BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator User Manual

June 1, 2024
BLAUBERG

Single-room reverSible energy recovery ventilator
USER’S MANUAL

BLAUBERG VENTO Single Room Reversible Energy Recovery
Ventilator

vento in Home Wi-Fi
vento in Home Wi-Fi m
vento in Home Wi-Fi mini
vento in Home Wi-Fi mini m
www.blaubergventilatoren.de

This user’s manual is a main operating document intended for technical, maintenance, and operating staff.
The manual contains information about purpose, technical details, operating principle, design, and installation of the VENTO inHOME Wi-Fi (mini) (M) unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.

SAFETY REQUIREMENTS

This unit is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the unit by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the unit.
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
Cleaning and user maintenance shall not be made by children without supervision.
Children shall not play with the appliance.

Connection to the mains must be made through a disconnecting device, which is integrated into the fixed wiring system in accordance with the wiring rules for design of electrical units, and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a safety hazard.
Ensure that the unit is switched off from the supply mains before removing the guard.
Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.

All operations described in this manual must be performed by qualified personnel only, properly trained and qualified to install, make electrical connections and maintain ventilation units.
Do not attempt to install the product, connect it to the mains, or perform maintenance yourself.
This is unsafe and impossible without special knowledge.
Disconnect the power supply prior to any operations with the unit.
All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.
Connection of the unit to power mains is allowed by a qualified electrician with a work permit for the electric units up to 1000 V after careful reading of the present user’s manual.
Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the document’s preparation.
The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
BEFORE INSTALLING ADDITIONAL EXTERNAL DEVICES, READ THE RELEVANT USER MANUALS.

**** THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE

PURPOSE

The ventilator is designed to ensure continuous mechanical air exchange in flats, cottages, hotels, cafés and other domestic and public premises. The ventilator is equipped with a regenerator that enables supply of fresh filtered air heated by means of extract air heat energy recovery.
The ventilator is designed for installation on external walls.
The ventilator is rated for continuous operation.

DELIVERY SET

Name Number

VENTO inHOME Wi-Fi mini VENTO inHOME Wi-Fi mini M| VENTO inHOME Wi-Fi VENTO inHOME Wi-Fi M
Indoor unit of the ventilator| 1 pc.| 1 pc.
Air duct| 1 pc.| 1 pc.
Silencer| 1 pc.| 1 pc.
Fan assembly| –| 1 pc.
Heat recovery unit assembly| –| 1 pc.
Assembled cartridge| 1 pc.| –
Outer ventilation hood| 1 pc.| 1 pc.
Remote control| 1 pc.| 1 pc.
Cardboard template| 1 pc.| 1 pc.
Mounting kit| 2 packs| 2 packs
Mounting wedges| 1 set| 1 set
User’s manual| 1 pc.| 1 pc.
Mounting hood installation instruction| 1 pc.| 1 pc.
Packing box| 1 pc.| 1 pc.

DESIGNATION KEY

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator -
DESIGNATION KEY

TECHNICAL DATA

The temperature in the room where the indoor unit of the ventilator is installed must be in the range from +1 ˚C to +40 ˚C with relative humidity up to 65 % (no condensation build-up).
The temperature of the transported air should be in the range from -15 ˚С to +40 ˚C.
If the conditions of use of the ventilator are outside the specified limits, turn off the ventilator. Provide fresh air supply through windows.
The unit is rated as a class II electric appliance.
Ingress protection rating against access to hazardous parts and water ingress is IP24.
The type of hood supplied and the length of the duct depend on the model of the ventilator (see section Designatioin Key).
The ventilator design is constantly being improved, thus some models may be slightly different from those described in this manual.

OVERALL DIMENSIONS OF THE INDOOR UNIT [MM]

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - OVERALL
DIMENSIONS

Wi-Fi technical data

Standard IEFE 802,11, b/g/n
Frequency band [GHz] 2.4
Transmission power [mW] (dBm) 100(+20)
Network DHCP
WLAN safety WPA, WPA2

DESIGN AND OPERATING PRINCIPLE

The ventilator consists of an indoor unit with a decorative front panel, a fan unit, a heat exchanger unit, located inside the air duct and the outer ventilation hood.
In the VENTO inHOME Wi-Fi mini and VENTO inHOME Wi-Fi mini M models, the fan and heat exchanger units are combined in a single cartridge.
Two filters are located inside the air duct in the airflow path to provide coarse air purification and prevent dust and foreign objects from entering the heat exchanger and the fan.
In the bottom right corner of the front panel of the ventilator, there is a window for the IR remote control receiver combined with a light sensor. The light sensor controls the brightness of the control panel LEDs.
The LEDs glow brighter during daylight hours and dimmer in the dark.

VENTILATOR DESIGN

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator -
VENTILATOR DESIGN

Operating principle of VENTO inHOME Wi-Fi and VENTO inHOME Wi-Fi mini ventilator shutters
The indoor unit of these models is equipped with automatic shutters. During the ventilator operation the automatic shutters are opened and let the air flow freely through the ventilator. The automatic shutters are closed for 2 minutes at the ventilator shut down.
The process of opening and closing the shutter can take up to five minutes.
WARNING! The product is equipped with a shutter lock (item 1). In the event of a power failure, the product shuts down but the shutters remain open.
If necessary, you can close the shutters. To do this, remove the front cover and press the push rod (item 2) in the direction of the arrow. This releases the push rod and the shutters close.
The product is equipped with a shutter position sensor. When power is restored, the sensor detects the position of the shutters and opens them if the product has been running or closes them if the product has not been running.
The shutter opening/closing mechanism operates with a delay of 1 to 5 minutes after the unit is switched on or off.
The indoor unit of the VENTO inHOME Wi-Fi M ventilators does not have shutters. The air duct in these models can only be blocked by pushing the front panel of the ventilator as far as it will go, as shown in the figure below.
The figure below shows the position of the shutters in the closed and open positions.

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator -
shutters

Opening/closing the airflow
To open the air duct, gently pull the front panel towards you with both hands. The fan starts operating according to the actual speed setting.
To close the air duct, gently press down on the front panel until the air duct is completely closed. The fan turns off automatically. The unit functionality is not changed.

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - closing
the airflow

VENTILATOR OPERATION MODES
Ventilation: the ventilator runs either in the air exhaust or air supply mode at a set speed.
In this mode some of the ventilators in the network run in the air supply mode and the other ones in air exhaust mode, depending on the position of the DIP switch No. 3 (See section Adjusting the operating mode of the ventilator with DIP-switches).
Air supply: the ventilator operates in the air supply mode irrespective of the position of the DIP switch No. 3 (see section Adjusting the operating mode of the ventilator with DIP-switches).
Boost: the ventilator goes to the maximum speed without changing the operation mode.
Regeneration: the ventilator runs in two cycles, 70 seconds each, with heat and humidity regeneration.
Cycle I. Warm stale air is extracted from the room and flows through the ceramic regenerator, which gradually absorbs heat and humidity. In 70 seconds, as the ceramic regenerator gets warmed, the ventilator is switched to supply mode.
Cycle II. Fresh intake air from outside flows through the ceramic regenerator, absorbs accumulated moisture and is heated up to the room temperature. In 70 seconds, as the ceramic regenerator gets cooled down, the ventilator is switched to air extraction mode  and the cycle is renewed. If two ventilators are installed, they operate with opposite rotation directions in this mode. While one ventilator supplies air, the other one extracts it.

The ventilators are equipped with a humidity sensor and terminals for connecting an external 0-10 V analogue sensor and an external normally open contact (relay sensor). When any of these devices is triggered, the ventilator switches to maximum speed (Boost
mode).
When the sensors return to their original position, the Boost mode switch-off delay timer starts.
Relevant sections of the Blauberg Home mobile app allow you to configure the following ventilator settings:

  • switch on or off the humidity sensor, 0-10 V analogue sensor, and relay sensor;
  • set the triggering threshold for the humidity sensor and the 0-10 V analogue sensor;
  • set the Boost mode switch-off delay duration (30 minutes by default);
  • set the operation duration under the first speed timer («Night» mode) (8 hours by default);
  • set the operation duration under the third speed timer («Party» mode) (4 hours by default).

If necessary, you can set different ventilator speeds for different time intervals by day of the week in the «Weekly Schedule» section of the Blauberg Home mobile app. For the week schedule to work correctly, you need to set the current date and time correctly in
the «Date and Time» section.

When simultaneously activating several operation modes that exclude each other, the ventilator selects the mode according to the following priority:

  1. The Night mode timer or the Party mode timer.
  2. Standby.
  3. Boost.
  4. Weekly Schedule
  5. Standard operation mode.

MOUNTING AND SET-UP

READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.
DO NOT BLOCK THE AIR DUCT OF THE INSTALLED VENTILATOR WITH DUST ACCUMULATING MATERIALS, SUCH AS CURTAINS, CLOTH SHUTTERS, ETC.
AS IT PREVENTS AIR CIRCULATION IN THE ROOM.

The figure below shows a schematic layout of the ventilator’s internal elements depending on the wall thickness. The ability to mount the ventilator in the wall depends on the length of the internal elements and the required protrusion A.
The length of the internal elements, the diameter of the required opening and the minimum wall thickness in which the ventilator can be installed when using different external ventilation hoods are shown in the table below.

Layout of the ventilator units inside the wall

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator -
ventilator 2

Reference dimensions for installation of ventilators| Ventilator model or installation variant
---|---
VENTO inHOME Wi-Fi mini| VENTO inHOME Wi-Fi
Length of cartridge or fan and regenerator units [mm]| 162| 244
Hole diameter D [mm]| 120| 180
Minimum possible wall thickness when using AH, AH-10, AH-8, AH-11, PP 160, hoods [mm]| from 152| from 234
Minimum possible wall thickness when using an AH-S, hood [mm]| from 52| from 134

  1. Prepare a round core hole in the outer wall.
    The figure below shows the minimum distance from the hole to the surrounding objects.
    The hole diameter depends on the specific ventilator model. The corresponding values are given in the table.BLAUBERG VENTO Single Room Reversible Energy
Recovery Ventilator - Fig 1

  2. Insert the air duct in the wall. For ease of installation use the mounting wedges included in the delivery set. The air duct end must protrude for the distance A that enables installation of the outer ventilation hood. The overall dimensions of the outer ventilation hood, the outside protrusion length of the air duct A and the mounting sequence of the hood are stated in its installation instruction.BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Fig 2Install the air duct with the minimum slope of 3 mm downwards from the outer wall side.
    The air duct can be cut by calculating preliminary the required length or after fixing the air duct on the wall (in this case, it is necessary to have access to the outside part of the wall).

  3. Install the outer ventilation hood. The mounting sequence of the outer ventilation hood is described in the installation instruction for the ventilation hood.

  4. Stick the delivered cardboard master plate on the indoor wall using a mounting tape. The large opening in the master plate must be axially aligned with the air duct. Align the master plate horizontally with a building level.
    Then mark the fastening holes for installation of the supplied dowels and drill the holes to a required depth.
    Route the power cable from the wall through the marked opening on the template.BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator -
Fig 3

  5. Separate the front panel of the indoor unit from its back part. To do this, press the round buttons on the top and bottom of the indoor unit simultaneously, as shown on the left in the figure below.BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Fig 4

  6. Remove the three retaining screws from the controller cover to enable access to the terminals.
    Route the power wires through the appropriate cable glands.BLAUBERG VENTO
Single Room Reversible Energy Recovery Ventilator - Fig
5

  7. Fix the back part of the indoor unit on the wall with the screws supplied with the mounting kit of the ventilator.

  8. Route the power cable as figured below and connect the ventilator to power mains in compliance with the external wiring diagram, see section Connection to power mains. Secure the power cable with the clamp.BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Fig 7

  9. After completion of the electrical connection reinstall the left cover in site.

  10. Install the cartridge or the regenerator unit and the fan unit into the air duct as figured below and connect the connector to the board as shown by the arrow.BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Fig 9Insert the sound-absorbing layer in the air duct. Roll the layer of the sound absorbing material to match the air duct diameter. The protecting paper layer must be outside. Insert the sound absorbing roll into the cartridge against stop. Make a mark at the end of the air duct, remove the material and cut the roll as marked. Insert the ready sound absorbing roll into the air duct.

  11. Install the front panel of the indoor unit.

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Fig
11

CONNECTION TO POWER MAINS

The ventilator is rated for connection to single-phase AC 100-240 V/50 (60) Hz power mains.
For electric installations use insulated, flexible conductors (cables, wires) with the minimum cross section of 0.5 up to 0.75 mm2 for power cables and 0.25 mm2 for sensor cables. The cable cross section is given for reference only. The actual conductor cross-section selection must be based on its type, maximum permissible heating, insulation, length and installation method.
Use copper wires for all the electric connections!
Connect the unit to power mains via the terminal block installed in the controller board in compliance with the wiring diagram and terminal designation.
Connect the unit to power mains through the external automatic switch with a magnetic trip integrated into the fixed wiring system.
The tripping current of the circuit breaker is selected based on the electrical characteristics shown on the label of the fan casing. The ventilator design enables connecting any external controls with a normally opened contact (NO contact), such as an external CO2 sensor, a humidity sensor, a switch, etc.
When the NO contact of the external device is closed, the unit changes to the maximum speed.
An analogue sensor with output voltage 0-10 V is also compatible with the unit.

EXTERNAL CONNECTIONS DIAGRAM

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Fig
12

*The circuit breaker is not included in the delivery set.

PRE-SETTING OF THE VENTILATOR

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Fig
13

Prior to operating the ventilator set it up using the DIP switch. It is located on the controller circuit board. To access the DIP switch, take off the front panel of the indoor unit and uplift the rubber plug that covers the switch.

DIP SWITCH POSITIONS
Defining the role of the ventilator when operating in a group

| 1| ON – slave unit (hereinafter referred to as “Slave unit”)
---|---|---
| 1| OFF – master unit (hereinafter referred to as “Master unit”)

Standby mode setup

| 2| Min – the ventilator operates at Speed I in the Standby mode.
---|---|---
| 2| OFF – the ventilator is switched off in the Standby mode.

**Setting of the fan rotation direction***

| 3| ON – in the Ventilation mode the ventilator supplies the air to the room.
in Regeneration mode the ventilator starts operating first in supply mode.
---|---|---
| 3| OFF – in the Ventilation mode the ventilator extracts the air from the room.
in Regeneration mode the ventilator starts operating first in extract mode.

Restore factory default settings

| 4| ON – restore factory default settings. To do this, when the ventilator is running, turn the switch to the ON position, after the sound signal, turn the switch to the OFF position.
---|---|---
| 4| OFF – standard operation of the unit.

*It is recommended to use either one or an even number of ventilators combined into a group to ensure an optimal ventilation mode.
The setting is carried out in such a way that during each operation interval one half of the ventilators supplies air to the room, and the other half extracts air out of the room.

The figure below shows the control buttons on the indoor unit and the remote control with a brief description of their function.

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Fig
14

VENTILATOR CONTROL WITH THE BUTTONS ON THE INDOOR UNIT
The table below shows the buttons and indicators on the indoor ventilator unit with a detailed description of their purpose and functionality.

| The speed selection sequence is follows: I-II-III-Standby. All ventilators combined into one network run at the speed set by the master ventilator.
I : permanent indicator glowing indicates operation of the unit at Speed I. Indicator blinking indicates activation of the Night mode timer.
I and II : permanent glowing of the indicators I and II indicates operation of the unit at Speed II.
I , II and III : permanent glowing of the indicators I, II and III indicates operation of the ventilation unit at Speed III. Synchronous blinking of the indicators I, II and III indicates activation of the timer in Party mode or the turn-off delay timer in the Boost mode in case of actuation of the connected external sensors or the integrated humidity sensor.
Alternate blinking of the indicators I, II and III indicates that the ventilator runs at the speed set with the mobile application using the slider selector for manual speed setting or that the Weekly Schedule mode is activated.
---|---
| Regeneration mode
The rotation direction of both fans changes to opposite every 70 seconds. Heat recovery is performed in this mode. To enable reverse phase operation of the ventilators, change the position of the DIP switch No. 3.
| Ventilation mode
The ventilator operates in the supply or extraction mode at a set speed. The direction of air flow depends on the position of the DIP switch 3.
No glowing of the indicators « Regeneration » and « Ventilation » indicates forced operation of the ventilation unit in the air supply mode. This mode may be activated only via the mobile application.
Filter| 90 days after installation of the cartridge the filter replacement indicator starts glowing. In this case, clean or replace the filters (see section Technical maintenance).
After replacement of the filters reset the timer using the mobile application or by pressing and holding the button on the Master ventilator indoor unit for 5 seconds until a signal sounds.
Alarm| Alarm indicator. In case of failure, the Alarm indicator on the indoor unit glows or blinks. Reasons of Alarm blinking:
• Battery charge is below the low level.
• No communication between the master ventilator and the router;
• Alarm shutdown of the ventilator.
If several ventilators are running in a group, in the event of an emergency stop of one ventilator, all the ventilators in the same group will stop (the Alarm indicator on the faulty ventilator will blink, while this indicator on the other ventilators will remain lit).
If the master ventilator does not communicate with the router for 20 seconds or more, the ventilator will switch to Standby mode (the Alarm indicator will blink), and the slave ventilators will signal that they are not communicating with the master ventilator (see the description of the Master indicator). When communication is restored, the slave ventilators automatically synchronise with the master ventilator.
Master| Continuously lit indicator light indicates the master ventilator in the group ( Master ).
Blinking indicates that the ventilator is a slave ventilator and that there is no communication with the master ventilator.
If the indicator is not lit it means that this ventilator is a slave ventilator and is paired with a Master ventilator.
Synchronous blinking of all the indicators on the casing of the ventilator indicates that the Setup mode is enabled.

REMOTE CONTROL OF THE VENTILATOR
The table below shows the buttons on the remote control with a detailed description of their purpose and functionality.

| ON/Standby. The Standby mode depends on the position of the DIP switch 2 (see section DIP switch positions). The same button is used to reset alarms ( Alarm ) and to turn off the timers.
---|---
| Ventilator speed selection: Speed III-II-I respectively.
| Regeneration mode
The rotation direction of both fans changes to opposite every 70 seconds. Heat recovery is performed in this mode. The fan rotation direction depends on the position of the DIP switch 3.
| Ventilation mode
The ventilator operates in the supply or extraction mode at a set speed. The fan rotation direction depends on the position of the DIP switch 3.
| Timer control buttons:
Party mode: the timer activates operation of the unit at Speed III for a set time period, 4 hours by default. The timer setting may be changed during setup of the unit on mobile device.
Night mode: the timer activates operation of the ventilation unit at Speed I for a set time period, 8 hours by default. The timer setting may be changed during setup of the unit on mobile device.
The ventilation unit reverts to operation with a previous speed setting upon elapse of the set time period. Press any speed setting key to deactivate the timer or press the timer control button once again.

VENTILATION UNIT OPERATION WITH THE MOBILE APPLICATION BLAUBERG HOME
Download the Blauberg Home application and install it on the mobile device.

Blauberg Home on the App Store (apple.com)| Blauberg Home – Apps on Google Play
---|---
BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - QR Code
1|

The ventilator with the factory settings operates as a Wi-Fi access point with the name FAN: + 16 characters of the ID number indicated on the device casing under the front panel.
Wi-Fi access point password: 11111111.
Follow the instructions in the mobile app to connect the device. The app allows configuring the ventilator to connect via your home Wi-Fi network and via a cloud server.

CONTROLLING THE VENTILATOR USING THE SMART HOME SYSTEM
The ventilators are connected to the Smart Home system in accordance with the user manual for connecting to the Smart Home system.

WIRELESS CONNECTION OF SEVERAL VENTILATORS
Ventilators can be combined into a group in which one ventilator shall act as the master and the others shall be connected to it as slaves.
If the ventilator is a master ventilator, the slave ventilators and mobile devices connect to it via Wi-Fi. The master ventilator is controlled using a mobile device, remote control or touch buttons on the ventilator casing. The control signal is automatically  transmitted to the slave ventilators. In this mode, the device receives signals from sensors (humidity sensor, external discrete sensor, external 0-10 V analogue sensor) and switches to the appropriate operating mode.
If the ventilator is a slave, it only receives control signals from the master ventilator. All other signals from other control devices are ignored. In this mode the units ignore any other signals from the sensors. In case there is no connection to the master ventilator for more than 20 seconds, the ventilator shall automatically switch to Standby mode.
Sensor-based operation
The ventilator shall only respond to sensor signals when they are acting as a master ventilator.
If any of the sensors is triggered, all ventilators in the group will reach maximum speed.

VENTILATOR WIRELESS CONNECTION DIAGRAMS
Wiring diagram 1

Connection of up to 8 Slave units or mobile devices to the Master unit with its own wireless access point.
In case of connection of 8 Slave units to the Master unit with its own wireless access point a mobile device may not be connected.

Wiring diagram 2
The Master units, the Slave units and the mobile devices are connected to a wireless access point of the Wi-Fi router. In this case, the Master unit can operate with the number (N) of Slave units, limited by the technical characteristics of the router.

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Wiring
diagram 2

If the Wi-Fi router capacity is not enough to connect a required number of the units, you may use an extra wireless access point to connect the other the unit. Several Master units can optionally be connected to the network for arranging a zone control.

BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Wiring
diagram 3

RECOVERY SETUP MODE
In the event of losing the Wi-Fi password or the master ventilator password or in other cases use the recovery Setup mode to restore access to the ventilator functions.
To enter the special Setup mode, press and hold the Ventilation button on the ventilator casing for 5 seconds until the beep and blinking of all the LED lights. The ventilator will stay in this mode for 3 minutes, after which it will automatically return to the previous  settings. To exit the Setup mode immediately, press and hold the Ventilation button on the ventilator casing once again for 5 seconds until the beep and shutdown of all the LED lights.

In this mode the following settings are available for the master ventilator:

  • Wi-Fi name: Setup mode.
  • Wi-Fi password: 11111111.
  • The unit password is ignored.

WHEN SETTING UP THE CONNECTION OF THE DEVICES, IT IS NECESSARY THAT ALL SLAVE VENTILATORS ARE WITHIN THE WI-FI COVERAGE AREA OF THE MASTER VENTILATOR.
AFTER CHANGING THE WI-FI PARAMETERS OF THE MASTER VENTILATOR, RECONNECT THE VENTILATORS

CONNECTING MASTER AND SLAVE VENTILATORS
Follow these steps to create a group of ventilators that are linked as master and slave ventilators:

  • Set the DIP switches on each ventilator to the position that corresponds to its role in the group (see «Position of the DIP switch»).
  • Next, configure the Wi-Fi settings of the master ventilator by following the instructions in the Blauberg Home mobile app.
  • Set the master ventilator to the special mode as described above, and all LEDs on the ventilator casing will flash. Repeat the same procedure with the slave ventilators and wait until the slave ventilators beep and the LEDs stop flashing. Switch the master to normal mode. Press and hold the Ventilation button . Wait for the beep when all the LEDs stop blinking. unit back

Note: If you have multiple Wi-Fi access points connected to your home router and you want to connect some of the ventilators to one access point and some to another, then

  • Connect the Master unit to the first Wi-Fi access point.
  • Complete the connection with the first group of Slave units.
  • Connect the Master unit to the second Wi-Fi access point.
  • Complete the connection with the second group of Slave units.

BATTERY REPLACEMENT
The Alarm indicator on the unit casing will blink when the battery is approaching the end of its life.
The mobile app will also display the warning and show the following message on pressing the indicator icon.
Low battery power may cause disruptions in the weekly schedule operation. Power off the unit before replacing the battery. After replacing the battery reset the time and date.

The battery is located on the A1 control board. To replace the battery, power off the ventilator, remove the front panel and the cover protecting the control circuit board. Then remove the battery and install a new one.
The battery type CR1220.

TECHNICAL MAINTENANCE

DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
MAKE SURE THE UNIT IS DISCONNECTED FROM POWER MAINS BEFORE REMOVING THE PROTECTION

Maintenance of the ventilator means regular cleaning of the ventilator surfaces of dust and cleaning and replacement of the filters. To enable access to the main units, follow the procedure described below. The ventilator must be previously turned off using the remote control or the buttons on the indoor unit. Then turn off power supply completely.

  1. Remove the front panel of the indoor control unit as shown in section 5 Installation and Set-up.BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Fig 15

  2. Disconnect the connector from the circuit board. Do not remove the connector by pulling the wires. Use a flat screwdriver to uplift it, if required.BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Fig 16

  3. Remove the sound-insulation material from the duct, then remove the cartridge or the fan unit and the regenerator unit.BLAUBERG VENTO Single Room Reversible Energy Recovery Ventilator - Fig 17

  4. Clean filters once they become dirty. Upon elapse of the set number of days the filter replacement indicator (Filter) starts glowing.
    Depending on the dustiness of the air, the duration of the ventilator operation until the next filter cleaning may be different. The duration of the period when the filter replacement indicator is turned on can be set using the mobile application in the range from 70 to 365 days of continuous operation (by default, the Manufacturer’s recommended value is set to 90 days).
    • Reset the filter timer using the application on your mobile device or using the button on the indoor unit of the ventilator, as described in the VENTILATOR CONTROL WITH THE BUTTONS ON THE INDOOR UNIT section.
    • Wash the filters and let those dry out completely.
    • Install the dry filters in their place and assemble the unit in the reverse order.
    • Cleaning with a vacuum cleaner is permitted.
    • The filter rated service life is 3 years.BLAUBERG VENTO Single Room
Reversible Energy Recovery Ventilator - Fig 18• Some dust may accumulate on the heat exchanger block even in case of regular maintenance of the filters.
    • Clean the regenerator regularly to ensure its high heat recovery efficiency.
    • Vacuum clean the regenerator not less than once a year.

  5. Replacement of the remote control battery (if necessary).
    In case of a long operation of the remote control the battery must be replaced.
    No response of the unit for pressing the remote control buttons indicates the need to replace the battery.
    The battery type is CR2025.
    Remove the holder with the battery from the lower part of the remote control.
    Replace the battery and install the holder with a new battery back to the remote control.

POSSIBLE FAULTS AND TROUBLESHOOTING

Problem Possible reasons Troubleshooting
When switching on the ventilator, the fan does not start. No power supply.

Make sure the power supply line is connected correctly, otherwise troubleshoot the connection error.
The motor is jammed, the impeller blades are clogged.| Turn the ventilator off. Troubleshoot the motor jam and impeller clogging. Clean the blades. Turn the ventilator on.
Circuit breaker tripping during the ventilation unit start-up.| Overcurrent as a result of short circuit in the electric circuit.| Turn the ventilator off.
Contact the Seller for further information.
Low air flow.| Low set fan speed.| Set higher speed.
The filters, the fan or the regenerator is clogged.| Clean or replace the filter. Clean the fan and the heat exchanger.
Increased noise, vibration.| The impeller is clogged.| Clean the impeller.
Loose screw connection of the unit casing or the outer ventilation hood.| Tighten the screws of the ventilator or the outer ventilation hood.

STORAGE AND TRANSPORTATION REGULATIONS

  • Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 °C to + 40 °C and relative humidity up to 70 %.
  • Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
  • Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
  • Follow the handling requirements applicable for the particular type of cargo.
  • The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
  • Avoid sharp blows, scratches, or rough handling during loading and unloading.
  • Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.

MANUFACTURER’S WARRANTY

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.

The warranty repair does not include:

  • routine technical maintenance
  • unit installation/dismantling
  • unit setup

To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for  warranty service.

The manufacturer’s warranty does not apply to the following cases:

  • User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
  • Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
  • User’s failure to ensure timely technical maintenance of the unit.
  • External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
  • Redesign or engineering changes to the unit.
  • Replacement and use of any assemblies, parts and components not approved by the manufacturer.
  • Unit misuse.
  • Violation of the unit installation regulations by the user.
  • Violation of the unit control regulations by the user.
  • Unit connection to power mains with a voltage different from the one stated in the user’s manual.
  • Unit breakdown due to voltage surges in power mains.
  • Discretionary repair of the unit by the user.
  • Unit repair by any persons without the manufacturer’s authorization.
  • Expiration of the unit warranty period.
  • Violation of the unit transportation regulations by the user.
  • Violation of the unit storage regulations by the user.
  • Wrongful actions against the unit committed by third parties.
  • Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
  • Missing seals if provided by the user’s manual.
  • Failure to submit the user’s manual with the unit purchase date stamp.
  • Missing payment paperwork certifying the unit purchase.

READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP

CERTIFICATE OF ACCEPTANCE

Unit Type Single-room reversible energy recovery ventilator
Model
Serial Number
Manufacture Date
Quality Inspector’s Stamp

SELLER INFORMATION

Seller|
---|---
Address|
Phone Number|
E-mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|

INSTALLATION CERTIFICATE

The __ unit is installed pursuant to the requirements stated in the present user’s manual.

Company name|
Address|
Phone Number|
Installation Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:|

WARRANTY CARD

Unit Type Single-room reversible energy recovery ventilator