VENTS VUT 160 V EC Air Handling Unit User Manual
- June 6, 2024
- VENTS
Table of Contents
- VENTS VUT 160 V EC Air Handling Unit
- SAFETY REQUIREMENTS
- PURPOSE
- TECHNICAL DATA
- DESIGN AND OPERATING PRINCIPLE
- INSTALLATION AND SET-UP
- UNIT INSTALLATION
- CONNECTION TO POWER MAINS
- TECHNICAL MAINTENANCE
- POSSIBLE REASONS AND TROUBLESHOOTING
- STORAGE AND TRANSPORTATION REGULATIONS
- MANUFACTURER’S WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
VENTS VUT 160 V EC Air Handling Unit
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about purpose, technical details, operating
principle, design, and installation of the VUT/VUE 160/350/550 V(1)(B) EC unit
and all its modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
SAFETY REQUIREMENTS
- All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
- Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.
- Only qualified electricians with a work permit for electrical units up to 1000 V are allowed for installation and maintenance. The present user’s manual should be carefully read before beginning works.
- Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.
- While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and excessive noise.
- Misuse of the unit and any unauthorised modifications are not allowed.
- Do not expose the device to adverse atmospheric agents (rain, sun, etc.).
- Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.
- Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.
- Do not close or block the intake or extract vents in order to ensure the efficient air flow.
- Do not sit on the unit and do not put objects on it.
- The information in this user’s manual was correct at the time of the document’s preparation. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.
- Never touch the unit with wet or damp hands.
- Never touch the unit when barefoot.
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
- Children should be supervised to ensure that they do not play with the appliance.
- If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a safety hazard.
- If the cord set is damaged, it must be replaced by a special cord set available from the manufacturer or its service agent.
- The connection to the supply mains must be made through a means of disconnection, which is incorporated in the fixed wiring in accordance with the wiring rules, and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions.
- Ensure that the appliance is switched off from the supply mains before removing the guard.
- Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
PURPOSE
The unit is designed to ensure continuous mechanical air exchange in houses,
offices, hotels, cafes, conference halls, and other utility and public spaces
as well as to recover the heat energy contained in the air extracted from the
premises to warm up the filtered stream of intake air.
The unit is not intended for organizing ventilation in swimming pools, saunas,
greenhouses, summer gardens, and other spaces with high humidity.
Due to the ability to save heating energy by means of energy recovery, the
unit is an important element of energy-efficient premises. The unit is a
component part and is not designed for stand-alone operation. It is rated for
continuous operation.
Transported air must not contain any flammable or explosive mixtures,
evaporation of chemicals, sticky substances, fibrous materials, coarse dust,
soot and oil particles or environments favourable for the formation of
hazardous substances (toxic substances, dust, pathogenic germs).
DELIVERY SET
Name | Number |
---|---|
Air handling unit | 1 pc. |
User’s manual | 1 pc. |
Control panel* | 1 pc. |
Packing box | 1 pc. |
*The control panel is not included in the delivery set of units equipped with an A21 controller.
DESIGNATION KEY
TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature
ranging from +1 °C up to +40 °C and relative humidity up to 60 % without
condensation. In cold, damp rooms, there is a possibility of freezing or
condensation inside and outside the casing.
In order to prevent condensation on the internal walls of the unit, it is
necessary that the surface temperature of the casing is 2-3 °C above the dew
point temperature of the transported air.
The unit should be operated continuously, and in cases where ventilation is
not necessary, reduce the air flow of the fans to a minimum (20%). This will
ensure a favorable indoor climate and reduce the amount of condensation inside
the unit, which can damage electronic components. Never use the unit for
dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP22 for the unit connected to the air ducts
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly
different from those described in this manual.
MODEL
| VUT 160 V EC| VUE 160 V EC| VUT 160 VB EC| VUE 160 VB
EC| VUT 160 V1 EC| VUE 160 V1 EC| VUT 160 V1B EC| VUE 160
V1B EC| VUT 350 V1B EC| VUE 350 V1B EC| VUT 350 VB EC| VUE
350 VB EC| VUT 550 VB EC| VUE 550 VB EC
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Supply voltage [V/50 (60) Hz]| 1~ 220-240
Maximum fan power [W]| 57| 169| 178| 337
Maximum unit current (without a heater) [A]| 0.5| 1.3| 1.4| 2.4
Maximum air flow [m3/h]| 200| 420| 450| 690
RPM [min-1]| 3770| 3200| 2860
Sound pressure level at 3 m distance [dBA]| 24| 22| 28| 26
Transported air temperature [°С]| -25…+40
Casing material| Painted steel
Insulation, mineral wool [mm]| 20| 40
Filtering class of the extract filter| G4
Filtering class of the supply filter| F7 (optionally F8)
Connected air duct diameter [mm]| 125| 160| 200
Weight [kg]| 34| 36| 42| 44| 57| 64| 82
Heat recovery efficiency [%]| 85-93| 76-92| 85-93| 76-92| 85-93| 76-92| 85-93|
76-92| 85-92| 73-91| 85-92| 73-91| 84-92| 73-91
Heat exchanger type| Counter-flow
Heat exchanger material
|
Polystyrene
| Enthalpy membrane|
Polystyrene
| Enthalpy membrane|
Polystyrene
| Enthalpy membrane|
Polystyrene
| Enthalpy membrane|
Polystyrene
| Enthalpy membrane|
Polystyrene
| Enthalpy membrane|
Polystyrene
| Enthalpy membrane
SEC class| A+| A| A+| A| A+| A| A+| A| A+| A| A+| A| A+| A
Chart for determining the condition of condensate formation on the unit surface (mineral wool insulation 20 mm), with a correction of 10 degrees Chart for determining the condition of condensate formation on the unit surface (mineral wool insulation 40 mm), with a correction of 10 degrees
Model | Dimensions [mm] |
---|---|
Ø D | Ø D1 |
VUT/VUE 160 V EC | 125 |
VUT/VUE 160 V1 EC | 125 |
VUT/VUE 160 VB EC | 125 |
VUT/VUE 160 V1B EC | 125 |
VUT/VUE 350 VB EC | 160 |
VUT/VUE 350 V1B EC | 160 |
VUT/VUE 550 VB EC | 200 |
DESIGN AND OPERATING PRINCIPLE
The unit has the following operating principle: warm stale extract air from the room flows into the unit where it is filtered by the extract filter, then air flows through the heat exchanger and is exhausted outside by the extract fan. Cold fresh air from the outside flows into the unit, where it is cleaned by the supply filter. Then the air flows through the heat exchanger and is directed to the room with the supply fan. Heat energy of warm extract air is transferred to clean intake fresh air from the outside and warms it up. The air flows are fully separated while flowing through the heat exchanger. Heat recovery minimizes heat losses, which reduces the cost of space heating in the cold season.
UNIT DESIGN
- control unit;
- bypass damper (except for VUT/VUE 160 V(1) EC models);
- counter-flow heat exchanger;
- extract filter;
- supply filter;
- supply fan;
- extract fan;
- drain pan;
- drain pipe;
- differential pressure switch (only for VUT/VUE 550 A21 models);
- SETUP MODE button (for the units with A21 automation);
- cable glands;
- control unit lid.
The air handling unit is equipped with a hinged front service panel for repair
and maintenance operations. The removable service panel design enables to
change the service side location. The control unit is accessible for
installation and wiring operations through the inspection door on top of the
unit. The power cable and ground cable are connected to the control unit via
the cable glands.
The bypass damper is open or closed depending on operation mode of the unit.
The VUT/VUE 550 VB EC units are equipped with differential pressure switches
for filter contamination control. Access to the pressure switches is provided
through the inlet and outlet spigots.
The difference between the supply and extract air flow temperature leads to
condensate generation in the VUT 160/350/550 V(1)B EC units. Condensate is
collected in the drain pan and is removed outside through the drain pipe.
The VUE 160/350/550 V(1)B EC units are equipped with a heat exchanger with an
enthalpy membrane and do not require condensate drainage.
Accessories for the unit are available on a separate order.
- Humidity sensor. The HV2 sensor in the VUT/VUE 160/350/550 V(1)(B) EC A21 models is connected to the controller. In the VUT/VUE 160/350/550 V(1)(B) EC A14 models, the HV2 sensor is connected to the terminal block. The HR-S sensor is connected to the controller. The unit with an installed humidity sensor maintains a set indoor humidity point. As the extract air humidity rises above the set point, the system automatically switches to the maximum speed. As the humidity drops down below the set point the unit returns to the previous mode.
- CO2 sensor (connected to the controller). Designed for indoor carbon dioxide concentration measurement and respective air capacity regulation through the control output signal to the fan. Ventilation performance control according to current CO2 levels is an effective way to reduce energy consumption of a building.
- VOC sensor (connected to the controller). Qualitative assessment of air saturation with contaminants (cigarette smoke, exhaled air, solvent and detergent vapours).The sensor sensitivity can be adjusted with regards to the expected maximum level of air pollution. Enables on-demand ventilation which results in considerable energy savings as air is exchanged only upon reaching the preset level of pollution.
- NKP duct preheater (for the VUT/VUE 160/350/550 V(1) (B) EC A21 units). The heater maintains the duct air temperature at a point that prevents the heat exchanger freezing. Heater installation and connection to the unit are described in the heater user’s manual.
- NKD duct reheater (for the VUT/VUE 160/350/550 V(1) (B) EC A21 units). The heater maintains a room temperature set by the temperature sensor. Heater installation and connection to the unit are described in the heater user’s manual.
UNIT OPERATION MODES
Heat Recovery mode
Warm extract air from the room flows into the unit and is cleaned in the
extract filter. Then the air is moved through the heat exchangers and is
exhausted outside with the extract fan. Cold fresh air from outside flows into
the unit, where it is cleaned in the supply filter. Then the air flows through
the heat exchanger and is directed to the room with the supply fan.
Heat is exchanged between the intake and extract air in the heat exchanger.
The air flows are fully separated while flowing through the heat exchanger.
Heat recovery minimizes heat losses, which reduces the cost of space heating
in the cold season.
Summer Cooling mode
The bypass damper is opened, the extract air that is removed from the premises
is routed along the bypass duct and does not come in contact with the heat
exchanger. The temperature of the air is not changed after passing through the
heat exchanger. Heat exchanger freeze protection (frost danger appears when
the extract air temperature downstream of the heat exchanger is lower than +5
°C and intake air temperature upstream of the heat exchanger is lower than -3
°C for units with preheating and +3 °C for units without preheating).
In case of freezing danger the supply fan is turned off in the VUT/VUE
160/350/550 V(1) (B) EC A14 units.
When the temperature increases, the unit returns to the previous operation
mode.
There are three freeze protection modes for the VUT/VUE 160/350/550 V(1) (B) EC A21 units:
- gradual speed reduction of the supply fan
- with the help of a bypass
- with the help of electric preheating of air (if the unit is equipped with a duct preheater) Mode selection and settings are described in the A21 control system user’s manual.
INSTALLATION AND SET-UP
READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.
AFTER INSTALLING THE UNIT, LOCK THE LATCH TO PREVENT ACCIDENTAL OPENING OF THE COVER.
SERVICE SIDE CHANGE
The unit design allows changing the service side.
Install the service panel on the opposite side, connect it with a ground wire.
Install the back cover.
Attach the hinge stopper.
UNIT INSTALLATION
To get the best performance of the unit and to minimize turbulence-induced air
pressure losses, connect the straight air duct section to the spigots on both
sides of the unit while installing.
Minimum straight air duct length:
- equal to 1 air duct diameter on the intake side
- equal to 3 air duct diameter on the outlet side
If the air ducts are too short or not connected, protect the unit parts from
ingress of foreign objects. To prevent uncontrollable access to the fans, the
spigots may be covered with a protecting grille or other protecting device
with mesh width not more than 12.5 mm.
When selecting the unit mounting position, enable free excess to the service
panel for maintenance and service operations.
The unit should be mounted strictly horizontally in the longitudinal and
transverse planes. In case of non-compliance, unit’s casing distortion and
operation disturbance will occur.
Unit wall mounting
Dowels for wall mounting are not included in the delivery set and should be
ordered separately.
While choosing dowels consider the material of the mounting surface as well as
the weigh of the unit, refer to the “Technical data” section. Dowels for unit
mounting should be selected by the installation specialist.
Install the dowels in the wall. Install the screws. Suspend the unit. Achieve
a strictly vertical position of the unit by rotating the adjustable stop (1).
Unit floor mounting
Install the unit on the pre-mounted floor supports, minimum 150 mm height, to
ensure sufficient access for the drain pipe connection to the U-trap and for
condensate drain system installation. CONDENSATE DRAINAGE
Condensate drainage is required for the VUT 160/350/550 V(1)(B) EC unit
series.
The hole for the drain pipe is at the bottom of the unit. Remove the plug from
the hole. Open the service panel and remove the plug in the drain pan. Install
the drain pipe from the delivery set into the hole, then connect the drain
pipe to the sewage system using the SFK 20×32 U-trap kit (available upon
separate order). Make sure the U-trap is always filled with water. The pipe
slope downwards must be at least 3°.
CONNECTION TO POWER MAINS
WARNING:
-
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL. -
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
The unit is rated for connection to 1~220-240 В/50 (60) Гц power mains.
The external power input must be equipped with an automatic circuit breaker
built into the stationary wiring to open the electric circuit in case of
overload or short-circuit. The circuit breaker installation place must provide
quick access for emergency shutdown of the unit. The trip current of the
automatic circuit breaker must exceed the maximum current consumption of the
unit (refer to the technical data table). The recommended trip current of the
circuit breaker is the next current in the standard trip current row following
the maximum current of the connected unit. The automatic circuit breaker is
not included in the delivery set.
For accessing the terminal block and the controller undo the screws of the terminal box cover and remove it.
Route the cables to the control unit through the cable glands in the unit. Carry out the electrical connections as shown in the wiring diagram.
EXTERNAL WIRING DIAGRAM FOR THE VUT/VUE 160/350/550 V(1)(B) EC A14 UNITS
Designation | Name | Model | Wire** |
---|---|---|---|
SM1* | Supply air damper actuator | 2 x 0.75 mm2 | |
SM2* | Extract air damper actuator | 2 x 0.75 mm2 | |
РК1* | Contact from fire alarm panel | NC | 2 x 0.75 mm2 |
С02* | CO2 sensor | NO | 2 x 0.75 mm2 |
HV1* | Humidity sensor | 3 x 0.75 mm2 | |
P1 | External control panel | 4 x 0.25 mm2 |
EXTERNAL CONNECTIONS DIAGRAM FOR THE VUT/VUE 160 V(1) B EC A21 UNITS
Designation | Name | Model | Wire type | Note |
---|---|---|---|---|
SM1* | Supply air damper actuator | NO | 2 x 0.75 | 3 A, 30VDC/~250 AC |
SM2* | Extract air damper actuator | NO | 2 x 0.75 | 3 A, 30VDC/~250 AC |
РК1 | Contact from fire alarm panel | NC | 2 x 0.75 | Remove the jumper 2 |
CCU | Cooler control | NO | 2 x 0.75 | 3 A, 30VDC/~250 AC |
Р1 | External control panel | 4 x 0.25 | ||
Boost | Boost On/Off contacts of the Boost mode | NO | 2 x 0.75 | |
CO2 | External CO2 sensor | 3 x 0.25 | ||
EVH | Duct heater (for preheating) | 4 x 0.5 | ||
ENH | Duct heater (for reheating) | 4 x 0.5 | ||
ENH RT2** | Duct temperature sensor | 2 x 0.25 | Remove the jumper 37 |
*The supply voltage U of the SM1, SM2 external dampers is selected depending on the type of dampers. **Part of ENH.
EXTERNAL CONNECTIONS DIAGRAM FOR THE VUT/VUE 350/550 V(1) B EC A21 UNITS
Designation | Name | Model | Wire type | Note |
---|---|---|---|---|
SM1* | Supply air damper actuator | NO | 2 x 0.75 | 3 A, 30VDC/~250 AC |
SM2* | Extract air damper actuator | NO | 2 x 0.75 | 3 A, 30VDC/~250 AC |
РК1 | Contact from fire alarm panel | NC | 2 x 0.75 | Remove the jumper 2 |
CCU | Cooler control | NO | 2 x 0.75 | 3 A, 30VDC/~250 AC |
Р1 | External control panel | 4 x 0.25 | ||
Boost | Boost On/Off contacts of the Boost mode | NO | 2 x 0.75 | |
CO2 | External CO2 sensor | 3 x 0.25 | ||
EVH | Duct heater (for preheating) | 4 x 0.5 | ||
ENH | Duct heater (for reheating) | 4 x 0.5 | ||
ENH RT2** | Duct temperature sensor | 2 x 0.25 | Remove the jumper 37 |
*The supply voltage U of the SM1, SM2 external dampers is selected depending on the type of dampers. **Part of ENH.
TECHNICAL MAINTENANCE
Maintenance operations of the unit are required 3-4 times per year. They include general cleaning of the unit and the following operations:
Filter maintenance (3-4 times per year).
Dirty filters increase air resistance in the system and reduce supply air
volume. The filters require cleaning not less than 3-4 times per year. Clean
the filter with a vacuum cleaner or replace it with a new one. For new filters
contact the Seller.
Heat exchanger maintenance (once per year).
Some dust may accumulate on the heat exchanger even in case of regular
maintenance of the filters. To maintain the high heat recovery efficiency,
regular cleaning is required. To clean the heat exchanger, remove it from the
unit and clean the heat exchanger by using compressed air or a vacuum cleaner.
In case of severe contamination, the heat exchanger can be washed with water.
After cleaning, re-install the heat exchanger into the unit. Fan maintenance
(once per year).
Even in case of regular maintenance of the filters, some dust may accumulate
inside the fans and reduce the fan performance and supply air flow. Fans
should be cleaned by the service technician.
Condensate drainage system maintenance (4 times per year).
The condensate drainage (drain line) may get clogged by dirt and dust
particles contained in the exhaust air. Check the drain line operation by
filling the drain pan under the unit with water, clean the U-trap and the
drain line, if necessary.
Supply air flow control (twice per year).
The supply duct grille may get clogged with leaves and other objects reducing
the unit performance and supply air delivery. Check the supply grille twice
per year and clean it as required.
Ductwork system maintenance (once in 5 years).
Even regular fulfilling of all the maintenance operations prescribed above may
not completely prevent dirt accumulation in the air ducts, which leads to air
pollution and reduces the unit capacity. Duct maintenance means regular
cleaning or replacement.
WARNING:
IF UNIDENTIFIED NOISES OR ODOURS SHOULD ARISE AND IN CASE OF DEFORMATION OF
ELEMENTS, VIBRATION, TERMINATION OF AIR SUPPLY/EXTRACTION OR REDUCED SYSTEM
PERFORMANCE, IMMEDIATELY DISCONNECT THE UNIT FROM POWER SUPPLY AND CONTACT THE
SELLER FOR THE VENTILATION SYSTEM DIAGNOSTICS.
DIAGNOSTICS MUST BE CARRIED OUT BY QUALIFIED SPECIALISTS.
POSSIBLE REASONS AND TROUBLESHOOTING
Problem | Possible reasons | Troubleshooting |
---|
The fan(s) does not start when the unit is on.
| No power supply.| Make sure the power supply line is connected correctly, otherwise troubleshoot the connection error.
The mode in which the fans are turned off is set.
| ****
Change the mode with the help of the control panel.
Low air flow.
| Low set fan speed.| Set higher speed.
The filters and the fans are clogged, the heat exchanger is clogged.| Clean or
replace the filters, clean the fans and the heat exchanger.
Ventilation system elements (air ducts, diffusers, louver shutters, grilles)
are clogged, damaged or closed.| Clean or replace the ventilation system
elements, such as air ducts, diffusers, louvre shutters, grilles.
Cold supply air.| The extract filter is soiled.| Clean or replace the extract
filter.
Noise, vibration.
| The fan or casing screw connection is loose.| Tighten the screw connection
of the fans or the casing.
No anti-vibration connectors on air duct pipe flanges.| Install anti-vibration
connectors.
Water leakage
(only for the VUT VB EC units)
| The drainage system is soiled, damaged, or installed incorrectly.| Clean the drain line. Check the drain line slope angle. Make sure that the U-trap is filled with water and the drain pipes are frost protected.
If troubleshooting steps have failed, contact the Seller of the product.
In case of faults not described in the table, contact the Seller for further
information.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range +5 ˚…+40 ˚С and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility. We hereby declare that the
product complies with the provisions of Electromagnetic Compatibility (EMC)
Directive 2014/30/EU of the European Parliament and of the Council, Low
Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the
Council and CE-marking Council Directive 93/68/EEC. This certificate is issued
following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 месяца
after the retail sale date provided the user’s observance of the
transportation, storage, installation, and operation regulations. Should any
malfunctions occur in the course of the unit operation through the
Manufacturer’s fault during the guaranteed period of operation, the user is
entitled to get all the faults eliminated by the manufacturer by means of
warranty repair at the factory free of charge. The warranty repair includes
work specific to elimination of faults in the unit operation to ensure its
intended use by the user within the guaranteed period of operation. The faults
are eliminated by means of replacement or repair of the unit components or a
specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
WARNING:
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE
STAMP.
CERTIFICATE OF ACCEPTANCE
Unit Type | Приточно-вытяжная установка |
---|---|
Model | VUT/VUE ____ |
Serial Number | |
Manufacture Date |
Quality Inspector’s Stamp
|
SELLER INFORMATION
Seller|
---|---
Address|
Phone Number|
E-mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s
manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|
INSTALLATION CERTIFICATE
The VUT/VUE __ unit is installed pursuant to the requirements stated in the present user’s manual.
Company name|
Address|
Phone Number|
Installation Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the
applicable local and national construction, electrical and technical codes and
standards. The unit operates normally as intended by the manufacturer.
Signature:|
WARRANTY CARD
Unit Type | Приточно-вытяжная установка |
---|---|
Model | VUT/VUE ____ |
Serial Number | |
Manufacture Date | |
Purchase Date | |
Warranty Period | |
Seller |
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>