BLAUBERG KOMFORT Ultra L 250-H Heat Recovery Air Handling Unit User Manual
- May 15, 2024
- BLAUBERG
Table of Contents
- KOMFORT Ultra L 250-H Heat Recovery Air Handling Unit
- SAFETY REQUIREMENTS
- PURPOSE
- DELIVERY SET
- DESIGNATION KEY
- TECHNICAL DATA
- DESIGN AND OPERATING LOGIC
- INSTALLATION AND SET-UP
- CONNECTION TO POWER MAINS
- TECHNICAL MAINTENANCE
- TROUBLESHOOTING
- STORAGE AND TRANSPORTATION REGULATIONS
- MANUFACTURER’S WARRANTY
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Heat recovery air Handling unit
KOMFORT Ultra L 250-H
KOMFORT Ultra S 250-H
KOMFORT Ultra L 250-E
KOMFORT Ultra S 250-E
USER’S MANUAL
KOMFORT Ultra L 250-H Heat Recovery Air Handling Unit
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about purpose, technical details, operating
principle, design, and installation of the KOMFORT Ultra S/L 250-H/E unit and
all its modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
The information in this user’s manual is correct at the time of the document’s
preparation.
The Company reserves the right to modify the technical characteristics,
design, or configuration of its products at any time in order to incorporate
the latest technological developments.
No part of this publication may be reproduced, stored in a retrieval system,
or transmitted, in any form or by any means in any information search system
or translated into any language in any form without the prior written
permission of the Company.
SAFETY REQUIREMENTS
- Please read the user’s manual carefully prior to installing and operating the unit.
- All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
- The warnings contained in the user’s manual must be considered most seriously since they contain vital personal safety information.
- Failure to follow the rules and safety precautions noted in this user’s manual may result in an injury or unit damage.
- After a careful reading of the manual, keep it for the entire service life of the unit.
- While transferring the unit control, the user’s manual must be turned over to the receiving operator.
UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS
- Disconnect the unit from power mains prior to any installation operations.
- The unit must be grounded!
- Do not change the power cable length at your own discretion.
- Do not bend the power cable.
- Avoid damaging the power cable.
- Do not put any foreign objects on the power cable.
- Do not use damaged equipment or cables when connecting the unit to power mains.
- Do not touch the unit controls with wet hands.
- Do not carry out the installation and maintenance operations with wet hands.
- Unpack the unit with care.
- While installing the unit, follow the safety regulations specific to the use of electric tools.
- Do not lay the power cable of the unit in close proximity to heating equipment.
- Do not operate the unit outside the temperature range stated in the user’s manual.
- Do not operate the unit in aggressive or explosive environments.
- Do not wash the unit with water.
- Protect the electric parts of the unit against ingress of water.
- Do not allow children to operate the unit.
- Do not store any explosive or highly flammable substances in close proximity to the unit.
- Do not open the unit during operation.
- Do not block the air duct when the unit is switched on.
- Do not sit on the unit and avoid placing foreign objects on it.
- Disconnect the unit from power mains prior to any technical maintenance.
- When the unit generates unusual sounds, odour, or emits smoke, disconnect it from power supply and contact the Seller.
- Do not direct the air flow produced by the unit towards open flame or ignition sources.
- In case of continuous operation of the unit, periodically check the security of mounting.
- Use the unit only for its intended purpose.
**** THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
PURPOSE
The unit is designed to ensure continuous mechanical air exchange in houses,
offices, hotels, cafes, conference halls, and other utility and public spaces
as well as to recover the heat energy contained in the air extracted from the
premises to warm up the filtered stream of intake air.
The unit is not intended for organizing ventilation in swimming pools, saunas,
greenhouses, summer gardens, and other spaces with high humidity.
Due to the ability to save heating energy by means of energy recovery, the
unit is an important element of energy-efficient premises.
The unit is a component part and is not designed for stand-alone operation. It
is rated for continuous operation.
Transported air must not contain any flammable or explosive mixtures,
evaporation of chemicals, sticky substances, fibrous materials, coarse dust,
soot and oil particles or environments favourable for the formation of
hazardous substances (toxic substances, dust, pathogenic germs).
THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL,
MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE TRAINING.
THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL
AFTER THE APPROPRIATE BRIEFING.
THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY
UNATTENDED CHILDREN.
DELIVERY SET
Name | Number |
---|---|
Air handling unit | 1 pc. |
User’s manual | 1 pc. |
Control panel | 1 pc. |
Drain pipe | 1 pc. |
Installation kit | 1 pc. |
Packing box | 1 pc. |
DESIGNATION KEY
TECHNICAL DATA
The unit is designed for application with the ambient temperature ranging from
+1 °C to +40 °C and relative humidity up to 80 %.
In order to prevent condensation on the internal walls of the unit, it is
necessary that the surface temperature of the casing is 2-3 °C above the dew
point temperature of the transported air.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
- IP22 for the unit connected to the air ducts;
- IP44 for the unit motors.
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
Model | KOMFORT Ultra S/L 250-H | KOMFORT Ultra S/L 250-E |
---|---|---|
Unit voltage [V /50 (60) Hz] | 1~ 230 | |
Maximum unit power [W] | 126 | |
Maximum unit current [A] | 0.6 | |
Maximum air flow [m3/h] | 260 | |
RPM [min-1] | 2700 | |
Sound pressure level at 3 m distance [dBA] | 28–47 | |
Transported air temperature [°C] | from -25 up to +40 | |
Insulation | 20 mm mineral wool | |
Extract filter | G4 | |
Supply filter | G4 (F8 PM2.5 81 %)* | |
Connected air duct diameter [mm] | Ø 125 | |
Weight [kg] | 26 | 25 |
Heat recovery efficiency [%] | from 57 up to 78 | from 52 up to 73 |
Humidity recovery efficiency [%] | from 27 up to 45 | |
Heat exchanger type | cross-flow | |
Heat exchanger material | polysterene | enthalpie |
OVERALL DIMENSIONS OF THE UNIT [mm]
Modell | A | A1 | B | B1 | C | C1 |
---|---|---|---|---|---|---|
KOMFORT Ultra S 250-H/E | 139 | – | 186 | – | 43 | – |
KOMFORT Ultra L 250-H/E | – | 139 | – | 186 | – | 43 |
DESIGN AND OPERATING LOGIC
Warm stale extract air from the room flows into the unit, where it is filtered
by the extract filter, then air flows through the heat exchanger and is
exhausted outside by the extract fan.
Clean cold air from outside is moved to the supply filter. Then filtered air
flows through the heat exchanger and is moved to the room with the supply fan.
Heat energy of warm extract air is transferred to clean intake fresh air from
outside and warms it up.
Heat recovery minimizes thermal energy losses and space heating expenses in
cold seasons.
Freeze protection
The heat exchanger freeze protection function of the unit is implemented with
a temperature sensor or a thermostat depending on model. The temperature
sensor is installed in the exhaust air duct downstream of the heat exchanger.
In case of a freezing danger (extract air temperature downstream of the heat
exchanger is +3 °C) the supply fan is turned off and the heat exchanger is
warmed up with warm extract air flow. To set the thermostat temperature set
point set the temperature control knob into a respective position.
INSTALLATION AND SET-UP
READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.
THE UNIT MUST BE MOUNTED BY A QUALIFIED EXPERT ONLY, PROPERLY TRAINED AND
HAVING THE REQUIRED TOOLS AND MATERIALS.
While installing the unit, provide enough access for maintenance or repair
work.
When selecting an installation location of the unit, provide free opening of
the service panel.
To get the best performance of the unit and to minimize turbulence-induced air
pressure losses, connect the straight air duct section to the spigots on both
sides of the unit while installing.
Minimum straight air duct length:
- equal to 1 air duct diameter on intake side
- equal to 3 air duct diameters on outlet side
If the air ducts are too short or not connected, protect the unit parts from
ingress of foreign objects.
To prevent uncontrollable access to the fans, the spigots may be covered with
a protecting grille or other protecting device with mesh width not more than
12.5 mm.
The unit must be mounted on a plane wall.
Installing the unit to an uneven surface could lead to the unit’s casing
distortion and operation disturbance.
The unit is designed for mounting on a horizontal plane as well as for wall
mounting with a fixing bracket that is fastened with three screws and dowels
(not included in the delivery set).
UNIT WALL MOUNTING
WARNING! CEILING MOUNTING IS ONLY AVAILABLE FOR THE UNITS KOMFORT ULTRA
S/L 250-E
- When selecting the installation site, provide minimum allowed distances to the unit.
- Attach the wall mounting brackets to a wall or to a ceiling considering the wall material and the unit weight.
- Install the unit on the mounting brackets. Tighten the triangular fixing screws on the mounting brackets.
SUSPENDED MOUNTING USING L-SHAPED BRACKETS (only for KOMFORT Ultra S/L
250-E models)
When using the L-shaped brackets, the unit can be mounted close to the ceiling
or on the threaded rods. UNIT FLOOR MOUNTING
Install the unit on the pre-mounted floor supports, minimum 150 mm height, to
ensure sufficient access for the drain pipe connection to the U-trap and for
condensate drain system installation. SERVICE SIDE CHANGE
Make sure of the correct unit service side selection. Unit mounting position
should enable free excess to the service panel for maintenance and service
operations.
- Unlatch and open the service panel. Remove the service panel, and then remove the latches. Disconnect the limit switch and rit from the opening in the holder.
- Remove four triangular screws and suspend the suspension brackets. Then unscrew six fixing screws from the back panel and remove the panel. Install the back panel on the opposite side of the unit.
- Install the limit switch, the latches and the service panel on the opposite side of the unit.
Service side change is shown by the example of the KOMFORT Ultra S 250-H/E air
handling unit.
The procedure of the service side changing for KOMFORT Ultra L 250-H/E is
carried out in the same manner.
CONDENSATE DRAINAGE SYSTEM CONNECTION (ONLY FOR THE KOMFORT ULTRA S/L 250-H
MODEL)
The KOMFORT Ultra S/L 250-E units are equipped with an enthalpy heat exchanger
and don’t require condensate drainage.
The hole for the drain pipe is at the bottom of the unit. Remove the plug from
the hole, open the service panel and install the drain pipe from the delivery
set into the hole, then connect the drain pipe to the sewage system using the
U-trap kit (available upon separate order). The pipe slope downwards must be
at least 3°.
CONNECTION TO POWER MAINS
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S
LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE
WARRANTY.
DO NOT LAY THE POWER CABLE OF THE UNIT IN CLOSE PROXIMITY AND PARALLEL TO THE
CONTROL PANEL CABLE! DO NOT COIL THE CONTROL PANEL CABLE WHILE LAYING ITS
OUT.Connect the unit to
a single-phase AC 230 V/50 (60) Hz power mains by using the pre-wired power
cord with the Euro Plug XP.
Connect the unit to power mains through the external automatic circuit breaker
QF with a magnetic trip integrated into the fixed wiring system with the rated
current not below the rated current consumption (refer to the «Technical data»
section).
EXTERNAL CONNECTION DIAGRAM FOR THE S1 SPEED CONTROLLER
— Electric shock hazard!
Designation | Name | Cable type |
---|---|---|
P1 | External control panel | 2 x 0.75 mm² |
(3 x 0.75 mm²)
EXTERNAL CONNECTIONS DIAGRAM FOR THE S12 CONTROL PANEL
— Electric shock hazard!
Designation | Name | Cable type |
---|---|---|
P1 | External control panel | 2 x 0.75 mm² |
— Electric shock hazard!
Designation | Name | Cable type |
---|---|---|
P1 | External control panel | 2 x 0.75 mm² |
TECHNICAL MAINTENANCE
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS.
FOLLOW THE SAFETY REGULATIONS WHEN CARRYING OUT MAINTENANCE.
Maintenance operations of the unit are required 3-4 times per year. It
includes general cleaning of the unit and the following operations:
-
Filter maintenance (3-4 times per year).
Dirty filters increase air resistance in the system and reduce supply air volume. The filters require cleaning not less than 3-4 times per year.
Vacuum cleaning is allowed. After two consecutive cleanings filters must be replaced. For new filters contact the Seller. The steps to replace the filters are as follows (refer to the figure on p. 14):
1. Press out on the latches.
2. Open the unit panel.
3. Remove the filters from the unit. -
Fan maintenance (once per year).
Even in case of regular maintenance of the filters, some dust may accumulate inside the fans and reduce the fan performance and supply air flow.
Clean the fans with a soft brush or cloth. Do not use water, aggressive solvents, or sharp objects as they may damage the impeller. -
Heat exchanger maintenance (once per year).
Some dust may accumulate on the heat exchanger even in case of regular maintenance of the filters. To maintain the high heat recovery efficiency, regular cleaning is required. To clean the heat exchanger, pull it out, flush the heat exchanger with warm detergent solution.
After cleaning install the dry heat exchanger back to the unit.
To remove the filters and the heat exchanger follow the operation operation in Fig. 16:
1. Release the latches and remove the bottom panel.
2. Open the unit panel.
3. Remove the heat exchanger. -
Technical maintenance of condensate drainage system (once a year).
The condensate drainage (drain line) may get clogged by dirt and dust particles contained in the exhaust air. Check the drain line operation by filling the drain pan under the unit with water, clean the U-trap and the drain line, if necessary. -
Supply air flow control (twice per year).
The supply duct grille may get clogged with leaves and other objects reducing the unit performance and supply air delivery. Check the supply grille twice per year and clean it as required. -
Technical maintenance of air duct system (every 5 years).
Even regular fulfilling of all the prescribed above maintenance operations may not completely prevent dirt accumulation in the air ducts which reduces the unit capacity.
TECHNICAL MAINTENANCE
TROUBLESHOOTING
Problem | Possible reasons | Troubleshooting |
---|---|---|
The fan(s) do(es) not get started. | No power supply. | Make sure the power |
supply line is connected correctly, otherwise troubleshoot a connection error.
Cold supply air.| Extract filter clogging.| Clean or replace the extract
filter.
The heat exchanger is frosted.| Check the heat exchanger for icing. Switch the
unit off if required and turn it on after the freezing danger is no longer
imminent.
Low air flow.| Filters, fans or the heat exchanger are soiled.| Clean or
replace the filters, clean the fans, and the heat exchanger.
The ventilation system is soiled or damaged.| Clean the ventilation system
components. Replace the damaged components.
Noise, vibration.| The fan impeller is soiled.| Clean the impellers.
The fan or casing screw connection is loose.| Tighten the screw connection of
the fans or the casing all the way.
Water leakage (only for the KOMFORT Ultra S/L 250-H| The drainage system is
soiled, damaged or arranged not correctly.| Clean the drain line. Check the
drain line slope angle. Make sure that the U-trap is filled with water and the
drain pipes are frost protected.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 ˚C up to +40 ˚C and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility. We hereby declare that the
product complies with the provisions of Electromagnetic Compatibility (EMC)
Directive 2014/30/EU of the European Parliament and of the Council, Low
Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the
Council and CE-marking Council Directive 93/68/EEC. This certificate is issued
following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months
after the retail sale date provided the user’s observance of the
transportation, storage, installation, and operation regulations. Should any
malfunctions occur in the course of the unit operation through the
Manufacturer’s fault during the guaranteed period of operation, the user is
entitled to get all the faults eliminated by the manufacturer by means of
warranty repair at the factory free of charge. The warranty repair includes
work specific to elimination of faults in the unit operation to ensure its
intended use by the user within the guaranteed period of operation. The faults
are eliminated by means of replacement or repair of the unit components or a
specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s
manual with the purchase date stamp, and the payment paperwork certifying the
purchase. The unit model must comply with the one stated in the user’s manual.
Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE
STAMP.
CERTIFICATE OF ACCEPTANCE
Unit Type | Heat recovery air handling unit |
---|---|
Model | KOMFORT Ultra 250- S __ |
Serial Number | |
Manufacture Date | |
Quality Inspector’s Stamp |
SELLER INFORMATION
Seller|
---|---
Address|
Phone Number|
E-mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s
manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|
INSTALLATION CERTIFICATE
The KOMFORT Ultra 250- S __ unit is installed pursuant to the requirements stated in the present user’s manual.
Company name|
Address|
Phone Number|
Installation
Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the
applicable local and national construction, electrical and technical codes and
standards. The unit operates normally as intended by the manufacturer.
Signature:|
** WARRANTY CARD**
Unit Type | Heat recovery air handling unit |
---|---|
Model | KOMFORT Ultra 250- S __ |
Serial Number | |
Manufacture Date | |
Purchase Date | |
Warranty Period | |
Seller |
www.blaubergventilatoren.de
B25EN-06
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>