VENTS VKPI EC Inline Centrifugal Fan in Sound Insulated Casing User Manual

June 5, 2024
VENTS

USER’S MANUAL

VKPI EC

VENTS VKPI EC Inline Centrifugal Fan

Inline centrifugal fan
in sound insulated casing


VENTS logo b21

VENTS logo b21VKPI EC


This user’s manual is a main operating document intended for technical, maintenance, and operating staff.
The manual contains information about purpose, technical details, operating principle, design, and installation of the VKPI EC unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
The information in this user’s manual is correct at the time of the document’s preparation.
The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means in any information search system or translated into any language in any form without the prior written permission of the Company.

SAFETY REQUIREMENTS
  • Please read the user’s manual carefully prior to installing and operating the unit.
  • All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
  • The warnings contained in the user’s manual must be considered most seriously since they contain vital personal safety information.
  • Failure to follow the rules and safety precautions noted in this user’s manual may result in an injury or unit damage.
  • After a careful reading of the manual, keep it for the entire service life of the unit.
  • While transferring the unit control, the user’s manual must be turned over to the receiving operator.
UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS

Disconnect the unit from power mains prior to any installation operations.

The unit must be grounded!

VENTS VKPI EC - Safety Symbol 3

Do not change the power cable length at your own discretion.
Do not bend the power cable.
Avoid damaging the power cable.
Do not put any foreign objects on the power cable.

VENTS VKPI EC - Safety Symbol 4 Do not use damaged equipment or cables when connecting the unit to power mains.

VENTS VKPI EC - Safety Symbol 5

Do not touch the unit controls with wet hands.
Do not carry out the installation and maintenance operations with wet hands.

Unpack the unit with care.

  While installing the unit, follow the safety regulations specific to the use of electric tools.

VENTS VKPI EC - Safety Symbol 8 Do not lay the power cable of the unit in close proximity to heating equipment.

VENTS VKPI EC - Safety Symbol 9

  • Do not operate the unit outside the temperature range stated in the user’s manual.
  • Do not operate the unit in aggressive or explosive environments.

VENTS VKPI EC - Safety Symbol 10

• Do not wash the unit with water.
• Protect the electric parts of the unit against ingress of water.

VENTS VKPI EC - Safety Symbol 11• Do not allow children to operate the unit.

VENTS VKPI EC - Safety Symbol 12• Do not store any explosive or highly flammable substances in close proximity to the unit.

VENTS VKPI EC - Safety Symbol 13• Do not open the unit during operation.

VENTS VKPI EC - Safety Symbol 14• Do not block the air duct when the unit is switched on.

VENTS VKPI EC - Safety Symbol 15• Do not sit on the unit and avoid placing foreign objects on it.

VENTS VKPI EC - Safety Symbol 16• Disconnect the unit from power mains prior to any technical maintenance.

VENTS VKPI EC - Safety Symbol 17• When the unit generates unusual sounds, odour, or emits smoke, disconnect it from power supply and contact the Seller.

VENTS VKPI EC - Safety Symbol 18• Do not direct the air flow produced by the unit towards open flame or ignition sources.

VENTS VKPI EC - Safety Symbol 19• In case of continuous operation of the unit, periodically check the security of mounting.

VENTS VKPI EC - Safety Symbol 20• Use the unit only for its intended purpose.

THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.

PURPOSE

THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL, MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE TRAINING.
THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING.
THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN.

The centrifugal fan in a sound insulated casing is designed for supply and exhaust ventilation of domestic, public and industrial premises with high requirements to the noise level and with limited space for mounting.
The unit is rated for continuous operation.
The unit is a component part and is not designed for stand-alone operation.
Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot and oil particles or environments favourable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).

DELIVERY SET

NAME                                     NUMBER
Fan                                          1 pc.
User’s manual                          1 pc.
Packing box                             1 pc.

DESIGNATION KEY

VENTS VKPI EC - DESIGNATION KEY

  1. Series name

  2. Rectangular duct size
    300×150/400×200/500×250/500×300/600×300/600×350/700×400/800×500/900×500/1000×500

  3. Motor modification
    M: medium pressure motor
    L: high pressure motor

  4. Phases
    1: single-phase
    3: three-phase

  5. Motor type
    EC: synchronous electronically commutated motor

TECHNICAL DATA

The unit is designed for indoor application with the ambient temperature ranging from 0 °C up to +45 °C and relative humidity up to 80 %. The unit is rated as a Class I electrical appliance. Ingress protection rating against access to hazardous parts and water ingress is IPX4. The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.

| VKPI 300х150 M1 EC| VKPI 300х150 L1 EC| VKPI 400х200 M1 EC| VKPI 400х200 L1 EC| VKPI 500х250 M1 EC| VKPI 500х250 L1 EC| VKPI 500х300 L1 EC| VKPI 600х300 M1 EC
---|---|---|---|---|---|---|---|---
Unit voltage [V/50 (60) Hz]| 1~230| 1~230| 1~230| 1~230| 1~230| 1~230| 1~230| 1~230
Power [W]| 97| 101| 91| 192| 252| 555| 553| 326
Current [A]| 0.73| 0.80| 0.69| 1.43| 1.85| 4.10| 4.20| 2.45
Max. air flow [m³/h]| 565| 665| 810| 1190| 1590| 2480| 2700| 2545
RPM [min-1]| 3300| 3500| 2470| 3010| 2500| 3100| 3100| 2000
Sound pressure level at 3 m distance [dBA]| 29| 30| 33| 30| 34| 41| 43| 34
Transported air temperature [°С]| -25…+50
Ingress protection rating| IPX4

| VKPI 600х350 M1 EC| VKPI 600х350 L3 EC| VKPI 700х400 M1 EC| VKPI 700×400 L3 EC| VKPI 800х500 М3 EC| VKPI 800×500 L3 EC| VKPI 900×500 L3 EC| VKPI 1000×500 L3 EC
---|---|---|---|---|---|---|---|---
Unit voltage [V/50 (60) Hz]| 1~230| 3~400| 1~230| 3~400| 3~400| 3~400| 3~400| 3~400
Power [W]| 361| 1308| 795| 2748| 2025| 2925| 3429| 3429
Current [A]| 2.62| 2.35| 3.48| 2.80| 2.01| 3.05| 5.00| 5.00
Max. air flow [m³/h]| 2815| 4290| 5710| 6810| 8395| 8535| 11190| 11190
RPM [min-1]| 2000| 3160| 1400| 2530| 1470| 2400| 1800| 1800
Sound pressure level at 3 m distance [dBA]| 38| 40| 37| 43| 43| 42| 47| 47
Transported air temperature [°С]| -25…+50
Ingress protection rating| IPX4

VENTS VKPI EC - DIMENSIONS 1

OVERALL DIMENSIONS

Model Dimensions [mm] Weight [kg]
B B1 B2
VKPI 300×150 M1 EC 300 320
VKPI 300×150 L1 EC 300 320
VKPI 400×200 M1 EC 400 420
VKPI 400×200 L1 EC 400 420
VKPI 500×250 M1 EC 500 520
VKPI 500×250 L1 EC 500 520
VKPI 500×300 L1 EC 500 520

VENTS VKPI EC - DIMENSIONS 3

OVERALL DIMENSIONS

Model Dimensions [mm] Weight [kg]
B B1 B3
VKPI 600×300 M1 EC 600 620
VKPI 600×350 M1 EC 600 620
VKPI 600×350 L3 EC 600 620
VKPI 700×400 M1 EC 700 720
VKPI 700×400 L3 EC 700 720
VKPI 800×500 М3 EC 800 820
VKPI 800×500 L3 EC 800 820
VKPI 900×500 L3 EC 900 920
VKPI 1000×500 L3 EC 1000 1020
MOUNTING AND SET-UP

BEFORE MOUNTING MAKE SURE THE CASING DOES NOT CONTAIN ANY FOREIGN OBJECTS (E.G. FOIL, PAPER).

WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT MAINTENANCE AND REPAIR.

Check the fan power cables for integrity and make sure the impeller has smooth rotation prior to mounting.
The VKPI 300×150 M1 E, VKPI 300×150 L1 E, VKPI 400×200 M1 E, VKPI 400×200 L1 E, VKPI 500×250 M1 E, VKPI 500×250 L1 E, and VKPI 500×300 L1 E fans are mounted between the rectangular air ducts and do not require special fastening if the connection is made directly to them.
Connect the fan to air ducts with M8 bolts and nuts.
The VKPI 600×300 M1 E, VKPI 600×350 M1 E, VKPI 600×350 L3 E, VKPI 700×400 M1 E, VKPI 700×400 L3 E, VKPI 800×500 M3 EC, VKPI 800×500 L3 E, VKPI 900×500 L3 E and VKPI 1000×500 L3 E fans are attached to the ceiling on anchors/studs or suspension brackets.
The fan may be installed in any position in consideration of the air flow direction (as indicated by the arrow on the fan casing).
Access for the fan maintenance shall be provided.
The casing is equipped with a removable access cover for maintenance purposes.

VENTS VKPI EC - MOUNTING AND SET-UP 1 VENTS VKPI EC - MOUNTING AND SET-UP 2

VENTS VKPI EC - MOUNTING AND SET-UP 3

VENTS VKPI EC - MOUNTING AND SET-UP 4

CONNECTION TO POWER MAINS

DISCONNECT THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.

CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED ELECTRICIAN WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER CAREFUL READING OF THE PRESENT USER’S MANUAL. THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.

The unit is rated for connection to 1~230 V/50 (60) Hz or 3~400 V/50 (60) Hz power mains according to the wiring diagram.
The connection must be made using durable, insulated and heat-resistant conductors (cables, wires).
The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and installation method.
The external power input must be equipped with an automatic circuit breaker QF built into the stationary wiring to open the circuit in the event of overload or short-circuit.
The position of the external automatic circuit breaker must ensure free access for quick power-off of the unit.
The trip current of the automatic circuit breaker must exceed the maximum current consumption of the unit (refer to the “Technical data” section or to the unit label).
It is recommended to select the nominal current of the circuit breaker from the standard series, following the maximum current of the connected unit.
The circuit breaker is not included in the delivery set and can be ordered separately.

Wiring diagram of the fan with a single-phase motor

VENTS VKPI EC - Wiring diagram 1

Wiring diagram of the fan with a three-phase motor

VENTS VKPI EC - Wiring diagram 2

TECHNICAL MAINTENANCE

DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!

The technical maintenance includes periodic cleaning of the surfaces from accumulated dust and dirt.
Use a soft brush or compressed air to remove dust from metal surfaces of the fan. Use a vacuum cleaner to remove dust from the sound insulating surface.
The impeller blades require thorough cleaning once in 6 months.
Detach air ducts from the fan before starting maintenance works.
Clean the impeller blades with a soft cloth wetted in mild water detergent solution. Avoid liquid dripping on the motor.
Wipe the fan surfaces dry after cleaning.
While cleaning the fan make sure the balance counterweights are not shifted and the impeller is not misaligned.

VENTS VKPI EC - TECHNICAL MAINTENANCE 1 VENTS VKPI EC - TECHNICAL MAINTENANCE 2

VENTS VKPI EC - TECHNICAL MAINTENANCE 3 VENTS VKPI EC - TECHNICAL MAINTENANCE 4

VENTS VKPI EC - TECHNICAL MAINTENANCE 5 VENTS VKPI EC - TECHNICAL MAINTENANCE 6

TROUBLESHOOTING
Problem Possible reasons Troubleshooting
The fan does not run. No power supply. Check the automatic circuit breaker.

Check the electric connections.
Noisy operation.| Impeller imbalance.| Clean the impeller.

STORAGE AND TRANSPORTATION REGULATIONS
  • Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 °C to +40 °C and relative humidity up to 70 %.
  • Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
  • Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
  • Follow the handling requirements applicable for the particular type of cargo.
  • The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
  • Avoid sharp blows, scratches, or rough handling during loading and unloading.
  • Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.

The warranty repair does not include:

  • routine technical maintenance
  • unit installation/dismantling
  • unit setup

To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.

The manufacturer’s warranty does not apply to the following cases:

  • User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
  • Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
  • User’s failure to ensure timely technical maintenance of the unit.
  • External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
  • Redesign or engineering changes to the unit.
  • Replacement and use of any assemblies, parts and components not approved by the manufacturer.
  • Unit misuse.
  • Violation of the unit installation regulations by the user.
  • Violation of the unit control regulations by the user.
  • Unit connection to power mains with a voltage different from the one stated in the user’s manual.
  • Unit breakdown due to voltage surges in power mains.
  • Discretionary repair of the unit by the user.
  • Unit repair by any persons without the manufacturer’s authorization.
  • Expiration of the unit warranty period.
  • Violation of the unit transportation regulations by the user.
  • Violation of the unit storage regulations by the user.
  • Wrongful actions against the unit committed by third parties.
  • Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
  • Missing seals if provided by the user’s manual.
  • Failure to submit the user’s manual with the unit purchase date stamp.
  • Missing payment paperwork certifying the unit purchase.

FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE- FREE OPERATION OF THE UNIT.

USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP.

CERTIFICATE OF ACCEPTANCE
Unit Type Inline centrifugal fan in sound insulated casing
Model VKPI _____ EC
Serial Number
Manufacture Date
Quality Inspector’s Stamp
SELLER INFORMATION

Seller| | VENTS VKPI EC - Stamp

Seller’s Stamp

---|---|---
Address|
Phone Number|
E-mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|

INSTALLATION CERTIFICATE

The VKPI _____ EC unit is installed pursuant to the requirements stated in the present user’s manual.| VENTS VKPI EC -
Stamp

Installation Stamp

---|---
Company name|
Address|
Phone Number|
Installation Technician’s Full Name| **
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:**|

WARRANTY CARD

Unit Type| Inline centrifugal fan in sound insulated casing| VENTS
VKPI EC - Stamp

Seller’s Stamp

---|---|---
Model| VKPI _____ EC
Serial Number|
Manufacture Date|
Purchase Date|
Warranty Period|
Seller|


www.ventilation-system.com

VENTS logo b22

VENTS VKPI EC - QR Code

V210EN-01

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals