VENTS CBF LP 200/250 Centrifugal ceiling fan
This user manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about the purpose, technical details, operating principle, design, and installation of the CBF LP unit and all its modifications. Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
SAFETY REQUIREMENTS
All user manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit. Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to 1000 V are allowed for installation and maintenance. The present user’s manual should be carefully read before beginning work.
- Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.
- While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and excessive noise.
- Misuse of the unit and any unauthorized modifications are not allowed.
- Do not expose the device to adverse atmospheric agents (rain, sun, etc.).
- Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.
- Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.
- Do not close or block the intake or extract vents in order to ensure efficient airflow.
- Do not sit on the unit and do not put objects on it.
- The information in this user’s manual was correct at the time of the document’s preparation.
- The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.
WARNING! Similar to the use of any other household electrical appliances when operating this fan, the following basic rules must be followed:
- Never touch the unit with wet or damp hands.
- Never touch the unit when barefoot.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance. The connection to the supply mains must be made through a means of disconnection, which is incorporated in the fixed wiring in accordance with the wiring rules and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions.
- If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a safety hazard.
- Ensure that the appliance is switched off from the supply mains before removing the guard.
- Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.
THE PRODUCT MUST BE DISPOSED OF SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT DISPOSE OF THE UNIT AS UNSORTED DOMESTIC WASTE.
PURPOSE
The centrifugal ceiling extract fan CBF LP is designed for extract ventilation of small to medium-sized premises. The unit is rated for continuous operation.
THE UNIT MUST NOT BE OPERATED ON KITCHEN PREMISES.
Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot, and oil particles, or environments favorable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).
DELIVERY SET
NAME | QUANTITY |
---|---|
Fan | 1 pc. |
LED lamp (for fans with the Light option) | 2 pcs. |
Cable gland | 1 pc. |
Mounting bracket | 1 pc. |
Fastening kit | 1 pc. |
User’s manual | 1 pc. |
Packing box | 1 pc. |
DESIGNATION KEY
TECHNICAL DATA
The unit is designed for indoor application at ambient temperatures from +1 °C up to +40 °C. The ingress protection rating against access to hazardous parts and water ingress is IP2X. The unit is rated as a class I electric appliance. The unit design is constantly being improved, so some models may be slightly different from those ones described in this manual
OVERALL AND CONNECTION DIMENSIONS OF THE FANS
Model | Dimensions [mm] |
---|---|
Ø d | L1 |
CBF LP 200/250
CBF LP 200/250 T/TH/TP
| 98| 100| 40.5| 330| 278| 255| 395| 134| 18
CBF LP 200/250 Light
CBF LP 200/250 Light T/TH/TP
| 98| 100| 40.5| 330| 278| 255| 395| 134| 57
Parameter
| CBF LP 200
CBF LP 200 T/TH/TP
CBF LP 200 Light
CBF LP 200 Light T/TH/TP
| CBF LP 250
CBF LP 250 T/TH/TP
CBF LP 250 Light
CBF LP 250 Light T/TH/TP
---|---|---
Frequency [Hz]| 50| 60| 50| 60
Speed| 1| 2| 1| 2| 1| 2| 1| 2
Voltage [V]| 1 ~ 220-240
Fan power [W]| 20| 29| 21| 34| 23| 39| 25| 50
Lamp power [W]*| 2 x 10
Fan current @ 230 V, A| 0.1| 0.13| 0.11| 0.15| 0.12| 0.18| 0.14| 0.22
Max air flow [m3/h]| 130| 210| 130| 225| 170| 260| 160| 270
Max air flow [l/s]| 36| 58| 36| 63| 47| 72| 44| 75
SFP [W/l/s]| 0.55| 0.50| 0.58| 0.54| 0.49| 0.54| 0.56| 0.67
Weight [kg]| 5.3(6.4)| 5.3(6.4)
IP| 2X
SEC class| D| C
- For fans with light only
DESIGN AND OPERATING PRINCIPLE
CBF LP 200/250 T/TH/TP
CBF LP 200/250 Light T/TH/TP
The fan casing is made of galvanized steel. The fan casing includes an exhaust spigot with a back draft damper to prevent back airflow. The terminal box comprises the terminals for wiring of the fan and is attached to the fan casing. The decorative grille is fixed to the casing via the springs inserted to the holders. The front panel is fixed via the grille slots. A single-phase electric motor with a centrifugal impeller with forwarding curved blades is fastened inside of the casing. Depending on the fan model the fan may be equipped with a LED lamp, a timer, a humidity or motion sensor.
Timer (t)
After an external switch, e.g. a light switch is turned off, the fan is turned
on or goes to high speed after a countdown of a set turn-on delay time,
adjustable from 0 to 3 minutes.
After the fan is turned off it keeps running for a set turn-off delay time,
adjustable from 1 to 90 minutes, and then reverts to the initial operation
status.
Motion sensor (tp)
In case of activation of the motion sensor the fan turns on or switches to a
higher speed.
After no motion is detected the fan keeps running for a set turn-off delay
time, adjustable from 1 to 90 minutes and then reverts to the initial
operation status.
Humidity sensor (th)
If the indoor humidity exceeds the set humidity point adjustable from 50 % up
to 90 %, the fan either turns on or goes to a higher speed. After indoor
humidity drops down the fan keeps running for a set turn-off delay time,
adjustable from 1 to 90 minutes, and then reverts to the initial operation
status.
MOUNTING AND SET-UP
READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.
- The fan is a component part and is not designed for stand-alone operation.
- The fan is constructed for ceiling installation in the floor slab and fixation to the interjoist with the distance between the ceiling joists from 270 up to 470 mm using the removable fixing brackets or the fastening holes in the fan casing.
- The installation place must be in compliance with local construction norms for units of this type.
- Check the fan for mechanical damages prior to mounting.
- Make sure that the casing comprises no foreign objects, such as paper or foil.
- While mounting the fan sufficient service access for maintenance or repair operations must be provided.
The minimum gap between the fan and the ceiling is 5 mm.
MOUNTING STEPS
-
Attach the fan to the interjoist using the screws.
Vertical attachment to the beams on the wall is permissible. -
Connect the air duct of the required diameter.
-
Connect the LED lamps (included in the delivery set) for the Light models.
Option: connect the humidity sensor or the motion sensor (specially ordered accessory).
For the Light models: connect the power socket of the LED lamp and the respective sockets in the terminal box. For the TH models with a humidity sensor: remove the protective cap from the grille prior to its installation. Route the contact socket of the sensor TH or TP via the opening in the grille and connect the sensor socket to the respective contact socket on the control unit.
Fix the sensor in the grille opening and cover the opening with a protective cap. -
Install the decorative grille on the fan casing using the holders on the casing.
CONNECTION TO POWER MAINS
- POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT. THE UNIT MUST BE CONNECTED TO THE POWER SUPPLY BY A QUALIFIED ELECTRICIAN. THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.
- ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
The fan is rated for connection to a single-phase AC 220-240 V 50/60 Hz power supply. The fan must be connected to power mains using durable, insulated, and heat-resistant conductors (cables and wires) via the circuit breaker QF integrated into the house cabling system. The external circuit breaker installation place must ensure unhampered access for emergency shutdown of the unit.
WIRING DIAGRAMS
ACCESS TO THE TERMINAL BOX FOR WIRING THE FAN
Remove the decorative grille
For accessing the connection terminals loosen the screw on the terminal box
lid and take the lid off.
Remove the protective cap and install the cable gland.
CONTROL
CONTROL UNIT WITH A SPEED SWITCH
The fan with AC motor is controlled by a three-position switch. The switch has three positions:
- OFF — the fan is turned off.
- LOW — the fan operates at the reduced performance (speed 1).
- HIGH — the fan operates at maximum performance (speed 2).
When the power is turned on (~ 230 V), the fan will operate in one of the above modes.
MICROPROCESSOR CONTROL UNIT WITH INDICATION
The AC fan motor is operated by a microprocessor control unit. The front panel
of the control unit comprises a light indicator, control buttons, and two
connectors for the connection of the humidity and motion sensors.
After the fan is connected to the power supply, the indicator displays for two seconds. After that, the light indicator goes off and the fan starts operating in set mode. Once the button F is pressed the indicator displays the turn-off delay timer setting , the first Setup menu entry. Use or buttons to navigate in the Setup menu. Press F , to select a current entry in the Setup menu. After that the indicator displays the selected parameter value (e.g., turn-off delay timer setting). Use or to change the value. Press F to come back to the Setup menu. If no button is pressed for 60 seconds, the indicator goes down.
Example
The indicator displays . Once the button is pressed, the Setup menu list goes
one position down and the symbol is displayed (refer to the Setup menu). Once
the button F is pressed, the indicator displays the turn-on delay timer
setting, which can be edited with the buttons and . Once the button F is
pressed again, the Setup menu is displayed again and the edited value is
saved.
To reset the menu to the factory settings press and hold the buttons F and synchronously. In 5 seconds the indicator displays , and goes off. The fan keeps running in normal mode with the factory settings.
INDICATOR SYMBOLS OF THE MICROPROCESSOR CONTROL UNIT
- turn-off delay timer adjustable from 1 to 90 minutes (default setting 15 minutes).
- turn-on delay timer adjustable from 0 to 180 seconds with an increment of 10 seconds (default setting 0).
- humidity set point adjustable from 50 % up to 90 % (default setting 75 %).
- access to the submenu of the fan operation mode.
Operation mode — the fan operates without any activation signal from the switch, humidity or motion sensor. Operation mode — the fan operates with an activation signal from the switch, humidity or motion sensor. — back to the upper setup menu level.
Once the switch is turned on or the humidity or motion sensor is activated, the fan switches from the mode to the mode . After a signal is no more received from the sensor in case of the indoor humidity normalization, or no more motion is detected in case of the fan shutdown, the fan keeps running for a set turn-off delay time and then switches from the mode to the mode .
SETUP OF THE OPERATION MODES AND
The and modes can take the following values for the fan with an AC motor:
- — the fan is turned off.
- — the fan operates at reduced performance.
- — the fan operates at maximum performance.
Example 1
— with these activated settings the fan is constantly turned off. Once the
switch is turned on or a sensor is activated, the fan starts to run at reduced
performance.
Example 2
— with these activated settings the fan runs at reduced performance. Once the
switch is turned on or a sensor is activated, the fan starts to run with the
maximum capacity. This setting is factory set and is the default setting.
TECHNICAL MAINTENANCE
DISCONNECT THE UNIT FROM THE POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
ENSURE THAT THE UNIT IS SWITCHED OFF FROM THE SUPPLY MAINS BEFORE REMOVING
THE GUARD.
The fan maintenance includes regular cleaning of the surfaces of dust and
dirt. Replace the filter as required, but at least every 6 months. The
impeller cleaning is shown below. Clean the impeller blades thoroughly every 6
months.
LAMP REPLACEMENT
DISCONNECT THE UNIT FROM THE POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
ENSURE THAT THE UNIT IS SWITCHED OFF FROM THE SUPPLY MAINS BEFORE REMOVING THE GUARD.
-
Remove the decorative grille:
- Pull the grille to release the springs from the holders on the casing.
- Take out the lamp power socket from the respective socket on the casing.
- Take out the power socket of the sensors from the respective sockets on the control unit (applicable for TH and TP models).
-
Take off the surface-mounted luminaire.
Press the holders on the reverse side of the grille frame and take off the surface-mounted luminaire. -
Replace the lamps.
-
Reassemble the unit in reverse order.
TROUBLES AND TROUBLESHOOTING
TROUBLE | POSSIBLE REASONS | TROUBLESHOOTING |
---|
The fan does not get started.
| ****
No power supply.
| Check the electric connections and the operation status of the circuit breaker.
Motor jam.
| Turn the fan off. Troubleshoot clogging of the impeller. Restart the fan.
Automatic circuit breaker tripping during the unit turning on.
| Overcurrent as a result of short circuit in the electric circuit leads to tripping of the circuit breaker.| ****
Disconnect the fan from power supply and contact the product Seller. Do not turn the fan on again!
Low air flow.
| Air ducts or other components of the ventilation system are clogged. The impeller is clogged. The air ducts are damaged. The air dampers are closed.| Clean the air ducts, the impeller and other components of the ventilation system. Make sure that the air ducts are not damaged. Make sure that the air dampers and louver shutters are open.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with a temperature range from +5 °C (+41 °F) to +40 °C (+104 °F) and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport providing proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3- 4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to the elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit components.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from a warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit are committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE- FREE OPERATION OF THE UNIT. USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP.
CERTIFICATE OF ACCEPTANCE
Unit Type | Centrifugal ceiling fan |
---|---|
Model | CBF LP __ |
Serial Number | |
Manufacture Date | |
**Quality Inspector’s Stamp** |
SELLER INFORMATION
Seller|
---|---
Address|
Phone Number|
E- mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s
manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|
INSTALLATION CERTIFICATE
The CBF LP __ unit is installed pursuant to the requirements stated in the present user’s manual.
Company name|
Address|
Phone Number|
Installation Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the
applicable local and national construction, electrical and technical codes and
standards. The unit operates normally as intended by the manufacturer.
Signature:|
WARRANTY CARD
Unit Type | Centrifugal ceiling fan |
---|---|
Model | CBF LP __ |
Serial Number | |
Manufacture Date | |
Purchase Date | |
Warranty Period | |
Seller |