BLAUBERG MOON Unique Range Of Contemporary Extractor Fans User Manual
- June 5, 2024
- BLAUBERG
Table of Contents
AXIAL FAN
MOON | HI-FI | BAVARIA
USER’S MANUAL
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about the purpose, technical details,
operating principle, design, and installation of the Blauberg Moon/Hi-
Fi/Bavaria unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
The information in this user’s manual is correct at the time of the document’s
preparation.
The Company reserves the right to modify the technical characteristics,
design, or configuration of its products at any time in order to incorporate
the latest technological developments.
No part of this publication may be reproduced, stored in a retrieval system,
or transmitted, in any form or by any means in any information search system
or translated into any language in any form without the prior written
permission of the Company.
READ THE USER’S MANUAL CAREFULLY BEFORE PROCEEDING WITH INSTALLATION WORKS.
COMPLIANCE WITH THE MANUAL REQUIREMENTS ENSURES RELIABLE OPERATION AND THE
LONG SERVICE LIFE OF THE UNIT.
KEEP THE USER’S MANUAL AVAILABLE AS LONG AS YOU USE THE UNIT. YOU MAY NEED TO
REREAD THE INFORMATION ON THE PRODUCT SERVICING.
All user’s manual requirements, as well as the provisions of all the
applicable local and national construction, electrical, and technical norms
and standards, must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing,
maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to
1000 V are allowed for installation and maintenance. The present user’s manual
should be carefully read before beginning work.
-
Single-phase power mains must comply with the acting local electrical norms and standards.
-
Fixed electrical wiring must be equipped with an automatic circuit breaker.
-
The unit must be connected to power mains through a double pole circuit breaker of suitable rating integrated into the fixed wiring system with the opening of contacts at all poles. The gap between the circuit breaker contacts at all poles must be not less than 3 mm.
-
Check the unit for any visible damage to the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.
-
While mounting the unit, avoid compression of the casing!
Deformation of the casing may result in motor jams and excessive noise. -
Misuse of the unit and any unauthorized modifications are not allowed.
-
Do not expose the device to adverse atmospheric agents (rain, sun, etc.).
-
Take steps to prevent ingress of smoke, carbon monoxide, and other combustion products into the room through open chimney flues or other fire-protection devices. A sufficient air supply must be provided for proper combustion and exhaust of gases through the chimney of fuel-burning equipment to prevent back drafting.
-
The unit may adversely affect the safe operation of appliances burning gas or other fuels (including those in other rooms) due to the backflow of combustion gases. These gases can potentially result in carbon monoxide poisoning. After installation of the unit, the operation of flued gas appliances should be tested by a competent person to ensure that backflow of combustion gases does not occur.
-
Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.
-
Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.
-
Do not close or block the intake or extract vents in order to ensure efficient airflow.
-
Do not sit on the unit and do not put objects on it.
-
This appliance can be used by children aged 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning the use of the appliance in a safe way and understand the hazards involved.
-
Do not allow children to play with the unit.
-
Cleaning and user maintenance shall not be made by children without supervision.
-
The information in this user’s manual was correct at the time of the document’s preparation.
-
The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.
-
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means in any information search system or translated into any language in any form without the prior written permission of the Company.
WARNING! Similar to the use of any other household electrical appliances when operating this fan, the following basic rules must be followed:
- Never touch the fan with wet or damp hands.
- Never touch the fan when barefoot.
THE PRODUCT MUST BE DISPOSED OF SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE OF THE UNIT AS UNSORTED DOMESTIC WASTE.
DELIVERY SET
Fan – 1 pc.
Screws with dowels – 4 pcs.
Plastic screwdriver – 1 pc. (only for the models with a timer)
User’s manual – 1 pc.
Packing box – 1 pc.
BRIEF DESCRIPTION
The product is an axial fan for exhaust ventilation of small and medium-sized premises heated in winter. The design of the fan may include a back valve that prevents air from flowing into the room when the fan is off. The fan is designed for connection to ø100 and 125 mm air ducts.
OPERATION GUIDELINES
The fan is rated for connection to 220-240 V/50 Hz or 12 V/50 Hz single-phase
AC power mains, depending on the model type.
For more detailed information, see the casing sticker. Ingress protection
rating against access to hazardous parts and water ingress is IP44. The
manufacturer’s recommended operating temperature range is from +1 °C to + 40
°C.
The unit is rated as a Class II (220-240 V/ 50 Hz) or Class III (12 V/50 Hz)
electric appliance.
DESIGNATION KEY
MOUNTING
The fan can be mounted to the ceiling or onto a wall with air extraction into
a ventilation shaft or a matching diameter round air duct (Fig. 2). The fan
installation steps are given in Fig. 3-11. Electric connection diagrams are
given in Fig. 12-17.
Connection diagram terminal key:
L — line
N — neutral
LT — timer control line
S — external switch
QF — automatic switch
WARNING! Fans rated for 12 V (as specified on the fan packing and casing) must be connected to ~12 V electric mains only!
ELECTRONIC SYSTEM OPERATION ALGORITHM
The T model fans equipped with a timer are activated by a control voltage
applied to input terminal S by an external switch (e.g. indoor light switch).
Upon control voltage removal the fan continues to operate for the period of
time set by the timer within the range of 2 to 30 minutes.
Fan with a ТR timer. When the control voltage is applied to input
terminal S by the external switch (e.g. indoor light switch), the turn-on
delay timer is activated. The fan blades do not rotate. The turn-on delay time
is in the range of 0 to 2 minutes. The adjustment range can be selected by
means of the potentiometer on the timer circuit board. Upon control voltage
removal the fan continues to operate for the period of time set by the turn-
off delay timer within the range of 2 to 30 minutes.
The fan with the V2 ТR timer runs at Speed 1. When the control voltage is
applied to the S input, the turn-on delay timer is activated by the external
switch from 0 to 2 minutes, and the fan switches to 2nd speed. You can select
the control range using a potentiometer on the timer board. After removing the
control voltage, the fan continues to operate for the time specified by the
turn-off delay timer, which ranges from 2 to 30 minutes, then switches to
Speed 1.
The H model fans equipped with a timer and a humidity sensor are
activated by a control voltage applied to input terminal S or on exceeding the
pre-set humidity level H adjustable within the ~60 % to ~90 % range. Upon
control voltage removal or a decrease of humidity level H the fan continues to
operate for the period of time set by the timer within the range from 2 to 30
minutes.
A V2 Н double-speed fan with a timer and humidity sensor is switched to
Speed 2 when the set humidity level in the room (from 60 to 90 %) is exceeded.
As the indoor humidity level drops down to the set value, the fan continues to
operate for 5 minutes and goes to Speed 1. The fan can be turned on in manual
mode, for example, using a light switch.
After turning on the switch, the fan switches to Speed 2 with a time delay of
45 s. After the switch is turned off, the fan will continue to work at Speed 2
for the time set by the turn-off delay timer, from 2 to 30 minutes, then it
will switch to Speed 1. To set the maximum level of humidity, it is necessary
to set the potentiometer regulator to the H max position (90 %).
THE TIMER CIRCUIT IS LIVE.
MAKE SURE THE FAN IS DISCONNECTED FROM THE POWER SUPPLY.
— To adjust the fan activation delay time, turn the T on the potentiometer
knob clockwise (+) or counter-clockwise (-) which sets the activation delay
time within the range from 0 to 2 minutes.
— To adjust the fan deactivation delay time, turn the T off potentiometer
knob clockwise (+) or counter-clockwise (-) which sets the activation delay
time within the range from 2 to 30 minutes.
— To adjust the humidity sensor threshold value turn the H potentiometer
knob clockwise (+) or counter-clockwise (-) which sets the threshold value
within the range from 60 % to 90 %.
DO NOT USE A METAL SCREWDRIVER, KNIFE, ETC. FOR ADJUSTMENT OPERATIONS NOT TO DAMAGE THE CIRCUIT BOARD.
The fan is supplied with a special plastic screwdriver. Use the screwdriver to adjust the fan activation or deactivation delay time or the humidity sensor threshold value.
MAINTENANCE
To clean the unit from any dust and dirt which may accumulate on the surfaces (Fig. 18-21), use a soft cloth and a brush soaked in a mild detergent solution. Avoid spilling liquid on the electrical components. Wipe the cleaned surfaces dry.
TROUBLESHOOTING
Problem | Possible reasons | Troubleshooting |
---|
When the unit is connected to power
mains, the fan does not rotate and
does not respond to any controls.| No power supply.| Make sure the power
supply line is connected correctly, otherwise troubleshoot the connection
error.
Internal connection fault.| Contact the Seller.
Low airflow.| The ventilation system is clogged.| Clean the ventilation
system.
increased noise, and vibration.| The impeller is clogged.| Clean the impeller.
The fan is not secured well or is not mounted properly.| Troubleshoot the
installation error.
The ventilation system is clogged.| Clean the ventilation system.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with a temperature range of +5 °C up to + 40 °C and relative humidity up to 70 %.
- The storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility.
We hereby declare that the product complies with the provisions of the
Electromagnetic Compatibility (EMC) Directive 2014/30/ EU of the European
Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the
European Parliament and of the Council and CE-marking Council Directive
93/68/EEC. This certificate is issued following a test carried out on samples
of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 60 months
after the retail sale date provided the user’s observance of the
transportation, storage, installation, and operation regulations. Should any
malfunctions occur in the course of the unit operation through the
Manufacturer’s fault during the guaranteed period of operation, the user is
entitled to get all the faults eliminated by the manufacturer by means of
warranty repair at the factory free of charge. The warranty repair includes
work specific to the elimination of faults in the unit operation to ensure its
intended use by the user within the guaranteed period of operation. The faults
are eliminated by means of replacement or repair of the unit components or a
specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from a warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts, and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit were committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT, AND THE USER’S MANUAL WITH THE PURCHASE DATE
STAMP.
| D, mm| A, mm| B, mm| L, mm
---|---|---|---|---
Moon 100| 99| 180| 128| 123
Hi-Fi 100| 99| 180| 128| 120
Bavaria 100| 99| 180| 128| 120
Moon 125| 123.5| 180| 158| 130
Hi-Fi 125| 123.5| 180| 158| 126
Bavaria 125| 123.5| 180| 158| 127
| ![BLAUBERG MOON Unique Range Of Contemporary Extractor Fans - 9](https://manuals.plus/wp- content/uploads/2022/06/BLAUBERG-MOON-Unique-Range-Of-Contemporary-Extractor- Fans-9.png)
---|---
![BLAUBERG MOON Unique Range Of Contemporary Extractor Fans - 10](https://manuals.plus/wp-content/uploads/2022/06/BLAUBERG-MOON-Unique- Range-Of-Contemporary-Extractor-Fans-10.png)
| ![BLAUBERG MOON Unique Range Of Contemporary Extractor Fans - 11](https://manuals.plus/wp- content/uploads/2022/06/BLAUBERG-MOON-Unique-Range-Of-Contemporary-Extractor- Fans-11.png)
![BLAUBERG MOON Unique Range Of Contemporary Extractor Fans - 12](https://manuals.plus/wp-content/uploads/2022/06/BLAUBERG-MOON-Unique- Range-Of-Contemporary-Extractor-Fans-12.png)
|
|
|
Quality Inspector’s Stamp|
---|---
Seller (name and stamp of the seller)|
Manufacture Date|
Purchase Date|
blaubergventilatoren.de
B160EN-06