Sonel DB-1 Demonstration Board User Manual
- May 15, 2024
- Sonel
Table of Contents
Sonel DB-1 Demonstration Board
Safety
The DB-1 demonstration board has been designed for the purpose of simulation of measurements, whose results determine the safety conditions of a virtual installation. Therefore, in order to guarantee appropriate operation and correctness of the obtained results, the following recommendations must be followed:
-
Before you proceed to operate the device read thoroughly the present manual and observe the safety regulations and instructions specified by the manufacturer.
-
The device has been designed for operation at the nominal voltage of 230 V 50 Hz.
-
The device cannot be used in the grid and with other devices in special interiors, for example those of a dangerous atmosphere regarding the risk of explosion or fire.
-
It is unacceptable to operate the following:
a damaged device which is completely or partially out of order
a device with damaged power cable insulation,
a device stored for an excessive period of time in disadvantageous conditions (e.g. excessive humidity). If the meter has been transferred from a cool to a warm environment of a high level of relative humidity, do not perform the measurements until the meter has been warmed up to the ambient temperature (approximately 30 minutes).
a device with damaged housing.
Before measurement of connection resistance or insulation resistance, make sure the measured object has been disconnected from the power supply. Disconnect the power cable of the device from the power supply contact and turn the RCD off. -
Repairs may be performed solely by an authorised service point. Before the device is connected to the power supply network, make sure the power supply socket is equipped with a properly connected earth pin. The board will not function if it is powered from a socket without an additional PE connection.
-
The board is equipped with a protection constituted by two F 4A 250 V fuses (T 3,14A 250 V fuse are acceptable). The fuses are located in the device power supply socket. Should the fuse elements be damaged, they must be replaced.
-
It is unacceptable to use other fuses.
WARNING
- The DB-1 demonstration board may be used solely by qualified personnel who have appropriate certificates that entitle them to work on electric installations, or by persons working under their supervision. Using the board by unauthorised personnel or without supervision of such personnel may cause damage of the device and be a source of a serious danger for the user.
- Before the fuses are replaced, the device must be disconnected from the 230 V power supply network.
NOTE!
- Before you proceed to operate the device, read thoroughly the present manual and observe the safety regulations and instructions specified by the manufacturer.
- The demonstration board has been designed for the purpose of simulation measurements of alternating voltage, impedance, short circuit, earth resistance, parameters of the RCD switch, ground resistivity, insulation resistance, resistance of equipotential bondings. Any application that differs from those specified in the present manual may cause damage of the device and be a source of a serious danger for the user.
- Before and during measurements of ground resistivity, insulation resistance, resistance of equipotential bondings, earth resistance (by means of the technical methods) disconnect the power cable of the device from the power supply socket and turn the RCD switch off. The power supply of the board is signalled by the „POWER ON” diode.
Application
The DB-1 demonstration board is an indispensable element of training courses regarding realisation of electric measurements. It may be applied in schools, distribution centres of meters used in the power industry as well as in training centres.
The board may be used for the purpose of simulation of the following measurements:
- measurement of the short circuit loop impedance in the L-N circuit for the TT and TN networks,
- measurement of the short circuit loop impedance in the L-PE circuit for the TT and TN networks,
- measurement of the parameters of the RCD switch type AC,
- insulation resistance measurement in the L-N circuit,
- insulation resistance measurement in the L-PE circuit,
- measurement of the earth resistance by means of the technical method,
- earth resistance measurement using clamps,
- earth resistance measurement by means of the two-clamp method,
- earth resistance measurements by means of the impulse method,
- earth resistance measurements using meters for short-circuit loop measurements,
- resistivity measurements of three kinds of ground,
- measurement of the resistance of equipotential bondings,
- measurement of alternating voltage.
The demonstration board makes it possible to cause irregularities in the installation under scrutiny. This is possible thanks to the panel switches.
The Front Panel
Arrangement of sockets and switches
Fig. 1. Arrangements of the panel elements of the DB-1 demonstration board
- Power supply network socket 230 V
- Additional PE socket
- 230 V power supply signalling diode
- RCD switch
- Measurement socket
- TN network jumper
- TT network jumper
- RE1 (ZW RE1) earth electrode jumper
- Equipotential pipe connection jumper H2O (ZW H2O)
- RE2 (ZW RE2) earth electrode jumper
- Measurement points P1, P2, P3, P4, P5
- Measurement point of the RE1 (E1) earth electrode
- Measurement point of the RE2 (E2) earth electrode
- Measurement electrode sockets
- Irregularity selection switches
- Ground type switch for ground resistivity measurements
Position of switches
Fig. 2. Position of switches simulating irregularities in the electric installation of the measured object
- RE – high earth resistance at P2. RE = 1 kΩ
- UB – the acceptable voltage value UB has been exceeded during measurements of the RCD parameters in the measurement socket. UB > 25 V
- RISO(L-PE) – low insulation resistance – measurement L-PE. RISO(L-PE) = 200 kΩ
- RISO(L-N) – low insulation resistance – measurement L-N. RISO(L-N) = 100 kΩ
- RCD-TA – the acceptable disconnection time of the RCD has been exceeded.
- ZL – high short circuit loop impedance. ZL ≈ 6 Ω
- RCD-IA – the activation current of the RCD is lower than the required value (damaged RCD or excessive leakage current of the installation). The leakage current of the installation IA ≈ 15 mA
Measurements
Measurement of the short circuit loop impedance
A reliable and the most commonly used method of protection from electric shock
consists in protection from indirect touch in circuits equipped with circuit
breakers. The method consists in a automatic disconnection in the case of
fault.
Conductive elements of the device are connected to the protective conductor of
the power supply network. At the moment a hazardous touch voltage appears,
which is caused by a metallic short circuit with the phase conductor of the
power supply network, the current will flow in the phase – protective
conductor circuit. The current is called short-circuit current. The passage of
the short circuit current will cause activation of the circuit breakers and
the power supply system will be turned off.
The condition that must be met to have the protection level specified for the
device as sufficient approved is that the elements must not be under a
dangerous touch voltage for an excessive period of time. Therefore the safety
device must respond quickly, and within the period of time specified in the
relevant norms. The condition of appropriate protection may be expressed by
the following equation:
ZS – short circuit loop impedance
IA – current activating the circuit breaker within the required period of time
UO – power supply network nominal voltage in relation to earth
Measurement of the short circuit loop impedance in the L-PE circuit
Measurement of the short circuit loop impedance in the L-PE circuit may be performed using the MPI-5XX meter in the ZL-PE[RCD] function. Should another meter or function be used, the RCD switch of the demonstration board may be trigged.
In order to perform the measurement proceed as follows:
- connect the 230 V AC power supply network cable to the socket of the demonstration board,
- select the kind of TT or TN network using a jumper in the appropriate position (Figure 3),
- all the switches simulating irregularities must be in the „green” position,
- turn the RCD switch on,
- connect the meter to the power network socket of the board using leads, in accordance with Figure 4,
- perform the measurement
The demonstration board permits to perform measurements of a short circuit loop, whose value may be artificially overstated (simulation of irregularities). In order to do so, before you proceed to perform the measurement place the ZL switch in the „red” position. Having finished the measurement, place the ZL switch again in the „green” position.
Fig. 3. Network type selection jumpers.
- jumper simulating measurements in the TN network,
- jumper placed simulating measurements in the TT network
Fig. 4. Connection of the meter
Expected results
- Switch ZL „green” for the TN network (TN jumper): ZL-PE = ZL-N of the network + 1.4 Ω
- Switch ZL „red” for the TN network (TN jumper): ZL-PE = ZL-N of the network + 5.5 Ω
- Switch ZL „green” for the TT network (TT jumper): ZL-PE = ZL-N of the network + 5.5 Ω
- Switch ZL „red” for the TT network (TT jumper): ZL-PE = ZL-N of the network + 10 Ω
ZL-N of the network – the network impedance in the L-N circuit of the socket to which the demonstration board cable is connected.
Measurement of the short circuit loop impedance in the L-N circuit
Measurements may be performed with any meter for measurements of the short
circuit loop whose short circuit current does not exceed 25 A, and whose
measurement time does not exceed 60 ms, e.g. MZC-30X, MZC-20X, MPI-5XX.
In order to perform the measurement proceed as follows:
- connect the 230 V AC power supply network cable to the socket of the demonstration board,
- select the kind of network, TT or TN, using the jumper in the appropriate position (Fig. 3),
- all the switches simulating irregularities must be in the „green” position,
- turn the RCD switch on,
- connect the meter to the power network socket of the board using leads, in accordance with Figure 4,
- perform the measurement
The demonstration board permits to perform measurements of a short circuit loop, whose value may be artificially overstated (simulation of irregularities). In order to do so, before you proceed to perform the measurement place the ZL switch in the „red” position. Having finished the measurement, place the ZL switch again in the „green” position.
Fig. 5. Connection of the meter
Expected results
- Switch ZL „green” for the TN network (TN jumper): ZL-N = ZL-N of the network + 1.1 Ω
- Switch ZL „red” for the TN network (TN jumper): ZL-N = ZL-N of the network + 5.5 Ω
- Switch ZL „green” for the TT network (TT jumper): ZL-N = ZL-N of the network + 1.1 Ω
- Switch ZL „red” for the TT network (TT jumper): ZL-N = ZL-N of the network + 5.5 Ω
ZL-N of the network – the network impedance in the L-N circuit of the socket to which the demonstration board cable is connected.
Measurement of the parameters of the RCD switch
The principal function of the RCD switch (Residual Current Device) is to
provide additional protection against electric shock. The purpose the RCD
switch is to disconnect the protected circuit in the case of an excessive
leakage current in the circuit in question.
The measurement section of the RCD switch measures constantly the differential
current IΔ and causes disconnection of the protected circuit from the power
supply source, if the differential current exceeds the characteristic value
for the given switch. The value in question is the nominal differential
current, which is indicated by the symbol IΔn. The voltage on the housing of
the protected device, in accordance with the Ohm’s law, is:
UB = IΔ • RE
here RE is the resistance between the earth terminal of the protected device and the earth.
Realisation of measurements of the RCD switch parameters
In order to perform the measurement proceed as follows:
- connect the 230 V AC power supply network cable to the socket of the demonstration board,
- select the kind of network, TT or TN, using the jumper in the appropriate position (Figure 3),
- all the switches simulating irregularities must be in the „green” position,
- turn the RCD switch on,
- connect the meter to the power network socket of the board using leads, in accordance with Figure 6,
- perform the measurement.
The demonstration board permits to simulate irregularities in an installation equipped with a RCD switch:
- The RCD switch-TA in the in the „red” position simulates an error consisting in shunting of the N PE lead with the RCD switch. During a measurement with this error, the RCD switch will not function, and the meter will display an adequate message, e.g. RCD.
- The RCD switch-IA in the „red” position causes an additional current leakage in the PE lead. During a measurement with this error the RCD switch will be activated at an incorrect moment (the TA and IA measurements will not be possible). The meter will display an adequate message, e.g. Err.
- Switch UB in the „red” position simulates a hazardous touch voltage during a measurement of the RCD parameters. Meter will display an adequate message, e.g. UB > 25 V. If the meter is supposed to block the measurements and display this message, the acceptable touch voltage UL set for the meter must not exceed 25 V. Should the acceptable touch voltage UL during measurement be set at 50V, the meter will perform the measurements and display the results.
Fig. 6. Connection of the meter
Expected results
- Switches „green” RCD-TA, RCD-IA and UB for the TN and TT network: IA = 15…. 30 mA, TA < 300 ms, UB ≈ 0.2 V, RE ≈ 0.00 kΩ
- The RCD switch-TA „red” for the TN and TT network: message „RCD”
- The RCD switch-IA „red” for the TN and TT network: IA < 15 mA , or the message „Err”, „RCD activated during the measurement”
- Switch UB „red” for the TN and TT network : IA = 15…. 30 mA, TA < 300 ms, UB ≈ 31 V, RE ≈ 1 kΩ or „excessive UL voltage”
Measurements of the earth resistance
The quality of the earth systems significantly influence the safety of
operation of electric installations and devices, and particularly the
reliability of the protection from electric shock and lightning protection.
Earth systems have also other functions related to safety, namely they are
used to carry off electric charge where there is a risk of explosion (e.g. at
petrol stations). In order to revise electric installations and fulfil the
requirements related to the protection from electric shock, it is necessary to
perform the measurements of earth resistance. The resistance in question
permits to determine the value of touch voltage, which may be generated
between different conductive elements of the protective lead. In the case of
measurements of a single earth system, the most common method is the 3-pole
potential drop method. It consists in driving measurement electrodes into the
ground near the earth system under test and forcing the passage of current in
the following circuit: meter-the earth system in question-current electrode-
meter.
Measurements of multiple earth systems may be performed using the
aforementioned method, disconnecting subsequent earth electrodes during the
measurement. Since it is an arduous task, the meters which are equipped with
clamps may perform the measurement without the necessity to disconnect the
measured earth system. In the case of this method the current and voltage
electrodes are placed in a similar manner to the 3-pole method, but the
current is measured with clamps which are fastened to the earth system under
test. The meter calculates the resistance „knowing” the current flowing
through the tested earth electrode, and ignoring the current flowing through
the adjacent earth electrodes. However the measurement method with clamps
cannot be applied in those multiple systems in which individual earth
electrodes are interconnected below the ground.
Measurements of multiple earth systems may be performed by means of the two-
clamp method.
This measurement is performed with two pairs of clamps – apart from the
measurement clamps also transmission clamps must be used (whose internal
structure is different). The transmission clamps induce current in the tested
circuit. The value of the current is measured with measurement clamps.
The result of the measurement is the resistance of the whole circuit through
which the measurement current is flowing. Using this method, remember of the
requirements: this function is excellent for the purpose of measurements of
multiple earth systems of low and medium resistance values. In order to obtain
a correct measurement the resistance of the earth electrode must be
significantly higher than the resultant resistance value for the whole earth
electrode system (the two-clamp measurement measures the sum of the resistance
of the tested earthing resistance and the resultant value of the other earth
resistances). The principal and considerable advantage of this measurement is
the fact that there is no necessity to drive auxiliary electrodes into the
ground.
There is also another method of an earth resistance measurements. This is the
measurement of the surge earth resistance. The purpose of this measurement is
to diagnose the dynamic parameters of lightning protection earth system. The
surge measurement is performed at an excitation whose shape corresponds to a
lightning pulse. The parameters of the pulse are defined by two values: the
duration of the pulse leading edge t1 and the duration of the semi-peak t2 .
The DB-1 demonstration board permits to perform measurements of the earth
resistance of three distinct earth electrodes, namely RE, RE1, RE2. Earth
resistance measurement RE2 is also possible using the clamp method. In order
to perform such a measurement, instead of a jumper at the E2, it is necessary
to use an auxiliary lead, which is included in the board delivery package and
fasten the clamps on the lead. In order to perform the measurements it is also
possible to use the meters of the MRU-10X and MRU-20X series. It is also
allowed to use meters dedicated to measurements of the short circuit loop.
However, using such a meter may activate the RCD switch.
Measurement of the earth electrode resistance using meters of the MRU series
a. Earth resistance measurement RE
In order to perform the RE earth resistance measurement proceed as follows:
- disconnect the 230 V AC power supply network cable from the socket of the demonstration board,
- remove the TN or TT jumper, the ZW H2O jumper, the earth electrode RE1: ZW RE1 jumper
- a jumper may be fastened on the RE2 earth electrode,
- connect the earth resistance meter (MRU-XXX) to the sockets in accordance with Figure 7,
- perform the measurement.
Expected results
- RE = 100 Ω
- RH = 200 Ω
- RS = 200 Ω
Fig. 7. Connection of the meter
b. Earth resistance measurement RE1
In order to perform the RE1 earth resistance measurement proceed as follows:
- disconnect the 230 V AC power supply network cable from the socket of the demonstration board,
- remove the TN or TT jumper, the ZW H2O jumper, the earth electrode RE1: ZW RE1 jumper
- a jumper may be fastened on the RE2 earth electrode,
- connect the earth resistance meter (MRU-XXX) to the sockets in accordance with Figure 8,
- perform the measurement.
Expected results
- RE1 = 4.7 Ω
- RH = 200 Ω
- RS = 200 Ω
Fig. 8. Connection of the meter
c. Earth resistance measurement RE2 by means of the technical method
In order to perform the RE2 earth resistance measurement proceed as follows:
- disconnect the 230 V AC power supply network cable from the socket of the demonstration board,
- remove the TN or TT jumper, the ZW H2O jumper, the earth electrode RE1: ZW RE1 jumper
- place a jumper on the RE2 ZW RE2 earth electrode,
- connect the earth resistance meter (MRU-XXX) to the sockets in accordance with Figure 9,
- perform the measurement.
Expected results
- RE = 6.8 Ω
- RH = 200 Ω
- RS = 200 Ω
Fig. 9. Connection of the meter
d. Earth resistance measurement RE2 by means of the technical method using current clamp
In order to perform the RE2 earth resistance measurement using clamp proceed as follows:
- disconnect the 230 V AC power supply network cable from the socket of the demonstration board,
- since the measurement of the measurement current is performed with clamps, the user is free to place all the jumpers,
- use an auxiliary lead, instead of the jumper on the E2,
- connect the earth resistance meter (MRU-XXX) to the sockets in accordance with Figure 10,
- perform the measurement.
Expected results
- RE = 6.8 Ω
- RH = 200 Ω
- RS = 200 Ω
Fig. 10. Connection of the meter
e. Earth resistance measurement RE2 by means of the two-clamp method
In order to perform the RE2 earth resistance measurement by means of the two- clamp method proceed as follows:
- disconnect the 230 V AC power supply network cable from the socket of the demonstration board,
- place a jumper on the ZW RE1,
- remove the TN or TT jumper and the ZW H2O jumper,
- use an auxiliary lead, instead of the jumper on the E2,
- connect the earth resistance meter (MRUXXX) to the sockets in accordance with Figure 11,
- perform the measurement.
Expected results
- RE = 11.5 Ω
Fig. 11. Connection of the meter.
Measurement of the earth resistance using loop impedance meters
Measurements of the earth resistance may also be performed with meters for
measuring the short circuit loop impedance. In order to perform such
measurements, the phase conductor of the power supply network is used as an
auxiliary source of voltage which permits to generate the measurement current.
The result of the measurement is a sum of the impedance of the tested earth
resistance, the working earth system, the source and the phase conductor, and
thus it is burdened with a positive error. However if it does not exceed the
acceptable value for the tested earth system, it may be assumed the earth
system is properly constructed and there is no need to apply more precise
measurement methods. Certain meters used for the purpose of measurements of
the short circuit loop impedance may activate the differential RCD switch.
This may influence the maximum measurement current and the time of generating
such current by the meter. In order to avoid activation of the RCD switch, it
is recommended to use the measurement of the short circuit loop impedance in
the ZL-PE[RCD] function.
a. Earth resistance measurement RE
In order to perform the RE earth resistance measurement proceed as follows:
- connect the 230 V AC power supply network cable to the socket of the demonstration board,
- remove the TN or TT jumper, the ZW H2O jumper, the earth electrode RE1: ZW RE1 jumper,
- place a jumper on the RE2 earth electrode,
- turn the RCD switch on,
- connect meter of the short circuit loop impedance in accordance with Figure 12,
- perform the measurement,
- the measurement may provoke activation of the RCD switch (it is impossible to perform a measurement).
Expected results
- RE = 100 Ω + ZL-N of the network
Fig. 12. Connection of the meter
b. Earth resistance measurement RE1
In order to perform the RE1 earth resistance measurement proceed as follows:
- connect the 230 V AC power supply network cable to the socket of the demonstration board,
- remove the TN or TT jumper, the ZW H2O jumper, the earth electrode RE1: ZW RE1 jumper,
- turn the RCD switch on,
- connect meter of the short circuit loop impedance in accordance with Figure 13,
- perform the measurement,
- the measurement may provoke activation of the RCD switch (it is impossible to perform a measurement).
Expected results
- RE = 4.5 Ω + ZL-N of the network
Fig. 13. Connection of the meter
c. Earth resistance measurement RE2
In order to perform the RE2 earth resistance measurement proceed as follows:
- connect the 230 V AC power supply network cable to the socket of the demonstration board,
- remove the TN or TT jumper, the ZW H2O jumper, the earth electrode RE1: ZW RE1 jumper,
- place a jumper on the RE2 earth electrode,
- turn the RCD switch on,
- connect meter of the short circuit loop impedance in accordance with Figure 14,
- perform the measurement,
- the measurement may provoke activation of the RCD switch (it is impossible to perform a measurement).
Expected results
- RE = 6.8 Ω + ZL-N of the network
Fig. 14. Connection of the meter
Earth resistivity measurements
Earth resistivity measurements are used to prepare designs of earth systems,
in cathode protection or in geology.
Earth resistivity measurements are performed using four electrodes which are
placed in line in equal distances (Wenner’s method). In order to determine the
ground resistivity value it is necessary to measure the resistance and perform
calculations taking into account the distances between the electrodes. Modern
meters permit to take into account the distances between the electrodes and
all the calculations are performed automatically. The meter will display both
the resistance value of the measurement probes (in Ω) and the ground
resistivity value (in Ωm).
In order to perform the measurement proceed as follows:
- disconnect the 230 V AC power supply network cable from the socket of the demonstration board,
- connect earth resistance and ground resistivity meter (MRU-XXX) to the sockets in accordance with Figure 5,
- place the „ground type selection” switch at the selected position,
- perform the measurement having previously entered to the meter the appropriate value of the distances between the measurement electrodes.
Expected results
- Switch in the position 5 m: ρ = 31 Ωm
- Switch in the position 10 m: ρ = 295 Ωm
- Switch in the position 20 m: ρ = 5.9 kΩm
Fig. 15. Connection of the meter
Measurements of the continuity of equipotential bondings
Using the demonstration board it is possible to simulate a measurement of the
resistance the equipotential bonding of an electric installation. The
measurement may be performed between point P1 of the equipotential bonding and
point P2 or P3. It is also possible to simulate irregularities related to the
resistance of the equipotential bonding of point P2 and point P1.
In order to activate this function the RE switch simulating the irregularity
must be placed in the „red” position.
Measurement of the resistance of the equipotential bonding between P1 and P2
In order to perform a measurement of the resistance of equipotential bonding between P1 and P2 proceed as follows:
- disconnect the 230 V AC power supply network cable from the socket of the demonstration board,
- place all the switches simulating irregularities in the „green” position,
- turn the RCD switch off,
- connect the meter with cables to the network socket of the board in accordance with Figure 16,
- perform the measurement,
- change the position of the irregularities switch RE to the „red” position,
- perform the measurement.
Expected results
- Switch RE in the “green” position: Rcont (P1-P2) = 0.4 Ω
- Switch RE in the “red” position: Rcont (P1-P2) = 1 kΩ
Fig. 16. Connection of the meter
Measurement of the resistance of equipotential bonding between P1 and P3
In order to perform a measurement of the resistance of equipotential bonding between P1 and P3 proceed as follows:
- disconnect the 230 V AC power supply network cable from the socket of the demonstration board,
- place all the switches simulating irregularities in the „green” position,
- turn the RCD switch off,
- insert the ZW H2O jumper,
- connect the meter with cables to the network socket of the board in accordance with Figure 17,
- perform the measurement.
Expected results
- Rcont (P1-P3) = 0.4 Ω
Fig. 17. Connection of the meter
Insulation resistance measurement
The purpose of the insulation resistance measurements is to determine the
conditions of the installation insulation and electric power loads. The
conditions of the insulation is a decisive factor in the context of safety of
operation and correct functioning of electrical devices. Good insulation is,
apart from other means of protection, also a guarantee of protection from
direct touch.
Before the measurements are performed, make sure the measured object is
disconnected from the power supply network. This is why the meters
manufactured by SONEL S.A. are equipped with a voltmeter.
The demonstration board permits a simulation of an insulation resistance measurement. The measurement may be performed in the L-N and L-PE circuits.
NOTE!
The test voltage must not exceed 1 kV.
Insulation resistance measurements in the L-N circuit
In order to perform the measurement of the insulation resistance in the L-N circuit proceed as follows:
- disconnect the 230 V AC power supply network cable from the socket of the demonstration board,
- place all the switches simulating irregularities in the „green” position,
- turn the RCD switch off,
- connect the meter with cables to the network socket in the board in accordance with Figure 18,
- perform the measurement,
- change the position switch of the irregularities of the resistance of insulation RISO(L-N) to the „red” position,
- perform the measurement.
Expected results
- Switch RISO(L-N) “green” position: RISO(L-N ) = 100 MΩ
- Switch RISO(L-N) “red” position: RISO(L-N) = 100 kΩ
Fig. 18. Connection of the meter
Insulation resistance measurements in the L-PE circuits
In order to perform the measurement of the insulation resistance in the L-PE circuit proceed as follows:
- disconnect the 230 V AC power supply network cable from the socket of the demonstration board,
- place all the switches simulating irregularities in the „green” position,
- turn the RCD switch off,
- connect the meter with cables to the network socket in the board in accordance with Figure 19,
- perform the measurement,
- change the position switch of the irregularities of the resistance of insulation RISO(L-PE) to the „red” position,
- perform the measurement.
Expected results
- Switch RISO(L-PE) “green” position: RISO(L-PE) ≥ 3 GΩ
- Switch RISO(L-PE) “red” position: RISO(L-PE) = 200 kΩ
Fig. 19. Connection of the meter
Replacement Of Fuses
In the case a defect of the device has been detected, when the signalling
diode „POWER” is off in spite of a correct connection of the device to the 230
V / 50 Hz power supply network, it is recommended to check the condition of
the fuse elements. The fuse elements are in the mains socket from which the
device is powered.
In order to do so, disconnect the power supply cord from the device and raise
the fuse compartment using flat screwdriver. The compartment contains two
fuses.
Fig. 20. Position of the fuses
NOTE!
Solely the following fuse elements are approved for the demonstration board: F4A 250 V or T3,15 250 V. In the case fuse elements which are not specified in the present manual are used, there is a risk of damage to the device and a serious danger for the user.
Cleaning And Maintenance
NOTE!
Use only the maintenance methods specified in this manual.
The casing of the device may be cleaned with a soft, damp cloth using all-
purpose detergents.
Do not use any solvents or cleaning agents which might scratch the casing
(powders, pastes, etc.).
The electronic system does not require maintenance.
Dismantling And Disposal
Worn-out electric and electronic equipment should be gathered selectively,
i.e. it must not be placed with waste of another kind.
Worn-out electronic equipment should be sent to a collection point in
accordance with the law of waste electrical and electronic equipment.
Before the equipment is sent to a collection point, do not dismantle any
elements.
Observe local regulations concerning disposal of packages, waste batteries and
accumulators.
Technical Specifications
a) measurement category acc. to EN 61010-1……………………………………………………….CAT II 300 V
b) type of insulation acc. to EN 61010-1………………………………………………………………………….single
c) ingress protection acc. to EN 60529 …………………………………………………………………………….IP40
d) power supply……………………………………………………………………………………………….230 V network
e) max. power consumption ………………………………………………………………………………….. ca. 15 mW
f) RCD type …………………………………………………………………………………………………. 30 mA type AC
g) dimensions ……………………………………………………………………………………….. 405 x 300 x 140 mm
h) weight ………………………………………………………………………………………………………………ca. 3.6 kg
i) operating temperature……………………………………………………………………………………..+10…+40ºC
j) storage temperature…………………………………………………………………………………………-20…+60ºC
k) quality standard …………………….. design, construction and manufacturing are ISO
9001 compliant
l) the product meets EMC requirements acc. to …………………………………………..EN 61000-1
3-2, 3-3
Manufacturer
The manufacturer and provider of warranty and post-warranty service:
SONEL S.A.
Wokulskiego 11
58-100 Świdnica
Poland
tel. +48 74 884 10 53 (Customer Service)
e-mail: customerservice@sonel.com
web page: www.sonel.com
NOTE!
Service repairs must be performed only by the manufacturer.
Customer Support
SONEL S.A.
Woku lskiego 11
58-100 Swidnica
Poland
Customer Service
tel. +48 74 884 10 53
e-mail: customerservice@sonel.com
www.sonel.com