VENTS JAF Impulse Axial Fan
This user’s manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about purpose, technical details, operating principle, design, and installation of the JAF unit and all its modifications. Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
SAFETY REQUIREMENTS
All user’s manual requirements as well as the provisions of all the applicable
local and national construction, electrical, and technical norms and standards
must be observed when installing and operating the unit. Disconnect the unit
from the power supply prior to any connection, servicing, maintenance, and
repair operations. Only qualified electricians with a work permit for
electrical units up to 1000 V are allowed for installation and maintenance.
The present user’s manual should be carefully read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the
grille before starting installation. The casing internals must be free of any
foreign objects that can damage the impeller blades. While mounting the unit,
avoid compression of the casing! Deformation of the casing may result in motor
jam and excessive noise. Misuse of the unit and any unauthorised modifications
are not allowed. Do not expose the device to adverse atmospheric agents (rain,
sun, etc.). Transported air must not contain any dust or other solid
impurities, sticky substances, or fibrous materials. Do not use the unit in a
hazardous or explosive environment containing spirits, gasoline, insecticides,
etc.
Do not close or block the intake or extract vents in order to ensure the
efficient air flow. Do not sit on the unit and do not put objects on it. The
information in this user’s manual was correct at the time of the document’s
preparation. The Company reserves the right to modify the technical
characteristics, design, or configuration of its products at any time in order
to incorporate the latest technological developments. Never touch the unit
with wet or damp hands. Never touch the unit when barefoot. This appliance is
not intended for use by persons (including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the
appliance by a person responsible for their safety. Children should be
supervised to ensure that they do not play with the appliance.
The connection to the supply mains must be made through a means of
disconnection, which is incorporated in the fixed wiring in accordance with
the wiring rules, and has a contact separation in all poles that allows for
full disconnection under overvoltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent, or similarly qualified persons in order to avoid a safety
hazard.
Ensure that the appliance is switched off from the supply mains before
removing the guard.
Precautions must be taken to avoid the back-flow of gases into the room from
the open flue of gas or other fuel-burning appliances.
| THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE. DO
NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
---|---
PURPOSE
| THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED
PHYSICAL, MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE
TRAINING. THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED
PERSONNEL AFTER THE APPROPRIATE BRIEFING. THE CHOICE OF UNIT INSTALLATION
LOCATION MUST PREVENT UNAUTHORISED ACCESS BY UNATTENDED CHILDREN.
---|---
DESIGNATION KEY
NAME | NUMBER |
---|---|
Fan | 1 pc |
User’s manual | 1 pc |
Packing box | 1 pc |
DESIGNATION KEY
TECHNICAL DATA
The unit is rated as a Class I electrical appliance. Ingress protection rating
against access to hazardous parts and water ingress is IP55 for the motor and
IP54 for the unit. The fan design is constantly being improved, thus some
models may be slightly different from those described in this manual.
Model | Dimensions [mm] | Weight [kg] |
---|---|---|
Ø D1 | A | B |
Unidirectional
JAF-CI-315-U| 414| 302| 355| 425| 1654| 1763| 40
JAF-CI-355-U| 467| 302| 420| 482| 1954| 2079| 50
JAF-CI-400-U| 515| 351| 460| 525| 2004| 2129| 65
JAF-CI-450-U| 565| 351| 500| 575| 2004| 2129| 85
JAF-CI-500-U| 603| 371| 580| 620| 2004| 2145| 110
JAF-CI-560-U| 663| 446| 620| 678| 2093| 2247| 155
JAF-CI-630-U| 733| 550| 710| 748| 2193| 2357| 245
Reversible
JAF-CI-315-R| 414| 302| 355| 425| 1654| 1872| 40
JAF-CI-355-R| 467| 302| 420| 482| 1954| 2202| 50
JAF-CI-400-R| 515| 351| 460| 525| 2004| 2253| 65
JAF-CI-450-R| 565| 351| 500| 575| 2004| 2253| 85
JAF-CI-500-R| 603| 371| 580| 620| 2004| 2290| 110
JAF-CI-560-R| 663| 446| 620| 678| 2093| 2400| 155
JAF-CI-630-R| 733| 550| 710| 748| 2193| 2520| 245
DESIGN AND OPERATING PRINCIPLE
Casing
The fans are supplied in an all-welded metal casing with rolled flanges. All
the casing components are powder coated for improved protection against the
environmental effects. The casing has special brackets for mounting the motor
which also double as guides and ensure even distribution of air across the
impeller blades thereby improving the aerodynamic performance. The fans also
have external mounting brackets for ceiling or wall mounting. A terminal box
is mated to the casing for quick and convenient electrical connections.
Silencers
Sound insulation is achieved by means of cylindrical silencers installed on
both sides. The casing of the silencers is completely lined with wear-
resistant mineral wool and perforated sheet. The silencer 1 at the inlet is
equipped with an aerodynamically optimized inlet nozzle, and the silencer 2 at
the outlet is equipped with louvre shutters.
Motor
The fans are driven by three-phase asynchronous electric motors with a square-
cage rotor. The motor is installed inside the fan casing. The impeller of the
motor is equipped with an axial high-efficient and dynamically balanced
impeller with blades of optimized shape made of corrosion-resistant aluminium
alloy.
MOUNTING AND SET-UP
| BEFORE MOUNTING MAKE SURE THE CASING DOES NOT CONTAIN ANY FOREIGN OBJECTS
(E.G. FOIL, PAPER).
---|---
| WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT
MAINTENANCE AND REPAIR.
---|---
Before installing the unit, carry out the following checks:
- Make sure that the fan impeller rotates freely.
- Make sure there is no condensate on the motor.
- Check the electrical resistance of insulation between the motor windings and between each winding and the motor casing. After installing the unit, you need to make sure that the fan impeller rotates freely.
Wall or ceiling mounting with fixing brackets. Installation is carried out at 4 points using dowels or mounting studs. The specially designed anti-vibration mounts (specially ordered accessories) are recommended for vibration absorption. While choosing fasteners consider the material of the mounting surface as well as the weigh of the fan, refer to the “Technical data” section. Fasteners for fan mounting are not included in the delivery set and should be ordered separately. Fasteners for unit mounting should be selected by the service technician.
CONNECTION TO POWER MAINS
| DISCONNECT THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED ELECTRICIAN
WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER
CAREFUL READING OF THE PRESENT USER’S MANUAL.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S
LABEL.
---|---
| ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE
WARRANTY.
---|---
- The unit is rated for connection to 3~400 V/50(60) Hz according to the wiring diagram. The connection must be made using insulated conductors (cables, wires). The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and installation method.
- The unit must be connected to power supply in accordance with the applicable standards.
The axial impulse fan is designed for integration into an automatic control system and is not intended for standalone operation. Connect the fan motor via the terminal block (X1) by means of a durable heat-resistant insulated cable according to the wiring diagram and the terminal designations. The terminal block and the terminal designation label are inside the terminal box. The terminal box is installed on the fan casing or on a mounting bracket depending on the particular model.
**Single-speed fan wiring diagram
Two-speed fan wiring diagram: -running at low speed
Two-speed fan wiring diagram:- running at high speed
**
| MAKE SURE THAT THE FAN IMPELLER ROTATES IN THE DIRECTION MARKED BY THE ARROW
ON THE FAN CASING.
IF NECESSARY, CHANGE THE IMPELLER ROTATION DIRECTION BY ALTERING THE PHASE
SEQUENCE ON THE ELECTRIC MOTOR TERMINALS.
---|---
ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS
There are several methods for starting asynchronous squirrel-cage electric
motors. The most common methods are: direct-on-line (DOL), with a soft starter
(SS) or with a frequency converter (FC).
Direct-on-line starting In case of direct-on-line starting (i.e. by
connecting the motor to the electric mains with a simple line contactor), the
motor starting time significantly increases due to high inertia of the
impeller, which, in turn, results in high in-rush starting currents in the
circuit. These currents of long duration may cause voltage slumps (especially
if the feed line section falls short of the requirements), which may affect
load operation. The in-rush current consumed by an electric motor in case of
DOL starting is 5-8 times larger than the rated value (or even 10-14 times
larger in some rare instances). It should be noted that the torque developed
by the motor also significantly exceeds the rated value. Upon energisation the
motor operates as a transformer with a squirrel-cage secondary winding formed
by the rotor cage with a very low resistance. The rotor develops high induced
current causing a rush of current in the feed line. The startup torque during
starting averages 0.5-1.5 of the rated torque value.
Despite such advantages as simple construction, high startup current, quick
start and low cost, direct-on-line systems are suitable only in the following
cases:
- the motor power is low compared to the mains power which limits the adverse effect of the rush of current
- the driven mechanism does not require gradual speed build-up or is equipped with a damping device to smooth out the inrush
- the high startup torque has no adverse effects on the operation of the driven mechanism
Soft start. SS starting.
A soft starter gradually increases the voltage supplied to the motor from
the initial to the rated value. This starting system can be used to meet the
following goals:
- limit the motor current
- regulate the torque
Regulation by limiting the current sets the maximum in-rush current equal to 300-400 % (or 250 % in some rare instances) of the rated current and reduces torque characteristics. This type of regulation is especially suited for turbomachinery such as centrifugal pumps and fans. Regulation by variation of torque optimizes the torque during startup and reduces in-rush current in the circuit. These conditions are suitable for mechanisms with constant load resistance. This type of soft starting may differ in the implementation pattern:
- motor start · motor start and stop
- device bridging at the end of start sequence
- start and stop of several motors in stage circuits
Soft start. FC starting. During the starting the FC raises the frequency from 0 Hz to the electrical mains frequency (50 or 60 Hz). As the frequency is increased gradually, the motor can be assumed to operate at its rated speed for a given frequency value. Furthermore, on the assumption that the motor runs at its rated speed the nominal torque should be immediately available whereas the current will be approximately equal to the rated value. This starting system is used for speed control and regulation and can be used in the following cases:
- start with high-inertia load
- start with high load and limited-capacity power supply source
- optimization of electric power consumption depending on turbomachinery speed The aforementioned starting system can be used for all types of mechanisms.
Problems associated with DOL starting
The problems caused by DOL starting may be divided into two groups: 1. An
abrupt start causes mechanical shock, jolts in the mechanism, shock removal of
free play etc. 2. A heavy start cannot be completed.
Let us review three variations of a heavy start:
-
The feed line performance is barely sufficient or insufficient to maintain the induced current.
Typical symptoms: Upon starting the circuit breakers at the system input are tripped; the lights, certain relays and contactors go off, and the supply generator shuts down.
Solution: In the best-case scenario an SS device may help reduce the in-rush current to 250 % of the motor rated current. If this is insufficient, an FC is necessary. -
The motor cannot start the mechanism with DOL starting. Typical symptoms: The motor fails to turn or “freezes” at certain speed which is maintained until actuation of the protection suite. Solution: This problem may not be solved with an SS device. The motor develops insufficient shaft torque. However, this problem can be addressed by using an FC, but each case may be different.
-
The motor spins up the mechanism with authority, but fails to reach the rated rotation speed. Typical symptoms: The input automatic circuit breaker is tripped during spin-up. This often happens with heavy-weight fans with a considerable rotation speed. Solution: Such problems may be addressed with an SS device, but not with 100 % certainty. The closer the motor speed to the rated value during the actuation of the protective equipment, the higher the chances of success. The use of an FC in this case helps solve the problem fundamentally.
Standard switching equipment (automatic circuit breakers, contactors and motor starters) is not designed to withstand prolonged overloads normally causing the fan to shut down automatically DOL starting that continues for a long period of time. Using switching equipment with a higher maximum current rating renders the electric motor protection system less sensitive. As a result the switching equipment will not be able to detect motor overload in time due to a high current sensing threshold. Such problems as mentioned above can only be addressed by utilizing a soft starter or a frequency converter to start the fan.
COMMISSIONING
| THE ORGANISATION RESPONSIBLE FOR THE COMMISSIONING SHALL BE RESPONSIBLE FOR
PROPER MOTOR PHASING AND STARTING PATTERN SELECTION.
DURING STARTING THE IN-RUSH CURRENTS OF THE FAN MAY SEVERAL TIMES EXCEED THE
RATED VALUES.
---|---
| SEE “ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS” IN THE “CONNECTION TO
POWER MAINS” SECTION
---|---
- After fan starting make sure that the electric motor rotates properly without undue vibration and abnormal noise.
- Make sure that the fan impeller rotates in the direction marked by the arrow on the fan casing. If necessary, change the rotation direction of the impeller by reversing the phase sequence (for a three-phase motor) or by rewiring according to the wiring diagram located inside the terminal box (for a single-phase motor).
- Make sure that the fan energy consumption complies with the value given on the equipment nameplate and check the motor for overheating.
- The phase current should be checked once the fan reaches the rated operating conditions. · Do not switch the fan on and off several times without pauses as this may result in damage to the winding or insulation due to overheating.
TECHNICAL MAINTENANCE
| DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
---|---
| PRIOR TO COMMENCING ANY TECHNICAL MAINTENANCE PUT UP A PROHIBITORY SIGN ON
THE FAN STARTING PANEL:
“DO NOT SWITCH ON! MEN AT WORK!”
---|---
| AVOID LIQUID SPILLS ON THE MOTOR! DO NOT USE AGGRESSIVE SOLVENTS AND SHARP
OBJECTS FOR CLEANING!
---|---
The technical maintenance of the fan includes periodic cleaning of the
surfaces from dust and dirt and replacement of fan or motor parts. The fan
surfaces should be cleaned periodically as they get dirty. To clean the motor
impeller as well as the internal metal parts of the fan, use a soft dry brush
with a long handle and some cloth. For easy access to the motor impeller,
disconnect the louvre shutters.
While carrying out motor repair or replacement make sure to provide sufficient access to the motor location:
- undo three bolts on each of the two mounting brackets and remove the casing with the silencers
- disconnect the casing from the silencer 1 by unscrewing the clamping bolts
- remove the terminal box cover and disconnect the electric motor cable from the terminal block undo the screws on the casing which secure the motor mounts
- carefully remove the motor on the mounts from the casing · on completing the technical maintenance re-install the fan into the casing in the reverse order
While performing technical maintenance:
- Check the grounding screw terminals and electric connectors for proper tightness and tighten them up if necessary.
- Check the casing fastening screws for tightness and tighten them up if necessary.
- Check the bolt connecting the motor shaft to the hub for proper tightness and tighten it up if necessary.
- Check the fan impeller for clogging and clean when necessary. To clean the impeller, remove the side cover. Technical maintenance must be carried out at least once a year.
TROUBLESHOOTING
Problem | Possible reasons | Troubleshooting |
---|---|---|
The fan does not start. | No power supply. | Check the automatic circuit |
breaker. Check the electric connections.
Jammed motor.| Carefully check the fan impeller for possible seizure and
eliminate it, if necessary. If the impeller is in order, replace the electric
motor.
The automatic breaker activates upon fan start-up.| Short circuit in the fan
or the electric circuit between the fan and the automatic circuit breaker.|
Eliminate the cause of a short circuit.
Excessive current consumption due to an overload in the electric mains
triggers the thermal release of the automatic circuit breaker.| Eliminate the
cause of excessive current consumption.
Improper fan starting method.| Use a soft starter or frequency converter to
start the motor ( see “Asynchronous Electric Motor Starting Methods” in
the “Connection to power mains” section ).
Improper switching equipment.| Re-select the switching equipment in accordance
with the current regulations and equipment specifications.
The installed switching equipment is of poor quality or its actual performance
falls short of the rated values stated by the manufacturer.| Re-select the
switching equipment by choosing a unit which successfully passed commutation
and load tests and has a technical compliance certificate. The selection
should be limited to the top five foreign switching equipment manufacturers.
The fan fails to reach the required rotation speed due to serious overheating
of the fan motor.| Fan motor overloaded.| Eliminate the overloa.
Improper fan starting method.| Use a soft starter or frequency converter to
start the motor ( see “Asynchronous Electric Motor Starting Methods” in
the “Connection to power mains” section ).
The fan motor runs at overload capacity with current consumption in excess of
the rated value.| Wrong motor phasing. The impeller rotates in the opposite
direction of the arrow on the fan casing.| If necessary, change the impeller
rotation direction by changing the phase sequence on the electric motor
terminals.
The fan supplies more air than expected.| Wrong choice of the fan.| Replace
the fan with a unit of proper standard size.
The fan supplies less air than expected.| Wrong choice of the fan.| Re-
calculate the parameters and select the right fan.
Wrong direction of the impeller rotation direction.| If necessary, change the
impeller rotation direction by changing the phase sequence on the electric
motor terminals (see the “Commissioning” section).
Impeller contamination with foreign objects or debris.| Clean the impeller
from foreign objects or debris.
Increased noise, vibration in the fan.| Loose screw connections.| Check the
screw connections for proper tightness.
No vibration mounts on the fan.| Install the anti-vibration mounts.
Impeller contamination with foreign objects or debris.| Clean the impeller
from foreign objects or debris.
Worn bearings.| Replace the bearings.
Unstable power supply, unstable motor operation.| Check the stability of power
supply parameters and electric motor operation.
STORAGE AND TRANSPORTATION REGULATIONS
-
Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range +5 °C..+40 °C and relative humidity up to 70 %.
-
Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation. Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
-
Follow the handling requirements applicable for the particular type of cargo. · The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and
mechanical damage. The unit must be transported only in the working position. -
Avoid sharp blows, scratches, or rough handling during loading and unloading.
-
Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
| RISK OF UNIT DAMAGE. IF THE STORAGE DURATION IS LONGER THAN 3 MONTHS, IT IS
NECESSARY TO REGULARLY TURN THE IMPELLER BY HAND.
---|---
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above. The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual. · Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
The manufacturer shall not accept any claims with regards to the condition of the paint-and-lacquer coating (hereinafter PLC) in the following cases:
- Dents, cracks, scratches and abrasions of the PLC sustained during handling, mounting and assembly operations.
- Progress of corrosion on areas damaged with stones, sand, and roof coat tar during the performance of roofing work.
- Signs of direct exposure of the PLC to excessive temperatures, which occurred during the performance of roofing work.
- Violation of regulations on transportation, storage, installation, and operation of the unit.
- Presence of damage caused by exposure to industrial and chemical emissions, acidic or alkaline pollution, sap or other factors not related to normal operating conditions.
| FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT.
---|---
| USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL
WITH THE PURCHASE DATE STAMP.
---|---