Sonel CMP-1006 Digital Clamp-On Multimeter User Manual
- June 5, 2024
- Sonel
Table of Contents
**USER MANUAL
CMP-1006
AC/DC DIGITAL CLAMP METER
v1.8.1 07.04.2021
**
Introdution
We appreciate your having purchased our digital clamp meter. The CMP-1006
meter is a modern, high-quality measuring device, which is easy and safe to
use. Please acquaint yourself with the present manual in order to avoid
measuring errors and prevent possible problems related to the operation of the
tester.
In the present manual, we apply three kinds of warnings. These are texts in
frames, which describe possible dangers both for the user and the meter
itself. The messages start from the word
‘WARNING:’ describe situations that imply a risk for life or health
should the recommendations presented in the present manual not be observed.
The word ‘ATTENTION!’ introduces a description of a situation where non-
observance of the recommendations presented in the present manual may imply
damage to the meter. Indications of possible problems are preceded by the word
‘Attention:’.
WARNING:
Before using the instrument acquaint yourself with the present manual and
observe the safety regulations and recommendations specified by the
manufacturer.
WARNING: The purpose of the CMP-1006 meter is to realize clamp measurements of
AC/DC current and also to realize AC/DC voltage, resistance, frequency, and
temperature measurements. Using the meter in a manner that does not comply
with the recommendations specified in the present manual may lead to its
damage and constitutes a source of serious risk for the user.
WARNING: The CMP-1006 meter may be operated solely by qualified and properly
authorized personnel for work at electric installations. Using the tester by
unauthorized personnel may lead to its damage and constitutes a source of
serious risk for the user.
Safety
In order to guarantee proper operation and correctness of the obtained results it is necessary to observe the following recommendations:
- Before commencing the operation of the meter please acquaint yourself thoroughly with the present manual,
- The instrument should be operated solely by properly qualified personnel, who also must be trained regarding the industrial safety regulations,
- Use great care when making measurements if the voltages are greater than 20VAC rms or 40VDC. These voltages are considered a shock hazard,
- Always discharge capacitors and remove power from the device under test before performing Diode, Resistance, or Continuity tests,
- Before use for non-contact AC voltage measurements, always test the voltage detector on a known live circuit to verify proper operation,
- It is prohibited to operate the meter:
If it is damaged and completely or partially out of order,
If the insulation of the test leads has been damaged,
If it has been stored for an excessive period of time in inadequate conditions
(e.g. if it is humid),
- Set function switch to the appropriate position before measuring,
- When measuring volts do not switch to current/resistance modes,
- Do not measure current on a circuit whose voltage exceeds 600V,
- When changing ranges always disconnect the test leads from the circuit under test,
- If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired,
- Repairs must be realized solely by an authorized service workshop.
ATTENTION!
Input Limits
Function| Maximum Input
A DC, A AC| 1000A DC/AC
V DC, V AC| 600V DC/AC
Resistance, Frequency, Diode Test| 250V DC/AC
Temperature (°C/°F)| 60V DC, 24V AC
WARNING:
Do not realise measurements with wet hands.
WARNING:
Do not realise measurements in environments in which there are
inflammable gases. Otherwise operation of the meter under such conditions
may cause sparking and explosion.
ATTENTION!
Do not exceed the maximum allowable input range of any function. Do not apply
voltage to meter when resistance function is selected. Set the function switch
OFF when the meter is not in use. Remove the battery if a meter is to be
stored for longer than 60 days.
2.1 International Safety Symbols
This symbol, adjacent to another symbol or terminal, indicates the user must
refer to the manual for further information.
This symbol, adjacent to a terminal, indicates that, under normal use,
hazardous voltages may be present
Double insulation
Preparation of the meter for operation
Before measurements commence, it is necessary to realise the following actions:
- Make sure the conditions of the batteries or accumulators permit to realise measurements,
- Make sure the casing of the meter and the insulation of the test leads are not damaged,
- Insert the black test lead into the negative COM terminal and the red test lead into the V·Ω°· C· °F·Hz positive terminal.
WARNING:
Connection of inappropriate or damaged test leads constitutes a risk of an
electric shock with a dangerous voltage.
Functional description
4.1 Measurement sockets and elements of selection of the measurement function
-
Current clamp
-
Clamp opening trigger
-
Control buttons:
a. Backlight
b. Inrush / Mode
c. Maks. / Min.
d. Data Hold
e. Hz / % / DC Zero -
Backlit LCD Display
-
COM negative input jack for black test lead
-
Rotary function switch
-
V·∧ ·°C·°F·Hz positive input jack for red lead
4.2 LCD display
HOLD | Data Hold |
---|---|
Minus sign | Negative reading display |
0 do 6600 | Measurement display digits |
DC ZERO | DCA Zero |
MAKS/MIN | Maximum/Minimum |
INRUSH | Inrush Current |
AUTO | Auto Range mode |
DC/AC | Direct Current / Alternating Current |
Direct Current / Alternating Current | |
mV or V | Milli-volts or Volts (Voltage) |
Ω | Ohms (Resistance) CMP-1006 – USER MANUAL |
--- | --- |
A | Amperes (Current) |
--- | --- |
F | Farad (Capacitance) |
Hz | Hertz (Frequency) |
°F i °C | Fahrenheit and Celsius units (Temperature) |
n, m, μ, M, k | Unit of measure prefixes: nano, milli, micro, mega, and kilo |
·))) | Continuity test |
Diode test |
4.3 Test leads
The manufacturer guarantees correct measurement indications provided original test leads are used.
WARNING:
Connection of inadequate test leads constitutes a risk of electric shock with
a dangerous voltage or may be a cause of measurement errors.
Measurements
It is recommended to get acquainted thoroughly with the contents of the present chapter since it describes the measurement systems, the manner of realization of measurements, and the basic principles of interpretation of the results. Set the function select switch to the OFF position when the meter is not in use.
5.1 AC/DC current measurements
WARNING:
Do not measure current on a circuit whose voltage exceeds 600V AC. Do not take
current readings on circuits where the maximum current potential is not known.
Do not exceed the maximum allowable input range while measuring current.
WARNING:
Do not realize measurements if the battery compartment is open.
WARNING:
Do not commence measurements if the test leads are connected to the
meter.
In order to realize a measurement of current, it is necessary to realize the
following actions:
- Set the Function switch to the 1000A or 660A range. If the approx. range of the measurement is not known, select the highest range then move to the lower ranges if necessary,
- Press the DC ZERO button to zero the meter display,
- Press the trigger to open the jaw. Fully enclose only one wire. For optimum results, center the wire in the jaw,
- Read the result of the measurement on the display.
Attention:
During measurements of the current make sure the clamp is properly
placed. Otherwise, the results of the measurements will not be exact. The
most exact result we will get if the wire is placed in the middle of a
clamp.
5.2 AC and DC voltage measurements
WARNING:
Do not realize measurements if the battery compartment is open.
In order to realize a measurement of AC or DC voltage, it is necessary to realize the following actions:
- Insert the black test lead into the negative COM terminal and the red test lead into the positive V·∧ ·°C·°F·Hz terminal,
- Set the function switch to the V Hz position,
- Use the MODE button to select AC or DC Voltage,
- Connect the test leads in parallel to the circuit under test,
- Read the voltage measurement on the LCD display.
5.3 Resistance measurements
WARNING:
Measurements must not be realized in live circuits. Capacitors must be
discharged.
WARNING:
Do not realize measurements if the battery compartment is open.
In order to realize a measurement of the resistance, it is necessary to realize the following actions:
- Insert the black test lead into the negative COM terminal and the red test lead into the V·∧ ·°C·°F·Hz positive terminal,
- Set the function switch to the ∧))) position,
- Touch the test probe tips across the circuit or component under test; it is best to disconnect one side of the device under test so the rest of the circuit will not interfere with the resistance reading,
- Read the resistance on the LCD display.
5.4 Frequency or % duty cycle measurements
In order to realize frequency or % duty cycle measurement it is necessary to realize the following actions:
- Insert the black test lead banana plug into the negative COM jack and the red test lead banana plug into the V·∧ ·°C·°F·Hz positive jack,
- Set the function switch to the V Hz position,
- Press the Hz/% button to select the Frequency (Hz) or Duty cycle (%)function,
- Touch the test probe tips across the circuit under test,
- Read the Frequency value on the display,
- Duty cycle measurement: When the duty cycle is less than 10.0%, the LCD panel shows UL. When the duty cycle is more than 94.9%, the LCD panel shows OL,
- The display will indicate the proper decimal point and value,
- Press the HZ/% button again to return to the voltage mode.
5.5 Temperature measurements
In order to realize temperature measurement it is necessary to realize the
following actions:
- Set the function switch to the Temp position,
- Insert the Temperature Probe into the negative COM and the V·∧ ·°C·°F·Hz positive jacks, observing polarity,
- Touch the Temperature Probe head to the device under test. Continue to touch the part under test with the probe until the reading stabilizes,
- Read the temperature on the display. The digital reading will indicate the proper decimal point and value,
- Use the MODE button to select o F or o C.
WARNING:
To avoid electric shock, be sure the thermocouple has been removed
before changing to another measurement function.
5.6 Continuity Measurements
WARNING:
Measurements must not be realized in live circuits. Capacitors must be
discharged.
WARNING:
Do not realize measurements if the battery compartment is open.
In order to realize the continuity test it is necessary to realize the following actions:
- Insert the black test lead into the negative COM terminal and the red test lead into the V·∧ ·°C·°F·Hz positive terminal,
- Set the function switch to the ∧ ))) position,
- Use the MODE button to select continuity “ ∧ )))”. The display icons will change when the MODE button is pressed,
- Touch the test probe tips across the circuit or component under test,
- If the resistance is < 40 ∧ , a tone will sound.
5.7 Diode Measurements
In order to realise diode test it is necessary to realise the following actions:
- Insert the black test lead banana plug into the negative COM jack and the red test lead banana plug into the V· ∧ ·°C·°F·Hz positive jack,
- Turn the function switch to ∧ ))) position. Use the MODE button to select the diode function if necessary (diode symbol will appear on the LCD when in Diode test mode),
- Touch the test probe tips to the diode or semiconductor junction under test. Note the meter reading,
- Reverse the test lead polarity by reversing the red and black leads. Note this reading,
- The diode or junction can be evaluated as follows:
If one reading displays a value (typically 0.400V to 0.900V) and the other
reading displays OL, the diode is good;
If both readings display OL the device is open;
If both readings are very small or ‘0’, the device is shorted.
5.8 DATA HOLD Function
To freeze the LCD reading, press the HOLD button. While the data hold is
active, the HOLD icon appears on the LCD. Press the HOLD button again to
return to normal operation.
5.9 DC ZERO
The DC ZERO is a relative feature and can be used in the measurement of DC
current.
- Press the DC ZERO button to zero the display. “ZERO” will appear on the display. The displayed reading is now the actual value less the stored “zero” value;
- To exit this mode, press and Hold the ZERO button until “ZERO” is no longer on the display.
5.10 Inrush Function
The Inrush current function for AC current measurement to de- gets the
starting-up current of a motor. In ACA modes, pressing the INRUSH button will
force the meter to enter INRUSH mode. Then LCD Displays ”- – – -” until the
motor starts up and is detected. The detection will be done only one time and
the output reading will be held. To exit INRUSH mode, press INRUSH button for
more than one second.
5.11 LCD Backlight Button
The LCD is equipped with backlighting for easier viewing, especially in dimly
lit areas. Press the backlight button to turn the backlight on. Press again to
turn the backlight off. Note that the meter does have an auto power-off
feature as described below.
5.12 Automatic Power OFF
In order to conserve battery life, the meter will automatically turn off after
approximately 25 minutes. To turn the meter on again, turn the function switch
to the OFF position and then to the desired function position.
Battery replacement
The CMP-1006 meter is supplied by means of one 9V battery. It is recommended to use an alkaline battery.
Attention:
When making measurements with a battery’s mnemonic on, one must take into
account additional indefinite measurement uncertainty or unstable working of
the meter.
WARNING:
Should the test leads be left in the sockets during the replacement of the
battery, there might be a risk of electric shock with a dangerous voltage.
In order to replace the battery it is necessary to do the following:
- Remove the Phillips head screw that secures the rear battery door,
- Open the battery compartment,
- Replace the 9V battery,
- Secure the battery compartment.
Cleaning and maintenance
The casing of the meter may be cleaned with a soft, damp cloth using all- purpose detergents. Do not use any solvents or cleaning agents which might scratch the casing (powders, pastes, etc.). The electronic system of the meter does not require maintenance.
Storage
In the case of storage of the device, the following recommendations must be observed:
- Disconnect all the test leads from the meter,
- Make sure the meter and its accessories are dry,
- In the case, the meter is to be stored for a prolonged period of time, the battery must be removed from the device.
Dismantling and utilization
Worn-out electric and electronic equipment should be gathered selectively, i.e. it must not be placed with the waste of another kind. Worn-out electronic equipment should be sent to a collection point in accordance with the law of worn-out electric and electronic equipment. Before the equipment is sent to a collection point, do not dismantle any elements. Observe the local regulations concerning the disposal of packages, worn-out batteries, and accumulators.
Technical data
„m.v.” means the measured value of standard
AC current measurement TRMS
Range | Resolution | Basic uncertainty |
---|---|---|
660.0A | 0.1A | ± (2.5% m.v. + 8 digits) |
1000A | 1A | ± (2.8% m.v. + 8 digits) |
- frequency range 45…65Hz
DC current measurement
Range | Resolution | Basic uncertainty |
---|---|---|
660.0A | 0.1A | ± (2.5% m.v. + 5 digits) |
1000A | 1A | ± (2.8% m.v. + 8 digits) |
AC voltage measurement TRMS
Range | Resolution | Basic uncertainty |
---|---|---|
6.600V | 0.001V | **** |
± (1.8% m.v. + 5 digits)
66.00V| 0.01V
600.0V| 0.1V
- frequency range 45…65Hz
DC voltage measurement
Range | Resolution | Basic uncertainty |
---|---|---|
6.600V | 0.001V | **** |
± (1.5% m.v. + 3 digits)
66.00V| 0.01V
600.0V| 0.1V
Resistance measurement
Range | Resolution | Basic uncertainty |
---|---|---|
660.0Ω | 0.1Ω | ± (1 % m.v. + 4 digits) |
6.600kΩ | 0.001kΩ | **** |
± (1.5 % m.v. + 2 digits)
66.00kΩ| 0.01kΩ
660.0kΩ| 0.1kΩ
6.600MΩ| 0.001MΩ| ± (2.5 % m.v. + 3 digits)
66.0MΩ| 0.1MΩ| ± (3.5 % m.v. + 5 digits)
Frequency measurement
Range | Resolution | Basic uncertainty |
---|---|---|
30.0…659.9Hz | 0.1Hz | **** |
± (1.2 % m.v. + 2 digits)
0.660…6.599kHz| 0.001kHz
6.60…15.00kHz| 0.01kHz
- sensitivity: 30…5kHz:10Vrms min., 5kHz…15kHz: 40Vrms min. @ 20% to 80% duty cycle
Duty Cycle
Range | Resolution | Basic uncertainty |
---|---|---|
10.0…94.9% | 0.1% | unspecified |
- Pulse width: 100µs…100ms
- Frequency: 30Hz…15kHz
- Sensitivity: 30…5kHz: 10Vrms, 5kHz…15kHz: 40Vrms
Temperature
Range | Resolution | Basic uncertainty* |
---|---|---|
-20…760°C | 1°C | ± (3% w.m. + 5°C) |
-4…1400°F | 1°F | ± (3% w.m. + 9°F) |
- probe accuracy not included
Other technical data
a) Measurement category according to EN 61010-1 …………. III 600V
b) Clamp jaw opening …………………….34mm (1.34″) approximately
c) Internal diameters of clamp ……………. 36x52mm (1,42×2,05”)
d) Display ………………………………… 6600 counts backlit LCD
e) Continuity check …………………. threshold 40Ω; Test current < 0.5mA
f) Diode test……………………………. test current of 0.3mA typical;
………………………………. open circuit voltage < 3VDC typical
g) Low Battery indication …………………………….. BAT’ is displayed
h) Over-range indication ………………….. OL’ is displayed
i) Measurement rate ………………… 2 readings per second, nominal
j) Inrush ……………………….. integration time 100ms, sampling 10ms
k) Temperature sensor ……………………… type K thermocouple
l) Input Impedance ………………………………. 10MΩ (VDC and VAC)
m) AC bandwidth …………………………. 50 to 400Hz (AAC and VAC)
n) Operating temperature ……….. 5°C to 40°C (41°F to 104°F)
o) Storage temperature………………. 20°C to 60°C (-4°F to 140°F)
p) Operating humidity …………………….max 80% up to 31°C F (87°)
………….decreasing linearly to 50% at 40 °C (104 °F)
q) Storage humidity …………………………. <80%
r) Operating altitude ……….. 2000m (7000ft) maximum
s) Battery ……………………………….. one 9V battery
t) Auto power OFF ………………………. after approximately 25 minutes
u) Dimensions ……………… 229 x 80 x 49mm (9.0 x 3.1 x 2.0″)
v) Weight …………….303g
Attention:
For indoor use and in accordance with the requirements for double
insulation to IEC1010-1 (1995): EN61010-1 (1995) Overvoltage Category III
600V, Pollution Degree 2.
Standard accessories
The standard set provided by the manufacturer includes the following components:
- The CMP-1006 meter,
- Test leads for clamp- and multimeters (set) – WAPRZCMP1,
- 9V battery,
- Type K temperature probe – WASONTEMK,
- Temperature probe type K adapter – WAADATEMK,
- Carrying case
- User manual,
- Guarantee card,
- Calibration certificate.
The current list of accessories can be found on the manufacturer’s website.
Service
The manufacturer of the device, which also provides guarantee and post- guarantee service is the following company:
SONEL S.A.
Wokulskiego 11
58-100 Świdnica
Tel: + 48 74 858 38 60
Fax: +48 74 858 38 09
E-mail: export@sonel.pl
Web page: www.sonel.pl
Note:
Service repairs must be realized solely by the manufacturer.
Laboratory services
SONEL Testing and Calibration Laboratory has been accredited by the Polish Center for Accreditation (PCA) – certificate no. AP 173.
Laboratory offers calibration for the following instruments that are used for measuring electrical and non-electrical parameters.
-
METERS FOR MEASUREMENTS OF ELECTRICAL PARAMETERS
o voltage meters,
o current meters (including clamp meters),
o resistance meters,
o insulation resistance meters,
o earth resistance and resistivity meters,
o RCD meters,
o short-circuit loop impedance meters,
o power quality analyzers,
o portable appliance testers (PAT),
o power meters,
o multimeters,
o multifunction meters covering the functions of the abovementioned instruments, -
ELECTRICAL STANDARD S
o calibrators,
o resistance standards, -
METERS FOR MEASUREMENTS OF NON-ELECTRICAL PARAMETERS
o pyrometers,
o thermal imagers,
o luxmeters.
The Calibration Certificate is a document that presents a relation between the
calibration standard of known accuracy and meter indications with associated
measurement uncertainties. The calibration standards are normally traceable to
the national standard held by the National Metrological Institute.
According to ILAC-G24 „Guidelines for determination of calibration intervals
of measuring instruments”, SONEL S.A. recommends periodical metrological
inspection of the instruments it manufactures no less frequently than once
every 12 months.
For new instruments provided with the Calibration Certificate or Validation
Certificate at the factory, re-calibration should be performed within 12
months from the date of purchase, however, no later than 24 months from the
date of purchase.
ATTENTION!
The person performing the measurements should be absolutely sure about the
efficiency of the device being used. Measurements made with an inefficient
meter can contribute to an incorrect assessment of the effectiveness of health
protection and even human life.
NOTES
SONEL S.A.
Wokulskiego 11
58-100 Swidnica
Poland
PL
+48 74 858 38 00 (Biuro Obstugi Klienta)
e-mail: bok@sonel.pl
GB • ES • RU +48 +48
74 858 38 60 74 858 38 00
fax: +48 74 858 38 09
e-mail: export@sonel.pl
www.sonel.pl
CMP-1006
Documents / Resources
|
Sonel CMP-1006 Digital Clamp-On
Multimeter
[pdf] User Manual
CMP-1006, Digital Clamp-On Multimeter
---|---
References
- 📧bok@sonel.pl
- 📧export@sonel.pl
- Offer to sell domain: somel.pl
- Sonel S.A.
- Sonel S.A.
- Standard (metrology) - Wikipedia
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>