Fronius Symo 3.0-3-S Grid Connected Inverter Instruction Manual

June 5, 2024
Fronius

/ Perfect Charging / Perfect Welding / Solar Energy

Installation instruction
Grid connected inverter

Safety

| WARNING! Incorrect operation or poorly executed work can cause serious injury or damage.
Only qualified staff are authorized to commission your inverter and only within the scope of the respective technical regulations.  Read the safety rules before commissioning the equipment or carrying out maintenance work.
---|---
| WARNING! An electric shock can be fatal. Danger due to grid voltage and DC voltage from
solar modules that are exposed to light.
– Ensure that both the AC side and the DC side of the inverter are de- energized before carrying out any connection work. –  Only an authorized electrical engineer is permitted to connect this equipment to the public grid.
| WARNING! An electric shock can be fatal. Danger due to grid voltage and DC voltage from solar modules.
– The DC main switch is only to be used to de-energize the power stage set. The connection area is still live when the DC main switch is switched off.
– Ensure that the power stage set and connection area are disconnected from one another before carrying out any maintenance or service tasks.
– The power stage set, which is enclosed in a separate housing, must only be disconnected from the connection area when in a de-energized state.
– Maintenance and servicing in the power stage set of the inverter must only be carried out by Fronius-trained service technicians.
| WARNING! An electric shock can be fatal. Danger due to residual voltage in capacitors. Wait for the capacitors to discharge. The discharge time is five minutes.
| WARNING! An inadequate ground conductor connection can cause serious injury or damage. The housing screws provide a suitable ground conductor connection for grounding the housing and must NOT be replaced by any other screws that do not provide a reliable ground conductor connection.
| CAUTION! Risk of damage to the inverter from dirt or water on the terminals and contacts of the connection area.
– When drilling, ensure that terminals and contacts in the connection area do not become dirty or wet.
– Without a power stage set, the mounting bracket does not conform to the protection class of the inverter as a whole and so must not be installed without the power stage set. The mounting bracket should be protected from dirt and moisture during installation.
| CAUTION! Risk of damage to the inverter as the result of incorrectly tightened terminals. Incorrectly tightened terminals can cause heat damage to the inverter that may result in a fire. When connecting AC and DC cables, ensure that all the terminals are tightened to the specified torque.
| CAUTION! Risk of damage to the inverter from overload.
– The maximum amperage when connecting to a single DC terminal is 32 A.
– Connect the DC+ and DC- cables to the DC+ and DC- terminals on the inverter, taking care to ensure that the polarity is correct.
– The maximum DC input voltage must not exceed 1000 V DC.
| Fire prevention
CAUTION! Risk of damage to inverters and other live photovoltaic system components due to poor or unprofessional installation. Poor or unprofessional installation can cause overheating of cables and terminal connections and result in arcs. These can cause heat damage, which in turn may lead to fires. Observe the following when connecting AC and DC cables: – Tighten all terminals to the torque specified in the Operating Instructions – Tighten all grounding terminals (PE / GND), including free ones, to the torque specified in the Operating Instructions – Do not overload cables – Check cables for damage and verify that they are laid correctly – Take note of the safety instructions, Operating Instructions and any local connection regulations Using fastening screws, always screw the inverter firmly to the mounting bracket to the torque specified in the Operating Instructions. Ensure that the fastening screws are tight before starting the inverter!
---|---
| NOTE! Protection class IP65 is only applicable if the inverter is permanently attached to the mounting bracket with screws.
Protection class IP20 applies to the mounting bracket with no inverter or venting duct.
| NOTE! The solar modules connected to the inverter must comply with the IEC 61730 Class A standard.
| NOTE! When photovoltaic modules are exposed to light they supply current to the inverter.
| NOTE! If the cable insulation of the AC cable is not designed for a maximum of 1000 V, AC and DC cables must not be crossed when connecting to the inverter. If crossing the cables during connection is unavoidable, the AC cable must be laid in one piece of the protective hose supplied with the inverter. AC and DC cables can only be laid together if the insulation on both cables is designed for the max. the possible voltage of 1000 V.

Observe the manufacturer’s connection, Installation, and Operating Instructions at all times. To reduce the hazard potential to a minimum, perform all installation and connection work carefully according to the instructions and regulations.
Refer to the device Operating Instructions / Installation Instructions for the tightening torques to be used at the relevant terminal connections.

Fronius manufacturer’s warranty

Detailed, country-specific warranty terms are available on the internet: www.fronius.com/solar/warranty
To obtain the full warranty period for your newly installed Fronius inverter or storage system, please register at: www.solarweb.com.

Installation Help and Recycling

More information on installation
eManual Installation Fronius Symo 3 – 8.2 kW: manuals.fronius.com/html/4204260172

Recycling. Check the provisions of your municipality. Reduce the volume of the box.

Technical Data (WLAN)

Hereby, Fronius International GmbH declares that the radio equipment type Fronius Symo is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.fronius.com

Fronius Symo Installation

Fronius Symo 3 0 3 S Grid Connected Inverter - fig27Fronius Symo 3 0 3 S Grid Connected Inverter -
fig26Fronius Symo 3 0 3 S Grid
Connected Inverter - fig25Fronius Symo
3 0 3 S Grid Connected Inverter - fig24Fronius Symo 3 0 3 S Grid Connected Inverter -
fig23Fronius Symo 3 0 3 S Grid
Connected Inverter - fig22Fronius Symo
3 0 3 S Grid Connected Inverter - fig19Fronius Symo 3 0 3 S Grid Connected Inverter -
fig20Fronius Symo 3 0 3 S Grid
Connected Inverter - fig21Fronius Symo
3 0 3 S Grid Connected Inverter - fig16Fronius Symo 3 0 3 S Grid Connected Inverter -
fig17Fronius Symo 3 0 3 S Grid
Connected Inverter - fig18Fronius Symo
3 0 3 S Grid Connected Inverter - fig14Fronius Symo 3 0 3 S Grid Connected Inverter -
fig15Fronius Symo 3 0 3 S Grid
Connected Inverter - fig12Fronius Symo
3 0 3 S Grid Connected Inverter - fig13

DATCOM

Fronius Symo 3 0 3 S Grid Connected Inverter - DATCOMFronius Symo 3 0 3 S Grid Connected Inverter - DATCOM
1Fronius Symo 3 0 3 S Grid Connected
Inverter - DATCOM 2Fronius Symo 3 0 3
S Grid Connected Inverter - fig9Fronius Symo 3 0 3 S Grid Connected Inverter -
fig10Fronius Symo 3 0 3 S Grid
Connected Inverter - fig11

Operation

Fronius Symo 3 0 3 S Grid Connected Inverter -
fig8Fronius Symo 3 0 3 S Grid
Connected Inverter - fig7Fronius Symo
3 0 3 S Grid Connected Inverter - fig6Fronius Symo 3 0 3 S Grid Connected Inverter -
fig5

Example Country Setups
The available country setups may change during a software update. Therefore, the following list may not exactly match the display on the inverter.

50Hz International 50 Hz
60Hz International 60 Hz
AT1E Österreich cosphi = 1
AT2E Österreich cosphi P 0,9
AT3E Österreich: Q(U)
AUS1 Australia AUS1 – AS/
NZS4777.2
AUS2 Australia AUS2 – VIC
AUS3 Australia AUS3 – NSW
Ausgrid
AUS4 Australia AUS4 – QLD
AUS5 Australia AUS5 – SA
AUS6 Australia AUS6 – WA –
WP
AUS7 Australia AUS7 – WA –
HP
AUA Australia Region A 2020
AUB Australia Region B 2020
AUC Australia Region C 2020
BE Belgique / België
BR2 Brasil: ≤ 6 kVA
BR3 Brasil: > 6 kVA
CH Schweiz / Suisse / Svizzera /
Size
CL
Chile
CY ?????? / Kıbrıs / Cyprus
CZ Česko
DE1F Deutschland (≤ 4,6 kVA)
– konst. cos phi(1)
DE1P Deutschland (≤ 4,6 kVA)
– cos phi(P) 0,95| DE2F Deutschland (> 4,6 kVA)
– konst. cosPhi(1)
DE2P Deutschland (> 4,6 kVA)
– cosPhi(P) 0,9
DE2U Deutschland (> 4,6 kVA)
– Q(U)
DKA1 West Denmark – 125kW
DKA2 East Denmark – 125kW
DU1 Dubai < 10 kW
DU2 Dubai 10 kW – 400 kW
EE Estonia
ES España
ESOS Territorios españoles en
el extranjero (Spanish
Oversea Islands)
EULV EU – low voltage
EUMV EU – medium voltage
FI Finland
FR France
FROS Territoire d’Outre-Mer
(French Oversea Islands)
G98
Great Britain GB – G98
GB Great Britain
GR ??????
HR Hrvatska
HU Magyarország
IE Éire / Ireland IL
????? / ??????? / Israel IN
India| IT6
Italia ≤ 11,08 kVA 2019
IT7
Italia > 11,08 kVA 2019
JO98 Jordan G98
JO99 Jordan G99
LK Sri Lanka
MG50 Microgrid 50 Hz
MG60 Microgrid 60 Hz
NI98 Northern Ireland G98
NI99 Northern Ireland G99
NL Nederland
NO Norge
NZ New Zealand
PF1 Polynésie française
(French Polynesia)
PL Poland
PT Portugal
RO România
SA Saudi Arabia
SE Sverige
SI Slovenija
SK Slovensko
TH M Thailand MEA
TH P Thailand PEA
TR Türkiye
UA ???????
ZA South Africa / Suid-Afrika
---|---|---

Fronius Symo 3 0 3 S Grid Connected Inverter - fig4

The display of parameters to be configured depends on the selected device type

Firmware-/Software-Update

Fronius Symo 3 0 3 S Grid Connected Inverter - fig3

Australia – Conduits

Tightly sealing the conduits

Ensure that the conduits are tightly sealed.Fronius Symo 3 0 3 S Grid
Connected Inverter - conduits are tightly

Seal Conduits

Fronius Symo 3 0 3 S Grid Connected Inverter - fig1

HINWEIS!
Condensation within the conduits can damage the inverter or components of the photovoltaic systems. To avoid undesirable air circulation and condensation in the conduits,
► seal all conduits being used with a permanently elastic sealant,
► seal every incoming and outgoing conduit,
► seal both conduit ends.

Fronius Symo 3 0 3 S Grid Connected Inverter - fig2

Serial Number Sticker for Customer Use

Fronius Symo 3 0 3 S Grid Connected Inverter - fig   fronius.com/en/solar-en-ergy/installers-partners/products- solutions/moni-toring-digital-tools
MONITORING & DIGITAL TOOLS

FRONIUS INTERNATIONAL GMBH
Froniusstraße 1
A-4643 Pettenbach
AUSTRIA
contact@fronius.com
www.fronius.com
Under www.fronius.com/contact you will find the addresses
of all Fronius Sales & Service Partners and locations.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals