VENTS VUT 230 V5 Air Handling Unit User Manual

October 30, 2023
VENTS

VENTS VUT 230 V5 Air Handling Unit

VENTS VUT 230 V5 Air Handling Unit

This user’s manual is a main operating document intended for technical, maintenance, and operating staff.
The manual contains information about purpose, technical details, operating principle, design, and installation of the VUT/VUE 230 V5 unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be  able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.

SAFETY REQUIREMENTS

This unit is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the unit by a person responsible for their safety. Children should be supervised to ensure that they do not play with the unit.

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.

Cleaning and user maintenance shall not be made by children without supervision. Children shall not play with the appliance.

If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a safety hazard.

Ensure that the unit is switched off from the supply mains before removing the guard.

Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.

All operations described in this manual must be performed by qualified personnel only, properly trained and qualified to install, make electrical connections and maintain ventilation units.
Do not attempt to install the product, connect it to the mains, or perform maintenance yourself.
This is unsafe and impossible without special knowledge.
Disconnect the power supply prior to any operations with the unit.
All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to 1000 V are allowed for installation. The present user’s manual should be carefully read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the document’s preparation.
The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
BEFORE INSTALLING ADDITIONAL EXTERNAL DEVICES, READ THE RELEVANT USER MANUALS.

THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.

PURPOSE

The unit is designed to ensure continuous mechanical air exchange in houses, offices, hotels, cafes, conference halls, and other utility and public spaces as well as to recover the heat energy contained in the air extracted from the premises to warm up the filtered stream of intake air.
The unit is not intended for organizing ventilation in swimming pools, saunas, greenhouses, summer gardens, and other spaces with high humidity.
Due to the ability to save heating energy by means of energy recovery, the unit is an important element of energy-efficient premises.
The unit is a component part and is not designed for stand-alone operation. It is rated for continuous operation.
Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot and oil particles or environments favourable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).

DELIVERY SET
Name Number
Air handling unit 1 pc.
User’s manual 1 pc
User’s manual for control panel 1 pc.
Control panel 1 pc.
Installation kit 1 pc.
Packing box 1 pc.

DESIGNATION KEY

Designation Key

TECHNICAL DATA

The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative  humidity up to 60 % without condensation. In cold, damp rooms, there is a possibility of freezing or condensation inside and outside the casing.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above the dew point temperature of the transported air.
The unit should be operated continuously, and in cases where ventilation is not necessary, reduce the air flow of the fans to a minimum (20%). This will ensure a favorable indoor climate and reduce the amount of condensation inside the unit, which can damage electronic components. Never use the unit for dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP22 for the unit connected to the air ducts
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.

TECHNICAL DATA

Model VUT 230 V5 VUE 230 V5
Unit voltage [V/50 (60) Hz] 1 ~ 220-240
Maximum fan power [W] 163
Maximum unit current [A] 0.7
Maximum air capacity [m³/h] 230
Sound pressure level at a distance of 3 m [dBA] 35
Transported air temperature [°С] -25…+40
Casing material EPP
Heat insulating material EPP 15…26 mm
Extract filter filtration class G4
Supply filter filtration class G4 (optionally F8)
Connected spigot diameter 125
Weight [kg] 13 13.5
Heat recovery efficiency [%] 87-98 % 72-94 %
Heat exchanger type Counter-flow
Heat exchanger material polystyrene enthalpy membrane
SEC class B C

Dimensions

Model Dimensions [mm]
Ø D Ø D1
VUT/VUE 230 V5 125

DESIGN AND OPERATING PRINCIPLE

The unit has the following operating logic: warm stale extract air from the room flows into the unit, where it is filtered by the extract filter, then air flows through the heat exchanger and is exhausted outside by the exhaust fan. Cold fresh air from the outside flows into the unit, where it is cleaned by the intake filter. Then the air flows through the heat exchanger and is directed to the room with the supply fan. Heat energy of warm extract air is transferred to clean intake fresh air from the outside and warms it up. The air flows are fully separated while flowing through the heat exchanger. Heat recovery minimizes heat losses, which reduces the cost of space heating in the cold season.
Design And Operating Principle

  1. exhaust fan;
  2. control unit;
  3. supply air filter;
  4. counter-flow heat exchanger;
  5. drain pipe (VUT 230 V5);
  6. supply fan;
  7. exhaust air filter;
  8. drain pan.

The service side of the unit is equipped with a detachable plate for filter and heat exchanger cleaning and replacement operations.
The control unit is positioned inside the unit casing. The power cable and grounding cables are connected to the control unit through the hole on the side of the unit. The difference between the supply and extract air flow temperature leads to condensate generation. Condensate is collected in the drain pan and is removed outside through the drain pipes.

UNIT OPERATION MODES

Heat recovery
Warm stale extract air from the room flows into the unit, where it is filtered by the intake filter, then air flows through the heat exchanger and is exhausted outside by the exhaust fan. Cold fresh air from the outside flows into the unit, where it is cleaned by the supply filter. Then the air flows through the heat exchanger and is directed to the room with the supply fan. Supply air is heated in the heat exchanger by transferring the heat energy of warm and humid extract air to the cold fresh air. The air flows are fully separated while flowing through the heat exchanger. Heat recovery minimizes heat losses, which
reduces the cost of space heating in the cold season.
Unit Operation Modes

Freeze protection
The heat exchanger freeze protection function of the unit is implemented with a temperature sensor. The sensor is installed in the exhaust air duct downstream of the heat exchanger. In case of a freezing danger the supply fan is turned off and the heat exchanger is warmed up with warm extract air flow. After temperature increase the unit returns to the previous operation mode.
Unit Operation Modes

INSTALLATION AND SET-UP

READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.

UNIT INSTALLATION

To reach the highest performance of the unit and to minimize turbulence- induced air pressure losses, connect the straight air duct section to the spigots while installing.

Minimum straight air duct length:

  • equal to 1 air duct diameter on the intake side
  • equal to 3 air duct diameters on outlet side

Push the air ducts onto the flanges until stop. Flexible ducts must be fixed rigidly with a metal worming clamp.
Unit Installation

If the air ducts are too short or not connected, protect the unit parts from ingress of foreign objects.
To prevent uncontrollable access to the fans, the spigots may be covered with a protecting grille or other protecting device with mesh width not more than 12.5 mm.

While installing the unit, ensure convenient access for subsequent maintenance and repair.
The unit must be mounted on a flat floor.

Installing the unit to an uneven surface could lead to the unit’s casing distortion and operation disturbance.

Do not expose the unit to direct sunlight.

Unit floor mounting
Install the unit on the pre-mounted floor supports, minimum 150 mm height, to ensure sufficient access for the drain pipe connection to the U-trap and for condensate drain system installation.

Unit wall mounting

Fasteners (dowels, self-tapping screws) for wall mounting are not included in the delivery set and should be ordered separately.

While choosing fasteners consider the material of the mounting surface as well as the weigh of the unit, refer to the Technical data section.

Fasteners for unit installation should be selected by a qualified technician.

Secure the wall bracket at required height.

Hang the unit on the wall bracket and secure it with a screw.
Unit wall mounting

CONDENSATE DRAINAGE

Condensate drainage is required for the VUT 230 V5 unit series. The VUE 230 V5 units are equipped with an enthalpy membrane heat exchanger. No condensate is generated in heat exchangers of this type, therefore, no condensate drainage is required. The hole for the drain pipe connection is located at the bottom of the unit. Open the service panel, remove the heat exchanger and filters, drill a 22 mm hole in the plastic pan in the exhaust air duct and install the drain pipe (supplied) in the hole. Then connect the drain pipe to the sewage system using the SG-32 U-trap kit (purchased separately). The pipe slope downwards must be at least 3°.
Condensate Drainage

1 – drain pipe; 2,4 – drain hose; 3 – U-trap; 5 – sewage system.

The condensate drainage system is designed for normal operation in premises with air temperatures above 0 °C!
If the expected ambient air temperatures are below 0 °C, the condensate drainage system must be equipped with heat insulation and pre-heating facilities.

SERVICE SIDE CHANGE

RIGHT-HANDED INSTALLATION

Right-handed Installation

LEFT-HANDED INSTALLATION

Left-handed Installation

Make sure of the correct unit service side selection. Unit mounting position should enable free excess to the opening plate for maintenance and service operations. The plate opposite to the service side must be fixed with the supplied screws.

CONNECTION TO POWER MAINS

POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.

ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.

DO NOT LAY THE POWER CABLE OF THE UNIT IN CLOSE PROXIMITY TO THE CONTROL PANEL CABLE! DO NOT COIL THE CABLE FROM THE CONTROL PANEL IN LOOPS WHILE LAYING IT.
Symbol

The air handling unit is rated for connection to single-phase AC 220-240 V/50 (60) Hz power mains.

Connect the unit to power mains using the supplied power cable with the mains plug.

The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the circuit in the event of overload or short-circuit.

The position of the external circuit breaker must ensure free access for quick power-off of the unit.

The trip current must be in compliance with the consumption current, refer to Technical data.

Complete the electrical connections through the terminal block in the control unit as shown in the external wiring diagram.
Connection To Power Mains

EXTERNAL WIRING DIAGRAM FOR UNITS WITH SPEED CONTROLLER A3

— Electric shock hazard!

Name **Wire***
Speed controller 4 x 0.75 mm2

*Maximum connecting cable length is 20 m!

EXTERNAL WIRING DIAGRAM FOR UNITS WITH SPEED CONTROLLER A4

— Electric shock hazard!

Name **Wire***
Speed controller 4 x 0.75 mm2

*Maximum connecting cable length is 20 m!

TECHNICAL MAINTENANCE

Maintenance operations of the unit are required 3-4 times per year. It includes general cleaning of the unit and the following operations:

  1. Filter maintenance (3-4 times per year)
    Dirty filters increase air resistance in the system and reduce supply air volume.
    The filters require cleaning not less than 3-4 times per year.
    Vacuum cleaning is allowed.
    After two consecutive cleanings filters must be replaced.
    For new filters, contact the Seller.
    To clean or replace the filters, detach the removable plates located on the service side of the unit.
    After cleaning install the filters and the detachable plates in the reverse order.

  2. Heat exchanger maintenance (once per year)
    Some dust may accumulate on the heat exchanger even in case of regular maintenance of the filters.
    To maintain the high heat recovery efficiency, regular cleaning is required.
    Before removing the heat exchanger, detach the removable plate located on the service side of the unit.
    To clean the heat exchanger pull it out, drain the water through the pipes, then flush the heat exchanger with warm detergent solution.
    After cleaning install the dry heat exchanger with the drain pan back to the unit.

  3. Drain system maintenance (once per year)
    The condensate drainage (drain line) may get clogged by dirt and dust particles contained in the exhaust air.
    Pour some water inside the drain pan to check the pipe for clogging. Clean the U-trap and the drain pipe if required.

  4. Technical maintenance of air duct system (every 5 years)
    Even regular fulfilling of all the maintenance operations prescribed above may not completely prevent dirt accumulation in the air ducts, which reduces the unit capacity.
    Duct maintenance means regular cleaning or replacement.

  5. Control unit maintenance (if necessary)
    The control unit maintenance must be performed by an expert qualified for unassisted operations with electrical installations with the voltage up to 1000 V after careful reading of the user’s manual.

POSSIBLE REASONS AND TROUBLESHOOTING

Problem Possible reasons Troubleshooting
The fan(s) does not start when the unit is on. No power supply. Make sure

the power supply line is connected correctly, otherwise troubleshoot the connection error.
The motor is jammed, the impeller blades are soiled.| Turn the unit off. Troubleshoot the motor jam and the impeller clogging. Clean the blades. Restart the unit.
Alarm in the system.| Turn the unit off. Contact the Seller.
Automatic circuit breaker trips following the unit turning on.| Overcurrent as a result of short circuit in the electric circuit.| Turn the unit off. Contact the Seller.
Low air flow.| Low set fan speed.| Set higher speed.
The filters and the fans are clogged, the heat exchanger is clogged.| Clean or replace the filters, clean the fans, and the heat exchanger.
Ventilation system elements (air ducts, diffusers, louver shutters, grilles) are clogged, damaged, or closed.| Clean or replace the ventilation system elements, such as air ducts, diffusers, louver shutters, grilles.
Cold supply air.| The extract filter is soiled.| Clean or replace the extract filter.
Noise, vibration.| The impeller(s) is soiled.| Clean the impeller(s).
The fan or casing screw connection is loose.| Tighten the screw connection of the fans or the casing all the way.
No anti-vibration connectors on air duct pipe flanges.| Install anti-vibration connectors.
Water leakage (only for the VUT units).| The drainage system is soiled, damaged, or installed incorrectly.| Clean the drain line if necessary. Check the drain line slope angle. Make sure that the U-trap is filled with water and the drain pipes are frost protected.

STORAGE AND TRANSPORTATION REGULATIONS

  • Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range +5…+40 ˚С and relative humidity up to 70 %.
  • Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
  • Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
  • Follow the handling requirements applicable for the particular type of cargo.
  • The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
  • Avoid sharp blows, scratches, or rough handling during loading and unloading.
  • Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.

MANUFACTURER’S WARRANTY

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.

The warranty repair does not include:

  • routine technical maintenance
  • unit installation/dismantling
  • unit setup

To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.

The manufacturer’s warranty does not apply to the following cases:

  • User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
  • Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
  • User’s failure to ensure timely technical maintenance of the unit.
  • External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
  • Redesign or engineering changes to the unit.
  • Replacement and use of any assemblies, parts and components not approved by the manufacturer.
  • Unit misuse.
  • Violation of the unit installation regulations by the user.
  • Violation of the unit control regulations by the user.
  • Unit connection to power mains with a voltage different from the one stated in the user’s manual.
  • Unit breakdown due to voltage surges in power mains.
  • Discretionary repair of the unit by the user.
  • Unit repair by any persons without the manufacturer’s authorization.
  • Expiration of the unit warranty period.
  • Violation of the unit transportation regulations by the user.
  • Violation of the unit storage regulations by the user.
  • Wrongful actions against the unit committed by third parties.
  • Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
  • Missing seals if provided by the user’s manual.
  • Failure to submit the user’s manual with the unit purchase date stamp.
  • Missing payment paperwork certifying the unit purchase.

FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND
TROUBLE-FREE OPERATION OF THE UNIT

USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP.

CERTIFICATE OF ACCEPTANCE

Unit Type Air handling unit
Model
Serial Number
Manufacture Date
**Quality Inspector’s Stamp**

SELLER INFORMATION

Seller| |
---|---|---
Address|
Phone Number|
E-mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|

INSTALLATION CERTIFICATE

This unit is installed pursuant to the requirements stated in the present user’s manual.|
---|---
Company name|
Address|
Phone Number|
Installation Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:|

WARRANTY CARD

Unit Type| Air handling unit|
---|---|---
Model|
Serial Number|
Manufacture Date|
Purchase Date|
Warranty Period|
Seller|

V170-2EN-02

VENTS Logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>