BLAUBERG ECSB250L Komfort Air Handling Unit User Manual
SAFETY REQUIREMENTS
All user’s manual requirements as well as the provisions of all the applicable
local and national
construction, electrical, and technical norms and standards must be observed
when installing
and operating the unit
Disconnect the unit from the power supply prior to any connection, servicing,
maintenance, and
repair operations
Only qualified electricians with a work permit for electrical units up to 1000
V are allowed for installation. The present user’s manual should be carefully
read before beginning works
Check the unit for any visible damage of the impeller, the casing, and the
grille before starting
installation. The casing internals must be free of any foreign objects that
can damage the impeller blades
While mounting the unit, avoid compression of the casing! Deformation of the
casing may result
in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.)
Transported air must not contain any dust or other solid impurities, sticky
substances, or fibrous
materials.
Do not use the unit in a hazardous or explosive environment containing
spirits, gasoline, insecticides, etc
Do not close or block the intake or extract vents in order to ensure the
efficient air flow. Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the
document’s preparation. The Company reserves the right to modify the technical
characteristics, design, or configuration of its products at any time in order
to incorporate the latest technological developments.
KOMFORT EC SB(E) 250(-E) L/R
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
This unit is not intended for use by persons (including children) with reduced
physical, sensory
or mental capabilities, or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the unit by a person
responsible for their safety. Children should be supervised to ensure that
they do not play with the unit.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent, or similarly qualified persons in order to avoid a safety
hazard.
If the cord set is damaged, it must be replaced by a special cord set
available from the manufacturer or its service agent.
Precautions must be taken to avoid the back-flow of gases into the room from
the open flue of gas or other fuel-burning appliances.
Ensure that the unit is switched off from the supply mains before removing the guard.
PURPOSE
The unit is designed to ensure continuous mechanical air exchange in offices,
hotels, cafés, conference halls, and other public spaces as well as to recover
the heat energy contained in the air extracted from the premises to warm up
the filtered stream of supply air The unit is not intended for organizing
ventilation in swimming pools, saunas, greenhouses, summer gardens, and other
spaces with high humidity.
Due to the ability to save heating energy by means of energy recovery, the
unit is an important element of energy-efficient premises. The unit is a
component part and is not designed for stand-alone operation. It is rated for
continuous operation. Transported air must not contain any flammable or
explosive mixtures, evaporation of chemicals, sticky substances, fibrous
materials, coarse dust, soot and oil particles or environments favorable for
the formation of hazardous substances (toxic substances, dust, pathogenic
germs).
DELIVERY SET
Name | Number |
---|---|
Air handling unit | 1 |
User’s manual | 1 |
Control panel* | 1 |
Packing box | 1 |
*The control panel is not included in the delivery set of units with an S21 controller.
DESIGNATION KEY
TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature
ranging from +1 °C up to +40 °C and relative humidity up to 60% without
condensation. In cold, damp rooms, there is a possibility of freezing or
condensation inside and outside the casing. In order to prevent condensation
on the internal walls of the unit, it is necessary that the surface
temperature of the casing is 2-3 °C above the dew point temperature of the
transported air.
The unit should be operated continuously, and in cases where ventilation is
not necessary, reduce the air flow of the fans to a minimum (20%). This will
ensure a favorable indoor climate and reduce the amount of condensation inside
the unit, which can damage electronic components. Never use the unit for
dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance
Hazardous parts access and water ingress protection rating
IP20 for the unit connected to the air ducts.
IP44 for the unit motors.
The unit design is constantly being improved, thus some models may be slightly
different from those described in this manual.
MODEL| KOMFORT EC SB 250 L/R| KOMFORT EC SB 250-E L/R|
KOMFORT EC SBE 250 L/R| KOMFORT EC SBE 250-E L/R
---|---|---|---|---
Supply voltage, 50 (60) Hz [V]| 1~ 230
Maximum fan power [W]| 180
Maximum unit current (without a heater) [A]| 1.37
Maximum electric heater power [W]| —| 1400
Maximum electric heater current [A]| —| 6.09
Maximum air flow [m3/h]| 390
RPM [min-1]| 2600
Sound pressure level at 3 m distance [dBA]| 35
Transported air temperature [°С]| -25…+40
Casing material| Painted steel
Insulation, mineral wool [mm]| 30
Filtering class of the extract filter| G4
Filtering class of the supply filter| G4 (optionally F7)
Connected air duct diameter [mm]| 160
Weight [kg]| 66
Heat recovery efficiency [%]| 88-95| 78-90| 88-95| 78-90
Heat exchanger type| Counter-flow
Heat exchanger material| Polystyrene| Enthalpy| Polystyrene| Enthalpy
SEC class| A+| A| A+| A
Dimansation
KOMFORT EC SB(E) 250(-E) L
KOMFORT EC SB(E) 250(-E) R
Model | Dimensions [mm] |
---|---|
H1 | A1 |
KOMFORT EC SB(E) 250(-E) L | 1094 |
9 | 160 |
KOMFORT EC SB(E) 250(-E) R | 320 |
DESIGN AND OPERATING PRINCIPLE
The unit has the following operating logic: warm stale extract air from the room flows into the unit, where it is filtered by the extract filter, then air flows through the heat exchanger and is exhausted outside by the exhaust fan. Cold fresh air from the outside flows into the unit, where it is cleaned by the supply filter. Then the air flows through the heat exchanger and is directed to the room with the supply fan. Heat energy of warm extract air is transferred to clean intake fresh air from the outside and warms it up. The air flows are fully separated while flowing through the heat exchanger. Heat recovery minimizes heat losses, which reduces the cost of space heating in the cold season.
KOMFORT EC SB(E) 250(-E) L
KOMFORT EC SB(E) 250(-E) R
SETUP MODE button (for the units with an S21 automation) 2 – control unit 3 – fan unit 4 – counter-flow heat exchanger 5 – supply filter 6 – extract filter 7 – bypass damper 8 – electric heater (only for KOMFORT EC SBE 250(-E) L/R units) 9 – drain pipe 10 – humidity sensor (optional)
The air handling unit is equipped with a front service panel for repair and
maintenance operations. The control unit is accessible for installation and
wiring operations through the inspection door on top of the unit. The power
cable and ground cable are connected to the control unit via the electric
lead-ins
The bypass damper is open or closed depending on operation mode of the unit.
During the operation of KOMFORT EC SB(E) 250 L/R units the difference between
the supply and extract air flow temperature leads to condensate generation.
Condensate is collected in the drain pan and is removed outside through the
drain pipe. The KOMFORT EC SB(E) 250-E L/R units are equipped with an enthalpy
heat exchanger and do not require condensate drainage
Accessories for the unit are available on a separate order.
-
Humidity sensor.
The unit with an installed humidity sensor maintains a set indoor humidity level. As the extract air humidity rises above the set point, the system automatically switches to the maximum speed. As the humidity drops down below the set point the unit returns to the previous mode -
CO2 sensor (connected to the controller).
Measures the level of concentration of carbon dioxide in the room and generates a signal that controls the performance of the fan. Air flow control based on CO2 concentration is an efficient energy saving solution. -
OC sensor (connected to the controller).
Qualitative assessment of air saturation with contaminants (cigarette smoke, exhaled air, solvent and detergent vapors). The sensor sensitivity can be adjusted with regards to the expected maximum level of air pollution. Enables on demand ventilation which results in considerable energy savings as air is exchanged only upon reaching the preset level of pollution. -
ENH duct heater for supply air reheating.
The heater maintains the room temperature set by the user. Heater installation and connection to the unit are described in the heater user’s manual.
RIGHT-HANDED AND LEFT-HANDED MODIFICATIONS
The figure below shows the arrangement of spigots for left- and right-handed modifications. Choosing the right arrangement can improve the ease of installation, shorten the length of the ducts and reduce the number of air duct bends.
KOMFORT EC SB(E) 250(-E) L
KOMFORT EC SB(E) 250(-E) R
UNIT OPERATION LOGIC
Heat recovery
Air from the room flows into the unit, where it is filtered by the extract
filter, then air flows through the heat exchanger and is exhausted outside by
the exhaust fan. Air from outside flows into the unit, where it is cleaned in
the intake filter. Then the air flows through the heat exchanger and is
directed to the room with the supply fan. Supply air is heated in the heat
exchanger by transferring the heat energy of warm and humid extract air to the
cold fresh air. The air flows are fully separated while flowing through the
heat exchanger. Heat recovery minimizes heat losses, which reduces the cost of
space heating in the cold season
Summer Cooling mode
The bypass damper is opened, the extract air that is removed from the premises
bypasses the heat exchanger. The temperature of the air is not changed after
passing through the heat exchanger.
Freeze protection
A freezing danger appears, if the exhaust air temperature downstream of the
heat exchanger is below +5 °C and the intake air temperature upstream of the
heat exchanger is below -3 °C for the units with an electric heater and when
the exhaust air temperature downstream of the heat exchanger is below +3 °C
for the units without an electric heater.
In the KOMFORT EC SBE 250(-E) L/R S14 units, when there is a risk of freezing,
the supply fan is switched off. After the temperature increase, the unit
returns to the previous mode. Three modes of freeze protection are available
in the KOMFORT EC SBE 250(-E) L/R S21 units-periodically the supply fan is
turned off with the bypass-with the electric preheater (if the unit is
equipped with a preheater)
Mode selection and settings are described in the 521 control system user’s
manual.
MOUNTING AND SET-UP
READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.
To attain the best performance of the unit and to minimise turbulence-induced air pressure losses, connect the straight air duct section to the spigots on both sides of the unit while mounting
Minimum straight air duct length:
- equal to 1 air duct diameter on the intake side
- equal to 3 air duct diameters on outlet side
If the air ducts are too short or not connected, protect the unit parts from ingress of foreign objects. To prevent uncontrollable access to the fans, the spigots may be covered with a protecting grille or other protecting device with mesh width not more than 12.5 mm. When choosing the unit installation location, it is necessary to provide free access to the hinged panel for technical and service maintenance.
The air ducts must be slipped over the unit flanges until tight. Flexible air
ducts must be rigidly fixed with a metal worm clamp.
he unit must be mounted strictly horizontally in the longitudinal and transverse planes. Failure to do so will cause the unit casing distortion and may prevent proper operation
Humidity sensor installation
The humidity sensor is not included in the delivery set and must be purchased
separately. For ease of installation, it is recommended to remove the filter
and the heat exchanger.
Connect the sensor connector to the connector with the cable from the control
unit. Fasten the sensor with the screw on the threaded rivet.
Unit floor mounting
Install the unit on the pre-mounted floor supports, minimum 150 mm height, to
ensure sufficient access for the drain pipe connection to the U-trap and for
condensate drain system installation.
Rotate the adjustable feet to achieve a strictly horizontal unit position.
Unit wall mounting
Dowels for wall mounting are not included in the delivery set and should be
ordered separately.
While choosing dowels consider the material of the mounting surface as well as
the weigh of the unit, refer to the “Technical data”section Dowels for unit
mounting should be selected by a qualified specialist.
Insert the dawel into the wall..
The delivery set includes fastening angles for fixing the unit in earthquake-
prone areas.
Unscrew the feet.
Direct mounting on the wall
Prepare holes in the wall and insert dowels.
Mounting with a bracket
Prepare holes in the wall and insert dowels. Attach the mounting bracket with
the screws.
Install the fastening angles to secure the unit in earthquake-prone areas.
Fix the unit to the wall with screws and screw the feet through the holes in
the angles.
Hang the unit on the bracket and screw the feet through the holes in the
angles.
CONDENSATE DRAINAGE
Condensate drainage is required for the KOMFORT EC SB(E) 250 L/R unit series.
The hole for the drain pipe is at the bottom of the unit. Remove the plug from
the hole in the unit. Install the drain pipe from the delivery set into the
hole
To ensure tightness, it is recommended to apply a sanitary sealarit to the
surfaces to be joined. Connect the drain pipe to the drainage system using a
U-trap kit (available separately)
The U-trap must be constantly filled with water. The pipe slope downwards must
be at least 3″.
1 – drain pipe 2 – U-trap 3 – connecting pipe 4 – sewage system
CONNECTION TO POWER MAINS
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT. THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN. THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
To access the control unit, remove the fixing screws and remove the cover. The
control unit contains a terminal block and a controller for connecting
external devices.
EXTERNAL CONNECTIONS DIAGRAM FOR THE KOMFORT EC SB(E) 250(-E) L/R S14
Designation | Name | Wire | Model | Note |
---|---|---|---|---|
SM1* | Supply air damper actuator | 2 x 0.75 | ||
SM2* | Extract air damper actuator | 2 x 0.75 | ||
РК1* | Contact from fire alarm panel | 2 x 0.75 | NC | Remove the jumper |
CO2* | CO2 sensor | 2 x 0.75 | NO | |
Р1 | External control panel | 4 x 0.25 |
EXTERNAL CONNECTIONS DIAGRAM FOR THE KOMFORT EC SB(E) 250(-E) L/R S21 UNITS
Designation | Name | Cable type | Model | Note |
---|---|---|---|---|
SM1 | Supply air damper actuator | 2 x 0.75 | NO | 3 A, 30VDC/~250 AC |
SM2 | Exhaust air damper actuator | 2 x 0.75 | NO | 3 A, 30VDC/~250 AC |
РК1 | Contact from fire alarm panel | 2 x 0.75 | NC | Remove the jumper |
Р1 | External control panel | 4 x 0.5 | ||
ENH | Duct heater for reheating | 4 x 0.5 | ||
ENH RT2** | Duct temperature sensor | 2 x 0.25 | Remove the jumper |
*The supply voltage of the SM1, SM2 external dampers is selected depending on the type of dampers.
**Part of ENH.
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
MAKE SURE THE UNIT IS DISCONNECTED FROM POWER MAINS BEFORE REMOVING THE PROTECTION
Maintenance operations of the unit are required 3-4 times per year. They include general cleaning of the unit and the following operations:
-
Filter maintenance (3-4 times per year).
Dirty filters increase air resistance in the system and reduce supply air volume. The filters require cleaning not less than 3-4 times per year. Clean the filter with a vacuum cleaner or replace it with a new one. For new filters contact the Seller. To access the filters, unscrew the thumbscrews and remove the service panels. -
Heat exchanger maintenance (once per year).
Some dust may accumulate on the heat exchanger even in case of regular maintenance of the filters. To maintain high heat recovery efficiency, regular cleaning is required. To clean the heat exchanger, remove it from the unit and clean the heat exchanger by using compressed air or a vacuum cleaner. Remove the service panel and take it out of the unit for the heat exchanger service operations
-
Fan maintenance (once per year).
Even in case of regular maintenance of the filters, some dust may accumulate inside the fans and reduce the fan performance and supply air flow. Fans should be cleaned selected by the service technician -
Condensate drainage system maintenance (4 times per year).
The condensate drainage (drain line) may get clogged by dirt and dust particles contained in the exhaust air. Check the drain line operation by filling the drain pan under the unit with water, clean the U-trap and the drain line, if necessary -
Supply air flow control (twice per year).
The supply duct grille may get clogged with leaves and other objects reducing the unit performance and supply air delivery. Check the supply grille twice per year and clean it as required. -
Ductwork system maintenance (once in 5 years).
Even regular fulfilling of all the maintenance operations prescribed above may not completely prevent dirt accumulation in the air ducts, which leads to air pollution and reduces the unit capacity. Duct maintenance means regular cleaning or replacement.
TROUBLESHOOTING
IF UNIDENTIFIED NOISES OR ODOURS SHOULD ARISE AND IN CASE OF DEFORMATION OF ELEMENTS, VIBRATION, TERMINATION OF AIR SUPPLY/EXTRACTION OR REDUCED SYSTEM PERFORMANCE, IMMEDIATELY DISCONNECT THE UNIT FROM POWER SUPPLY AND CONTACT THE SELLER FOR THE VENTILATION SYSTEM DIAGNOSTICS DIAGNOSTICS MUST BE CARRIED OUT BY QUALIFIED SPECIALISTS
.POSSIBLE MALFUNCTIONS AND TROUBLESHOOTING
Problem | Possible reasons | Troubleshooting |
---|---|---|
**** The fan(s) does (do) not start when the unit is on. | No power supply. |
Make sure the power supply line is connected correctly, otherwise troubleshoot
a connection error.
The mode in which the fans are turned off is set.| Change the mode
with the help of the control panel.
**** Low air flow.| Low set fan speed.| Set higher speed.
The filters and the fans are clogged, the heat exchanger is clogged.| Clean or
replace the filters, clean the fans, and the heat exchanger.
Ventilation system elements (air ducts, diffusers, louver shutters, grilles)
are clogged, damaged or closed.| Clean or replace the ventilation system
elements, such as air ducts, diffusers, louvre shutters, grilles.
Cold supply air.| The extract filter is soiled.| Clean or replace the extract
filter.
Noise, vibration.| The fan or casing screw connection is loose.| Tighten
the screw connection of the fans or the casing.
No anti-vibration connectors on air duct pipe flanges.| Install anti-vibration
connectors.
Water leakage(only forKOMFORT EC SB(E) 250 L/Reknits)| The drainage
system is soiled, damaged, or installed incorrectly.| Clean the drain
line.Check the drain line slope angle. Make sure that the U-trap is filled
with water and the drain pipes are frost protected.
If troubleshooting steps have failed, contact the Seller of the product.
In case of faults not described in the table, contact the Seller for further information.
STORAGE AND TRANSPORTATION REGULATIONS
-
Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range +5.+40 °C and relative humidity up to 70%.
-
Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
-
Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit
-
Follow the handling requirements applicable for the particular type of cargo
-
The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and
mechanical damage. The unit must be transported only in the working position. -
Avoid sharp blows, scratches, or rough handling during loading and unloading
-
Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above. The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE- FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP.
CERTIFICATE OF ACCEPTANCE
Unit Type | Air handling unit |
---|---|
Model | |
Serial Number | |
Manufacture Date | |
Quality Inspector’s Stamp |
SELLER INFORMATION
Seller|
---|---
Address|
Phone Number|
E-mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s
manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|
Seller’s Stamp
INSTALLATION CERTIFICATE
The unit __ is installed pursuant to the requirements stated in the present user’s manual.
Company name|
Address|
Phone Number|
Installation Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the
applicable local and national construction, electrical and technical codes and
standards. The unit operates normally as intended by the manufacturer.
Signature:|
Installation Stamp
WARRANTY CARD
Unit Type | Air handling unit |
---|---|
Model | |
Serial Number | |
Manufacture Date | |
Purchase Date | |
Warranty Period | |
Seller |
Seller’s Stamp