S S REGELTECHNIK ETR Built in Temperature Controllers Instruction Manual

June 12, 2024
S S REGELTECHNIK

S S REGELTECHNIK ETR Built in Temperature Controllers

Product Information

  • Product Name: D G F r
  • Model Number: 6000-2860-0000-1XX
  • Manufacturer: SplusS
  • Website: www.SplusS.de

Product Usage Instructions

  1. Read the important notices and warnings in the user manual before proceeding with installation or operation.
  2. Mount and install the product according to the provided instructions.
  3. Connect the product to a power source with a voltage range of 24-250V AC and a current of either 10A or 1.5A, depending on the specific requirements.
  4. Ensure that the product is properly grounded and that the switch block is sealed to protect against dust and water (IP65 rating).
  5. Refer to the provided wiring diagrams for proper connection of the TW, TR, and STB terminals.
  6. Adjust the temperature ranges as needed using the adjustable settings.
  7. Set the desired thermal switching differential (3K for most models) for accurate temperature control.
  8. Refer to the table for the appropriate capillary length and thread type for your specific model.
  9. Follow the specified temperature and flow rate ranges for optimal performance.
  10. Refer to the user manual for additional instructions and troubleshooting tips.

Dimensional drawing

S-S-REGELTECHNIKETR-Built-in-Temperature-Controllers-
FIG-2
S-S-REGELTECHNIKETR-Built-in-Temperature-Controllers-
FIG-3

DIN-tested German quality product. Temperature control and limiting device for heat generation plants in accordance with DIN EN 14597. Safety temperature limiter (STB) with EC type test (module B) according to directive 2014 ⁄ 68 ⁄ EU.
Mechanical temperature control device ⁄ rod thermostat THERMASREG® ETR with switching output, used for monitoring, controlling or limiting the temperatures of liquid or gaseous media as a boiler controller or in heating, air conditioning technology as well as in mechanical and apparatus engineering and in heat generation plants. It is available as one – step or two-step device, as adjustable temperature controller TR, temperature monitor TW, or as safety temperature limiter STB.

TECHNICAL DATA

S-S-REGELTECHNIKETR-Built-in-Temperature-Controllers-
FIG-9

Connecting diagram

S-S-REGELTECHNIKETR-Built-in-Temperature-Controllers-
FIG-4
S-S-REGELTECHNIKETR-Built-in-Temperature-Controllers-
FIG-5
S-S-REGELTECHNIKETR-Built-in-Temperature-Controllers-
FIG-6

Built-in temperature controllers, one-step, two-step, including immersion sleeve

S-S-REGELTECHNIKETR-Built-in-Temperature-Controllers-
FIG-10 S-S-REGELTECHNIKETR-Built-in-
Temperature-Controllers-FIG-11 S-S-REGELTECHNIKETR-Built-in-Temperature-Controllers-
FIG-12

General notes

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.
In addition, the following points are to be observed:

  • These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!
  • Devices must only be connected under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.
  • This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.
  •  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
  • Consequential damages caused by a fault in this device are excluded from warranty or liability.
  • These devices must be installed and commissioned by authorised specialists.
  • The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.
  • In case of any modifications made by the user, all warranty claims are forfeited.
  • This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat i rradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.
  • Operating this device close to other devices that do not comply with EMC directives may influence functionality.
  •  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
  • Dimensions of housing or housing accessories may show slight tolerances on the specifications provided in these instructions.
  • Modifications of these records are not permitted.
  • In case of a complaint, only complete devices returned in original packing will be accepted.
  • Notes on commissioning: This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an initial manual adjustment on-site during commissioning and subsequently at regular intervals.
  • Commissioning is mandatory and may only be performed by qualified personnel!
  • These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

Installation and Commissioning

Permissible approach velocities (flow rates) for crosswise approached protective tubes in water.
The approaching flow causes protective tube to vibrate. If specified approach velocity is exceeded even by a marginal amount, a negative impact on the protective tube’s service life may result (material fatigue). Discharge of gases and pressure surges must be avoided as they have a negative influence on the service life and may damage the protective tubes irreparably.

Please observe maximum permissible approach velocities

  • for stainless steel protective tubes 9 x 1 mm (1.4571) (see graph THR – VA – 09 ⁄ xx)
  • for stainless steel protective tubes 17 x 1 mm (1.4571) (see graph THR – VA – 17 ⁄ xx)
  • for brass protective tubes 8 x 0.5 mm (see graph THR – ms – 08 ⁄ xx)

S-S-REGELTECHNIKETR-Built-in-Temperature-Controllers-
FIG-7 S-S-REGELTECHNIKETR-Built-in-
Temperature-Controllers-FIG-8

ACCESSORIES

| | | Immersion sleeve

100 Type ⁄ WG01

p max

(static)

| T max| Time Constant for

Air              Water

| Medium:

Oil

| Inserted Length (EL)| Item No.
 |  |  |  |  |  |
T HR- MS – 08 / 100| 10 bar| +150 °C| 106 s           18 s| 53 s| 100 mm| 7100-0011-3022-000
T HR- MS – 08 / 150| 10 bar| +150 °C| 106 s           18 s| 53 s| 150 mm| 7100-0011-3404-000
T HR- MS – 08 / 200| 10 bar| +150 °C| 106 s           18 s| 53 s| 200 mm| 7100-0011-3403-000
T HR-VA- 09 / 100| 25 bar| +150 °C| 92 s             17 s| 41 s| 100 mm| 7100-0012-3022-000
T HR-VA- 09 / 150| 25 bar| +150 °C| 92 s             17 s| 41 s| 150 mm| 7100-0012-3032-000
T HR-VA- 09 / 200| 25 bar| +150 °C| 92 s             17 s| 41 s| 200 mm| 7100-0012-3042-000
T HR-VA-17/ 150| 25 bar| +150 °C| –                   45 s| 55 s| 150 mm| 7100-0012-3033-000
T HR-VA-17/ 200| 25 bar| +150 °C| –                   45 s| 55 s| 200 mm| 7100-0012-3404-000

Mounting diagram

S-S-REGELTECHNIKETR-Built-in-Temperature-Controllers-
FIG-13

COPYRIGHTS

© Copyright by S+S Regeltechnik GmbH

  • Reprint in full or in parts requires permission from S+S Regeltechnik GmbH.
  • Subject to errors and technical changes. All statements and data herein represent our best knowledge at date of publication. They are only meant to inform about our products and their application potential, but do not imply any warranty as to certain product characteristics. Since the devices are used under a wide range of different conditions and loads beyond our control, their particular suitability must be verified by each customer and/or end user themselves. Existing property rights must be observed. We warrant the faultless quality of our products as stated in our General Terms and Conditions.

ABOUT COMPANY

  • S+S REGELTECHNIK GMBH THURN-UND-TAXIS- STR. 22 90411 NÜRNBERG ⁄ GERMANY FON
  • +49 (0) 911 ⁄ 5 19 47- 0
  • mail@SplusS.de
  • www.SplusS.de

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

S S REGELTECHNIK User Manuals

Related Manuals