail@SplusS.de
www.SplusS.de

CARTONS

Dimensional drawing
KW

M12 connector
(optional on request)

pro-dynamic cross convertion
Patant No. DW 10 2012 015 726.6

KW – external

M12 connector
(optional on request)

Patented quality product (pro-dynamic cross convection patent no. DE 10 2012 015 726.6)

The condensation control switch HYGRASREG® KW with housing made from impact- resistant plastic with quick-locking screws or the cost-effective HYGRASREG® KW SD with snap-on lid is installed on cooling ceilings, on cooling /cold-water piping or on cooled surfaces and is designed to prevent the formation of condensation.

It reliably detects formation of dew by means of its humidity and temperature sensor (no conductivity measurement) and, thanks to its measuring method, pro dynamic cross convection, yields an exact measurement result (with LED status indicator).

Dew point temperature is that temperature at which air reaches the state of saturation and water vapour starts to condensate. The KW condensation control switch can be operated as a monitor on cooling ceilings or pipes so that the switching output is activated when dew builds up on the cooling ceilings of the property to be monitored and e.g. a heating system is started, or other actuators are initiated.

TECHNICAL DATA

Power supply: 24 V AC (± 20 %) and 15…36 V DC
Power consumption: < 1.1 VA / 24 V DC ; < 2.2 VA / 24 V AC
Switchpoint: approx. 93% r.H. (permanently set)
Output: potential-free changeover contact (24 V), 1 A ohmic load
Sensor protection: membrane filter
Medium: clean air and non-aggressive, non-combustible gases
Housing: plastic, UV-resistant, material polyamide, 30% glass-globe

reinforced, colour traffic white (similar to RAL 9016), housing cover is transparent!
KW-xx| with quick-locking screws (slotted /Phillips head combination),
KW-xx-SD| with snap-on lid,
Housing dimensions:| 72 x 64 x 43.3 mm   (Tyr 1/Tyr 01)
Cable connection:| cable gland, plastic
(M 16 x 1.5; with strain relief, exchangeable, inner diameter 10.4mm) or
M12 connector
according to DIN EN 61076-2-101 (optional on request)
Electrical connection:| 0.14 – 1.5 mm2, via terminal screws
Process connection:| endless strap with metal tightener, 300 mm, for pipes up to 3″ diameter (included in the scope of delivery)
Mounting:| The mounting position should be selected so that no condensate can enter the sensor system in the event that condensation forms!
KW/KW-SD with strap for direct mounting on pipes or for direct mounting on flat surfaces (e.g. walls, ceilings)
KW-external/KW-SD-external with detached sensor head (cable length KL =1.5 ml for mounting on pipes
Protection class:| Ill (according to EN 60 730)
Protection type:| KW-xx| IP 65 (according to EN 60 529) Housing tested, TUV SOD, Report No. 713139052 (Tyr1)
KW-SD-xx| IP 54 (according to EN 60 529) Housing tested, TOV SOD, Report No. 7131609604 (Tyr 01)
Standards:| CE-conformity, electromagnetic compatibility according to EN 61326, EMC Directive 2014 /30/EU
FUNCTION| The relay output is triggered (contact 13-11 closed) if the switchpoint (93% r.H.) is not reached and opens (contact 12-11 closed) in the event of a fault (power failure, condensation).

LED short pulses =
relay active —. switchpoint not reached
ACTUAL humidity < 93% r.H. (no condensation)

LED long pulses =
relay inactive —. switchpoint exceeded
ACTUAL humidity > 93% r.H. (condensation)

Installation and Commissioning

HYGRASREGR KW-SD Condensation control switches including strap„ Standard
HYGRASREGR KW-SD-external Condensation control switches with detached sensor head, Standard

Type/WG01B| Switchpoint Humidity| Output Humidity| Mounting| Item No.
---|---|---|---|---
KW-SD| | | Sensor internal| IP 54
KW-W-SD| ca. 93% r. H.| Changeover contact| for direct mounting on pipes, for direct mounting on flat surfaces| 1202-1075-0001-020
• KW-SD-external| | | Sensor external| IP 54
KW-W-SD extern| ca. 93% r. H.| Changeover contact| for mounting on pipes| 1202-1075-0001-040
Optional:| Cable connection wi h M12 connector according to DIN EN 61076-2-101| on request

HYGRASREGR KW Condensation control switches including strap, Premium
HYGRASREGR KW-external Condensation control switches with detached sensor head, Premium

Type/WG01| Switchpoint Humidity| Output Humidity| Mounting| Item No.
---|---|---|---|---
KW| | | Sensor internal| IP 65
KW-W| ca. 93% r.H.| Changeover contact| for direct mounting on pipes, for direct mounting on flat surfaces| 1202-1025-0001-020
KW-external| | | Sensor external| IP 65
KW-W-extern| ca. 93% r.H.| Changeover contact| for mounting on pipes| 1202-1025-0001-040
Optional:| Cable connection with M12 connector according to DIN EN 61076-2-101| on request

General notes

  • This device must only be used in non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element.
  • On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor against potential dust exposure. In case of pollution/contamination, this filter should be cleaned on a regular basis.
  • Dust and pollution falsify measurement results and are to be avoided. Slight pollution and dust sediments can be removed by using compressed air.
  • Touching the humidity element is under any circumstances to be avoided, as that would result in considerable mismeasurements.
  • In case of pollution, we recommend cleaning and recalibration in the
  • In any case, the sensor must not get in contact with chemicals or other cleaning agents.
  • The relative humidity of 0…100% is indicated by an output signal of 0 -10 V or 4 … 20
  • The device operating range covers0…99.9% r. I-I. Beyond that range, mismeasurements or increased deviations may occur.
  • When several sensors (0.10 V) are connected to one voltage supply of 24V AC, correct polarity must be regarded as otherwise the alternating voltage source may be short-circuited.
  • The voltage outputs are short-circuit proof. Applying overvoltage or voltage supply to the voltage output will destroy the device.
  • If this device is operated beyond the specified range, all warranty claims are

Our “General Terms and Conditions for Business” together with the “General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry” (ZVEI conditions) including supplementary clause “Extended Retention of Title” apply as the exclusive terms and conditions.

In addition, the following points are to be observed:

  • These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

  • Devices must only be connected to safety extra-low voltage and under dead-voltage To avoid damages and errors at the device (e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

  • This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TOV and the local energy supply company must be The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.

  • No warranties or liabilities will be assumed for defects and damages arising from improper use of this

  • Consequential damages caused by a fault in this device are excluded from warranty or liability.

  • These devices must be installed and commissioned by authorised

  • The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.

  • In case of any modifications made by the user, all warranty claims are forfeited.

  • This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat
    Direct sun irradiation or heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

  • Operating this device close to other devices that do not comply with EMC directives may influence functionality.

  • This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

  • Dimensions of housing or housing accessories may show slight tolerances on the specifications provided in these instructions.

  • Modifications of these records are not permitted.

  • In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning: This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an initial manual adjustment on-site during commissioning and subsequently at regular intervals.

Commissioning is mandatory and may only be performed by qualified personnel!
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

SUPPLY VOLTAGE:
For operating voltage reverse polarity protection, a one-way rectifier or reverse polarity protection diode is integrated in this device variant. This internal one-way rectifier also allows operating 0 -10 V devices on AC supply voltage.
The output signal is to be tapped by a measuring instrument. Output volt­age is measured against zero potential (0 V) of the input voltage!
When this device is operated on DC supply voltage, the operating voltage input UB+ is to be used for 15…36 V DC supply and UB— or GND for ground wire!
When several devices are supplied by one 24V AC voltage supply, it is to be ensured that all ‘positive operating voltage input terminals (+) of the field devices are connected with each other and all ‘negative operating voltage input terminals (—) f= reference potential) are connected together fin-phase connection of field devices). All outputs of field devices must be referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage short- circuit would be caused by that device. The consequential short-circuit current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!

© Copyright by S+S Regeltechnik GmbH
Reprint in full or in parts requies permission from S+S Regeltechnik GmbH
Subject to errors and technical changes. All statements and data herein represent our best knowledge at date of publication. They are only meant to inform about our products and their application potential, but do not imply any warranty as to certain product characteristics. Since the devices are used under a wide range of different conditions and loads beyond our control, their particular suitability must be verified by each customer and/or end user themselves. Existing property rights must be observed. We warrant the faultless quality of our products as stated in our General Terms and Conditions.

Mounting diagram
KW

KW-external

Note when mounting: Sensor must remain unobstructed (min. distance 10 cm), ambient air may not be shielded off.

HYGRASREGe KW
HYGRASREG® KW- SD

Documents / Resources

| S S REGELTECHNIK KW-SD Condensation Control Switches [pdf] User Guide
KW-SD, Condensation Control Switches, KW-SD Condensation Control Switches, Control Switches, Switches
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

S S REGELTECHNIK User Manuals

Related Manuals