DeltaOHM HD2016 Weighing Rain Gauge Instruction Manual

June 5, 2024
DeltaOHM

DeltaOHM logo Operating manual
Weighing rain gauge
HD2016DeltaOHM HD2016 Weighing Rain Gauge -

INTRODUCTION

HD2016 is a rain gauge that detects the weight of the rainfall collected by a 400 cm 2 inlet. The sensor is a load cell located at the base of the rainfall collecting reservoir. The signal of the load cell is processed by the internal electronic board of the rain gauge in order to output the information on the rainfall. Many acquisition systems can be connected to the rain gauge, thanks to the multiplicity of outputs available:

  • RS485 with Modbus-RTU or proprietary ASCII protocol
  • SDI-12
  • Voltage-free pulse contact output

Delta OHM offers a wide range of acquisition systems /data loggers for gathering the data detected by the rain gauge. The rain gauge is able to provide the total rainfall, the partial rainfall (from the last reset command or from the last reading command), and the average rainfall rate in the last minute and in the last hour.
The measured rainfall is regularly saved into a non-volatile memory, which retains the information even in case of power failure.
The automatic discharge of the rainfall collected allows using a compact and lightweight structure for the installation of the rain gauge. So as to ensure accurate measurement even with low-temperature climatic conditions, a version with heating that is automatically activated below +4 °C has been developed (HD2016R ) so that snow deposits and ice formations are prevented. If the discharge of the water collected takes place during a rainfall, a retention valve, located at the top of the rain gauge, temporarily holds the current rainfall, so as to avoid losing the amount of rainfall that falls while discharging.
The rain gauge is equipped with sophisticated features that allow reducing the effects of wind, ensuring better accuracy and stability of the measurement.
An NTC temperature sensor allows keeping under control the internal temperature of the instrument. The corrosion-resistant materials used and the absence of moving parts guarantee reduced maintenance and long operating life.
The rainfall collecting parts are treated with a nonadherent product for a better water flow. The rain gauge is factory calibrated and ready for use. A self-diagnostic system periodically checks the correct operation of the instrument and reports any anomalies. The rain gauge requires a 10…15 Vdc power supply.
When submitting your order , a bird dissuader, made of eight 3 mm diameter spikes, 60 mm in height, can be installed on the rain gauge upon request.

DESCRIPTION

DeltaOHM HD2016 Weighing Rain Gauge - 1

  1. Optional flange for the installation of the rain gauge raised above the ground.
  2. Electronic board housing.
  3. M12 connector for the connection of the measuring circuit power supply and signals.
  4. Optional support rod for the installation of the rain gauge raised above the ground.
  5. Optional flat base for fixing the support of the rain gauge raised above the ground.
  6. Place the support rod.
  7. Discharge of the rainfall collected.
  8. Cover of the electronic board housing. To access the electronic board, loosen the 7 screws that secure the cover.
  9. Terminal for protective earth connection.
  10. Overflow drain.
  11. Optional cable for the connection of the measuring circuit power supply and signals.
  12. Cable gland for the heater power supply.
  13. Port reserved for technical service.
  14. Screws for fixing the cylindrical cover.
  15. Cylindrical cover.

INSTALLATION

The instrument must be installed in an open area (any close objects should be at a distance equal to at least 4 times their height), away from buildings, busy roads, trees, etc., ensuring the space over it is free from all objects which could obstruct rain measurements, and in an easily accessible position for the filter to be cleaned periodically.
Although the rain gauge is equipped with features that allow reducing the effects of wind, for the best measurement accuracy it is recommended to avoid installation in areas exposed to turbulence (for example, do not install the instrument on the top of a hill, but on the side).
The rain gauge can be installed on the ground or raised 500 mm above the ground. Other sizes above the ground are available on request. For ground installation, three adjustable support feet, so that the instrument can be leveled correctly, and holes for fixing to the floor have been provided.
For raised installations, a flange to be fastened to the base of the instrument, and on which the support rod must be inserted, is provided. The rod may end with a flange so that it can be fixed to the floor.
For the measurement to be correct, it is important that the rain gauge is placed perfectly leveled; the base of the rain gauge is fitted with a bubble level.

3.1 ELECTRICAL CONNECTIONS
The measuring circuit power supply and the outputs (RS485, SDI-12, or contact) are connected via the male 8-pole M12 connector of the instrument (point 3 on page 4). Use a cable with a female 8-pole M12 connector and 0.7 mm2 (AWG 19) minimum wires section. Use a shielded cable over long distances. Upon request, CP18… cables with 5 or 10 m standard lengths are available (other lengths available upon request). The connections of the M12 connector and CP18… cable are listed below.

DeltaOHM HD2016 Weighing Rain Gauge - 2

Connector pin N° Function CP18… cable wire N°/colour
1 Measuring circuit power supply negative (GND) SDI-12 output negative

12/Black + 7/Violet
+ 6/Pink (‘)
2| Measuring circuit power supply positive (+Vdc)| 1/Red + 2/Blue +
4/Grey-Pink (*)
3| Not used| 3/Yellow
4| DATA – (RS485)| 9/White
5| DATA + (RS485) or SDI-12 line (depending on the setting of the switch SW1)| 5/Red-Blue
6| 1st pole of the voltage-free contact| 8/Grey
7| Not used| 10/Brown
8| 2nd pole of the voltage-free contact| 11/Green

(*) Wires shorted on the connector pin.
Fig. 3.1.1: M12 connector and CP18… cable

Connect the Protective Earth via the terminal under the base of the rain gauge (point 9 on page 4).
The heater power supply (only HD2016R) is connected directly to the internal terminal block.
Unscrew the cover of the electronic board (point 8 on page 4) and pass the cable through the cable gland (point 12 on page 4). Use a cable with 2.5 mm² (AWG 13) minimum wires section.
The heater power supply is isolated from the measuring circuit.
The following figure shows the electronic board.

=DeltaOHM HD2016 Weighing Rain Gauge - 3

WARNING FOR VERSION HD2016R:
In order to prevent possible burns by coming into contact with the heater, make sure that the heater is NOT powered when the cylindrical cover of the rain gauge is removed for cleaning or maintenance operations.

3.2 CHOOSING THE DIGITAL OUTPUT AND THE PROTOCOL
The selection of the type of digital output is done by means of the switch SW1 on the electronic board. Set the switch toward the RS485 or SDI-12 indication depending on the desired output.
The switch is set at the factory toward the RS485 indication (unless otherwise requested).
The switch S1 of the DIP switch on the electronic board allows selecting the communication protocol of the digital output at the instrument power-on. Set the switch S1 toward the MODBUS indication to select the standard protocol (Modbus-RTU or  SDI-12depending  on the digital output selected with the switch SW1), or set the switch toward the ASCII indication to select the ASCII proprietary protocol. If the standard protocol is selected, it is possible to switch to the ASCII proprietary protocol while the instrument is operating as described in the paragraph “ ASCII proprietary protocol ”. By default, the standard protocol is selected (Modbus-RTU or SDI-12 depending on the digital output selected with the switch SW1).
The setting of the switch SW1 and the DIP switch are read-only at instrument power-on, therefore they must be set before powering the instrument. The change of the setting of the switch SW1 and the DIP switch while the instrument is powered has no effect until the instrument is turned off and back on.
Note: the switch S2 of the DIP switch does not perform any function.
To change the other instrument settings, see the paragraph “ ASCII proprietary protocol ”.

3.3 RS485 CONNECTION
In the RS485 connection, the instruments are connected through a twisted-pair shielded cable for signals and the third wire for the ground.
Line terminations should be placed at the two ends of the network. The rain gauge has a built-in termination resistor, but it is not connected by default; if the rain gauge is at one end of the network, you can connect the built-in termination resistor by using the command COt of the ASCII proprietary protocol.
The RS485 output of the rain gauge is not isolated from the power supply.DeltaOHM HD2016 Weighing Rain Gauge - 4

The maximum number of devices that can be connected to the RS485 line (Bus) depends on the load characteristics of the devices to be connected. The RS485 standard requires that the total load does not exceed 32 unit loads; if the load is greater, divide the network into segments and add a signal repeater between a segment and the successive one. Line termination should be applied at both ends of each segment. The maximum length of the cable depends on the transmission speed and the cable characteristics. Typically, the maximum length is 1200 m. The data line should be kept separate from any power lines in order to prevent interference with the transmitted signal. Each instrument on the network is univocally identified by an address. Multiple transmitters with the same address should not be placed in the network. Before connecting the instrument to the network, set the address and, if necessary, the communication parameters.

3.4 SDI-12 CONNECTION
More SDI-12 sensors can be connected in parallel. The distance between a sensor and the acquisition system should not exceed 60 m.
Before connecting the instrument to an  SDI-12 network containing other sensors, set the address by using the proper SDI-12 command.

DeltaOHM HD2016 Weighing Rain Gauge - 5

3.5 CONTACT OUTPUT

The voltage-free contact output simulates the pulse output of a tipping bucket rain gauge. The contact is isolated and is normally open. At 1-minute intervals, the output generates a pulse train (TON ≈ 60 ms, TOFF ≈ 60 ms) as a function of the rainfall measured in the previous minute. Each pulse corresponds to an amount of rainfall configurable from 0.001 to 1 mm/pulse (default=0.2) by using the command CP0 of the ASCII proprietary protocol.

DeltaOHM HD2016 Weighing Rain Gauge - 6

3.6 UNLOCKING THE LOAD CELL

The load is locked for the transport of the rain gauge. Loosen the three nuts (point 14 on page 4) at the base of the cylindrical cover (point 15 on page 4) and remove the cylindrical cover by pulling it upwards. Unlock the load cell located at the base of the rain gauge by loosening the two screws on the sides of the cell and translating the locking support outward (fig.3.6.1). Replace the cylindrical cover and tighten the 3 fixing nuts.

DeltaOHM HD2016 Weighing Rain Gauge - 7

3.7 FIXING THE RAIN GAUGE
For the measurement to be correct, it is important that the rain gauge is placed perfectly leveled; the base of the rain gauge is fitted with a bubble level.

DeltaOHM HD2016 Weighing Rain Gauge - 8

For ground installation, secure the three support feet to the base of the instrument. Adjust the height of the feet so that the instrument is perfectly leveled. The instrument can be fixed to the floor by using the holes provided in the feet, close to the adjustment screws.

DeltaOHM HD2016 Weighing Rain Gauge - 9

For raised installation, screw the support rod to the flange placed on the base of the instrument; the rod may end with a flange (HD2003.78) to be fixed to the floor.

DeltaOHM HD2016 Weighing Rain Gauge - 9

ASCII PROPRIETARY PROTOCOL

The ASCII proprietary protocol is mainly used to set the operating parameters of the instrument by sending serial commands from a PC. The protocol can be used both with RS485 and SDI-12 physical interface. The rain gauge should be connected to the PC by using a converter from RS485 or SDI-12 (depending on the rain gauge output used) to USB or RS232C (depending on the PC port used). The use of the RS48 cable incorporating an RS485/USB converter is recommended. If a USB converter is used, it is necessary to install the relevant USB drivers on the PC.

NOTES ON THE INSTALLATION OF UNSIGNED USB DRIVER: before installing an unsigned USB driver into operating systems starting from Windows 7, it is necessary to restart the PC by disabling the driver signing request. If the operating system is 64-bit, even after installation the request of driver signing has to be disabled each time the PC is restarted.
The ASCII proprietary protocol can be activated both at instrument power-on and while the instrument is operating with the Modbus-RTU or SDI-12 protocols. In order to activate the ASCII proprietary protocol at the rain gauge power- on, the DIP switch S1 on the electronic board must be set to OFF (toward the ASCII indication, see figure 3.1.2 on page 7) before turning the instrument on. If activated at power-on, the protocol operates with the following communication parameters:

  • Baud Rate = 57600
  •  Data bits = 8
  •  Parity = None (N)
  •  Stop bits = 1
  • Flow control = None

If the rain gauge is powered with the DIP switch S1 set to ON (toward the MODBUS indication on the electronic board), the Modbus-RTU or SDI-12 protocol, depending on the physical interface used, is activated by default. In this case, the ASCII proprietary protocol can be activated without turning the rain gauge off and without changing the setting of the DIP switch S1 by the following procedure:

  1.  In the PC, start a serial communication program (many free programs suitable for the purpose can be found on the Internet), then set the COM port number to which the instrument is connecting and the communication parameters with which the instrument is operating (19200 8E1 by default for RS485 Modbus-RTU, 1200 7E1 for SDI-12).
  2. Send the command ||| (sequence of three 124 decimal code ASCII characters followed by the Enter key). The instrument replies with @.
  3. Within 10 seconds from the reply of the instrument, send the command @ (64 decimal code ASCII character followed by the Enter key). The instrument replies with address: &, where nnn is the address of the instrument (if the instrument does not receive the command @ within 10 seconds, the ASCII proprietary protocol is not activated; in this case, repeat from point 2). The ASCII proprietary protocol is now active keeping the communication parameters of the previous protocol (therefore, it is not necessary to change the settings of the serial communication program). To disable the ASCII proprietary protocol after use and return to the previous protocol, send the command # (or power cycle the instrument).

After activation of the ASCII proprietary protocol, the serial commands given below can be sent. To change the rain gauge parameters, the serial command CAL USER ON must be sent first (the instrument replies with the address: USER ENABLED!). In order to cancel the command CAL USER ON, send the command CAL END (the instrument replies with address: LOCKED). The command CAL USER ON is automatically disabled after 5 minutes of inactivity. If the settings should be only read, the command CAL USER ON is not required.

Instrument general information

Command Reply Description
P0 address: & Ping
G0 HD2016 Model
G2 SN=number Serial number
G3 Firm. Ver.=version Firmware version
G4 Firm. Date=yyyy/mm/dd Firmware date
GD F cal:yyyy/mm/dd hh:mm:ss Factory calibration date

Reservoir discharge

Command Reply Description
CD address: & Runs the reservoir discharge cycle
CVL address: state& Changes in the state of the reservoir discharge

valve:
state= Opened ⇒ valve has been opened
state= Closed ⇒ valve has been closed
COa| address: &| Activates the discharge after 20 minutes from the end of the rainfall if the reservoir filling percentage is greater than or equal to 80% (2400 cc)
COb| address: &| Activates the discharge after 20 minutes from the end of the rainfall if the reservoir filling percentage is greater than or equal to 10% (300 cc)
RDE| address: delay| Reads the delay time before running the discharge at the end of a rainfall (default = 20 minutes)
CDE nnn| address: &| Activates the discharge after nnn minutes (20 ≤ nnn ≤480) from the end of the rainfall if the reservoir filling percentage is greater than the set threshold
RTE| address: percentage| Reads the reservoir filling percentage that enables the discharge (default = 10% ⇒ 300 cc)
CTE nn| address: &| Activates the discharge (after the delay time set) if the reservoir filling percentage is greater than nn % (1 ≤ nn ≤ 99)

Note: the discharge takes place normally at the end of rainfall after the delay time set; if the reservoir should overfill during rainfall, the discharge will take place during the rainfall and the upper retention valve will close to maintain the current rainfall in the upper part of the rain gauge; at the end of the discharge phase, the rainfall collected in the upper part of the rain gauge will be discharged in the main reservoir and weighted.

Upper retention valve

Command Reply Description
ROv address: state Reads the enabling state of the upper retention

valve:
state= 0 ⇒ valve is not enabled
state= 1 ⇒ valve is enabled
COv n| address: &| Enables/disables the use of the upper retention valve:
n= 0 ⇒  disable ; n= 1 ⇒  enable
CVH| address: state&| Change the state of the upper retention valve:
state= Opened ⇒ valve has been opened
state= Closed ⇒ valve has been closed

Heater
The HD2016R rain gauge has a temperature sensor that detects the internal temperature of the instrument ( not the air temperature ). The heater is activated when the internal temperature falls below the value set with the command CTL (default 4 °C) and is switched off when the internal temperature rises above the value set with the command CTH (default 10 °C).

Command Reply Description
RTH address: temperature Reads the heater deactivation temperature

(default = 10.0 °C)
CTH nn.d| address: &| Sets the heater deactivation temperature to the value nn.d, (activation temperature ≤ nn.d ≤ 10.0 °C)
RTL| address: temperature| Reads the heater activation temperature (default = 4.0 °C)
CTL nn.d| address: &| Sets the heater activation temperature to the value nn.d (4.0 °C ≤ nn.d ≤ deactivation temperature)
RTD| address: state| Reads the heater enabling state:
state= Enabled ⇒ heater is used
state= Disabled ⇒ heater is not used
CTD n| address: &| Enables/disables the use of the heater:
n= 0 ⇒  disable ; n= 1 ⇒  enable
CHS| address: state&| Changes the activation state of the heater:
state= On ⇒ heater has been switched on
state= Off ⇒ heater has been switched off

Resolution of contact output

Command Reply Description
RP0 address: resolution Reads the resolution, in mm/pulse, of the

contact output (default = 0.200 mm/pulse)
CP0 n.ddd| address: &| Sets the resolution of the contact output to the value
n.ddd mm/pulse (max. 1 mm/pulse)

Counters reset

Command Reply Description
CS address: & Resets the partial rainfall value
CLR address: & Resets all the counters

It must be run before the total weight counter reaches the maximum value of 999,999,999 mg

RS485 settings

Command Reply Description
ROt address: state Reads the connection state of the termination

resistor of the RS485 output:
state= 0 ⇒ termination resistor not connected
state= 1 ⇒ termination resistor connected
COt n| address: &| Connect/disconnect the termination resistor of the RS485 output: n= 0 ⇒ disconnect ; n= 1 ⇒Þ connect
RMA| address: address address| Reads the Modbus address (default = 1)
CMA nnn| address: &| Sets the Modbus address to nnn (1…247)
RMB| address: baud rate index MB baud| Reads the Modbus Baud Rate:
Baud rate index= 0 ⇒  1200 Baud rate index= 1 ⇒  2400 Baud rate index= 2 ⇒  4800 Baud rate index= 3 ⇒  9600
Baud rate index= 4 ⇒  19200 (default)
CMB n| address: &| Sets the Modbus Baud Rate of index n:
n= 0 ⇒  1200 ;  n= 1 ⇒  2400 ;  n= 2 Þ 4800
n= 3 ⇒  9600 ;  n= 4 ⇒  19200
RMP| address: mode index MB mode| Reads the Modbus transmission mode:
mode index= 0 ⇒  8N1
mode index= 1 ⇒  8N2
mode index= 2 ⇒  8E1 (default)
mode index= 3 ⇒  8E2 mode index= 4 Þ 8O1 mode index= 5 Þ 8O2
(N=no parity, E=even parity, O=odd parity)
CMP n| address: &| Sets the Modbus transmission mode:
n= 0 ⇒  8N1 ; n= 1 Þ 8N2  ; n= 2 ⇒  8E1
n= 3 ⇒  8E2  ; n= 4 ⇒  8O1 ; n= 5 ⇒  8O2
(N=no parity, E=even parity, O=odd parity)
RMW| address: delay index MB Tx delay| Reads the receiving mode after the Modbus transmission:
delay index= 0 ⇒  Violate protocol and go in receiving mode right after Tx
delay index= 1 ⇒ Respect protocol and wait for 3.5 characters after Tx (default)
CMW n| address: &| Sets the receiving mode after the Modbus transmission:
n= 0 ⇒  Violate protocol and go in receiving mode right after Tx
n= 1 ⇒  Respect protocol and wait for 3.5 characters after Tx

Printing the measures

Command Reply Description
SR n address: measured value Single print of the measure of index n:

n=0 ⇒ Status register content in hexadecimal
n=2 ⇒ Partial rainfall, in µm, from the last reading command
n=4 ⇒ Total rainfall in µm
n=6 ⇒ Partial rainfall, in µm, from the last reset command
n=8 ⇒ Average rainfall rate, in µm/min, calculated in the last minute
n=10 ⇒ Average rainfall rate, in µm/h, calculated in the last hour
n=12 ⇒ Rain gauge the internal temperature in °C
n=14 ⇒ Rainfall total weight (Pmg) in mg ()
n=16 ⇒ Rainfall total weight, in mg, considering the evaporation (WMG) (
)
n=18 ⇒ Weight, in mg, of the current reservoir content (Tmg) ()
n=20 ⇒ Partial rainfall, in mils, from the last reading command
n=22 ⇒ Total rainfall in mils
n=24 ⇒ Partial rainfall, in mils, from the last reset command
n=26 ⇒ Average rainfall rate, in mils/min, calculated in the last minute
n=28 ⇒ Average rainfall rate, in mils/h, calculated in the last hour
n=30 ⇒ Rain gauge the internal temperature in °F
(
) For details on weight measurements, please see the paragraph “Notes on weight measurements”.
RR n| address: measured value| Continuous print (once per second) of the measure of index n (see the command SR for the indexes)
S0| String with 16 fields| Single print of all the measures:
campo 1 ⇒ & followed by a control code
campo 2 ⇒ Filling percentage of the rain gauge reservoir
campo 3 ⇒ Weight, in mg, of the current reservoir content (Tmg) ()
campo 4 ⇒ Rainfall total weight, in mg, considering the evaporation (WMG) (
)
campo 5 ⇒ Rainfall total weight (Pmg) in mg ()
campo 6 ⇒ Partial rainfall, in µm, from the last reset command
campo 7 ⇒ Average rainfall rate, in µm/min, calculated in the last minute
campo 8 ⇒ Average rainfall rate, in µm/h, calculated in the last hour
campo 9 ⇒ Reservoir status (Evap if in evaporation, Rain if in precipitation) followed by
(valid data) or! (invalid data)
campo 10 ⇒ Indicates how long the status reported in the previous field has been active camp 11…15 ⇒ Confidential information campo 16 Þ Internal temperature in °C
(*) For details on weight measurements, please see the paragraph “Notes on weight measurements”.
R0| String with 16 fields| Continuous print (once per second) of all the measures (see the command S0 for the fields)
ST| address: & voltage status_register| Prints the supply voltage in Volt and the content of the status register in hexadecimal
SS| address: status_register| Prints the content of the status register in hexadecimal- mal
---|---|---

MODBUS-RTU PROTOCOL

For enabling the Modbus-RTU protocol, set on the electronic board, before powering the instrument, the DIP switches S1 to ON, toward the MODBUS indication, and the switch SW1 toward the RS485 indication (see figure 3.1.2 on page 7). In Modbus-RTU mode, the instrument sends the detected measurements only if specifically requested by the PC, PLC or data logger.

The default communication parameters are

  • Baud Rate = 19200
  • Data bits = 8
  • Parity = Even (E)
  • Stop bits = 1
  • Flow control = None

The communication parameters can be changed by using the appropriate serial commands of the ASCII proprietary protocol or, alternatively, directly with Modbus commands by changing the value of the Holding Registers described later.
The function code 04h (Read Input Registers) allows reading the values measured by the instrument. The following table lists the Input Registers available.

Modbus Input Registers

Register address Datum Format
0 Content of the status register 16-bit integer
1 Not used 16-bit integer
2,3 Partial rainfall, in µm, from the last reading command 16-bit integer
4,5 Total rainfall in µm 16-bit integer
6,7 Partial rainfall, in µm, from the last reset command 16-bit integer
8,9 Average rainfall rate, in µm/min, calculated at the last minute 16-bit

integer
10,11| Average rainfall rate, in µm/h, calculated in the last hour| 16-bit integer
12,13| Rain gauge the internal temperature in °C| 16-bit integer
14,15| Rainfall total weight (Pmg) in mg ()| 16-bit integer
16,17| Rainfall total weight, in mg, considering the evaporation (Wmg) (
)| 16-bit integer
18,19| Weight, in mg, of the current reservoir content (Tmg) (*)| 16-bit integer
20,21| Partial rainfall, in mils, from the last reading command| 16-bit integer
22,23| Total rainfall in mils| 16-bit integer
24,25| Partial rainfall, in mils, from the last reset command| 16-bit integer
26,27| Average rainfall rate, in mils/min, calculated at the last minute| 16-bit integer
28,29| Average rainfall rate, in mils/h, calculated in the last hour| 16-bit integer
30,31| Rain gauge the internal temperature in °F| 16-bit integer

(*) For details on weight measurements, please see the paragraph “Notes on weight measurements”. The measures are signed 32-bit integer values. Two consecutive 16-bit registers must be accessed to read a measure.
The register with a lower address (for example the register with address 12 for the temperature in °C) contains the most significant bits.
Some operating parameters of the instrument can be changed directly with Modbus commands by setting the value of the Holding Registers with the function code 06h (Write Single Register) or 10h (Write Multiple Registers). The following table lists the Holding Registers available.

Modbus Holding Registers

Register address Datum Format
0 Indicator of the correct execution of the last writing command. If 0 ,

the command has been executed correctly.
If 1 , command execution errors occurred.| 16-bit integer
1| Indicator of the correct permanent storage of the parameters. If 0 , the parameters have been stored correctly.
If 1 , storage errors occurred.| 16-bit integer
2| Content of the status register| 16-bit integer
8| Heater enabling/disabling.
Write A500 h to enable the use of the heater. Write A501 h to disable the use of the heater.| 16-bit integer
9| Reset all the counters.
Write A55A h to reset the counters.| 16-bit integer
10| Reset the partial rainfall value. Write A55B h to reset the value.| 16-bit integer
11| Reservoir discharge cycle.
Write A55A h to run the discharge cycle.| 16-bit integer
100| Modbus address (from 1 to 247, default=1).| 16-bit integer
101| Modbus Baud Rate.
If 0 , the Baud Rate is 9600. If 1 , the Baud Rate is 19200 (default).| 16-bit integer
102| Modbus transmission mode.
0 Þ 8N1, 1 ⇒  8N2, 2 ⇒  8E1 (default), 3 ⇒  8E2, 4 Þ 8O1, n= 5 ⇒  8O2 (N=no parity, E=even parity, O=odd parity)| 16-bit integer
103| Receiving mode after the Modbus transmission (Tx).
0   ⇒  Violates the protocol and goes immediately in reception mode after Tx
1   ⇒  Respects the protocol and waits for 3.5 characters after Tx (default)| 16-bit integer

In order to check whether the last writing operation has been completed successfully, verify that the Holding Register with address 0 contains 0 by using the function 03h (Read Holding Registers).
The 06h and 10h writing functions change only the value of the parameters in the RAM memory, the change is therefore canceled in case of a power supply failure in the instrument.
For making the change permanent, write the hexadecimal value FF00 in the Coil with address 2 by using the 05h function code (Write Single Coil). The command 05h must be sent within 10 seconds from the last 06h or 10h command.

Modbus Coils

Register address Datum
2 Permanent storage of the parameters.

In order to check whether the permanent storage has been completed successfully, verify that the Holding Register with address 1 contains 0, by using the function 03h (Read Holding Registers).

SDI-12 PROTOCOL

For enabling the SDI-12 protocol, before powering the instrument set on the electronic board the DIP switch S1 to ON, toward the MODBUS indication, and the switch SW1 toward the SDI-12 indication (see figure 3.1.2 on page 7).

The instrument is in compliance with version 1.3 of the protocol. The communication parameters of the protocol are:

  • Baud Rate = 1200
  • Data bits = 7
  • Parity = Even (E)
  • Stop bits = 1

Communication with the instrument is performed by sending a command in the following format:
< Address>!
With

= address of the instrument, the command is sent to

= type of operation requested to the instrument The instrument reply is as follows: **< Address>** With
= address of the replying instrument = information sent by the instrument = ASCII character Carriage Return = ASCII character Line Feed

The table below shows the available SDI-12 commands. For consistency with the documentation of the SDI-12 standard, the instrument address is indicated in the table with the letter a. The rain gauge leaves the factory with an address preset to 0. The address can be changed by using the proper SDI-12 command reported in the table.

SDI-12 commands

Command Instrument reply Description
a! a Verifies the presence of the in- instrument.
aI! allccccccccmmmmmmvvvssssssss with:

a = address of the instrument (1 character)
ll = SDI-12 compliant version (2 characters) cccccccc = manufacturer (8 characters) mmmmmm = instrument model (6 characters) vvv = firmware version (3 characters) ssssssss = serial number (8 characters) ⇒ Example of reply: 013DeltaOhmHD2016A0013201518
with:
0 = instrument address 13 = SDI-12 version 1.3 compliant
DeltaOhm =  anufacturer’s name HD2016 = instrument model
A00 = firmware version 13201518 = serial number| Requests for information from the instrument.
aAb!| b| Modification of the instrument
Where: b = new| Note: if the b character is not an acceptable address, the instrument replies with an instead of b.| address.
address| |
?!| a| The request for the address of the instrument. If more than one sensor is connected to the bus, a conflict occurs.
---|---|---
T YPE M ( START MEASUREMENT ) AND TYPE C ( START CONCURRENT MEASUREMENT ) COMMANDS
Total rainfall (mm) and rainfall rate
aM!

aC!

| atttn

with: ttt = number of seconds necessary for the instrument to make the measure available (3 characters)
n = number of detected variables (1 character for aM!, 2 characters for aC!)
Note: ttt = 000 means that datum is immediately available.

| Request to detect:
–   total rainfall (mm)
–   rainfall rate
aD0!| a+SR+IM+IH + RT
with:
SR = content of the status register in hexadecimal
IM = average rainfall rate, in mm/min, calculated in the last minute
IH = average rainfall rate, in mm/h, calculated in the last hour
RT = total rainfall in mm| Reads:
–   total rainfall (mm)
–   rainfall rate
Rainfall (mm), rainfall rate and temperature (°C)
aM1! aC1!| atttn with: ttt = number of seconds necessary for the instrument to make the measure available (3 characters)
n = number of detected variables (1 character for aM1!, 2 characters for aC1!)
Note: ttt = 000 means that the datum is immediately available.| Request to detect:
–   rainfall (mm)
–   rainfall rate
–   temperature (°C)
aD0!| a+SR+IH + RT
with:
SR = content of the status register in hexadecimal
IH = average rainfall rate, in mm/h, calculated in the last hour
RT = total rainfall in mm| Reads:
–   total rainfall (mm)
–   rainfall rate
aD1!| a+RP+IM+T 
with:
RP = partial rainfall, in mm, from the last reset command IM = average rainfall rate, in mm/min, calculated in the last minute
T = rain gauge the internal temperature in °C| Reads:
–   partial rainfall (mm)
–   rainfall rate
–   temperature (°C)
Rainfall (inches), rainfall rate, and temperature (°F)

aM2! aC2!| atttn
with: ttt = number of seconds necessary for the instrument to make the measure available (3 characters)
n = number of detected variables (1 character for aM2!, 2 characters for aC2!)
Note: ttt = 000 means that the datum is immediately available.| Request to detect:
–   rainfall (inches)
–   rainfall rate
–   temperature (°F)
aD0!| a+SR+IH + RT
with:
SR = content of the status register in hexadecimal
IH = average rainfall rate, in inches/h, calculated in the last hour
RT = total rainfall in inches| Reads:
–   total rainfall (inches)
–   rainfall rate
aD1!| a+RP+IM+T 
with:
RP = partial rainfall, in inches, from the last reset command
IM = average rainfall rate, in inches/min, calculated in the last minute
T = rain gauge the internal temperature in °F| Reads:
–   partial rainfall (inches)
–   rainfall rate
–   temperature (°F)
Rainfall weight
aM3! aC3!| atttn
with: ttt = number of seconds necessary for the instrument to make the measure available (3 characters)
n = number of detected variables (1 character for aM3!, 2 characters for aC3!)
Note: ttt = 000 means that the datum is immediately available.| Request to detect the rainfall weight.
aD0!| a+SR+Pmg + Wmg + Tmg 
with:
SR = content of the status register in hexadecimal Pmg = rainfall total weight in mg ()
WMG = rainfall total weight, in mg, considering the evaporation (
)
Tmg = weight, in mg, of the current reservoir content (*)| Reads the rainfall weight.
TYPE R ( CONTINUOUS MEASUREMENTS ) COMMANDS

aR0!| a+SR+IM+IH + RT
with:
SR = content of the status register in hexadecimal
IM = average rainfall rate, in mm/min, calculated in the last minute
IH = average rainfall rate, in mm/h, calculated in the last hour
RT = total rainfall in mm| Reads:
–   total rainfall (mm)
–   rainfall rate
aR1!| a+SR+IH + RT+RP+IM+T 
with:
SR = content of the status register in hexadecimal
IH = average rainfall rate, in mm/h, calculated in the last hour
RT = total rainfall in mm
RP = partial rainfall, in mm, from the last reset command IM = average rainfall rate, in mm/min, calculated in the last minute
T = rain gauge the internal temperature in °C| Reads:
–   total rainfall (mm)
–   partial rainfall (mm)
–   rainfall rate
–   temperature (°C)
aR2!| a+SR+IH + RT+RP+IM+T 
with:
SR = content of the status register in hexadecimal
IH = average rainfall rate, in inches/h, calculated in the last hour
RT = total rainfall in inches
RP = partial rainfall, in inches, from the last reset command
IM = average rainfall rate, in inches/min, calculated in the last minute
T = rain gauge the internal temperature in °F| Reads:
–   total rainfall (inches)
–   partial rainfall (inches)
–   rainfall rate
–   temperature (°F)
aR3!| a+SR+Pmg + Wmg + Tmg 
with:
SR = content of the status register in hexadecimal Pmg = rainfall total weight in mg ()
WMG = rainfall total weight, in mg, considering the evaporation (
)
Tmg = weight, in mg, of the current reservoir content (*)| Reads the rainfall weight.

(*) For details on weight measurements, please see the paragraph “Notes on weight measurements”.

In addition to the above-mentioned commands, the sensor also implements the corresponding commands with CRC, which require adding a 3-character CRC code at the end of the reply before . The format of these commands is obtained from the previous by adding the letters C: AMC!, aMC1!, aMC2!, aMC3!, ACC!, aCC1! aCC2! aCC3! aRC0! aRC1! aRC2! aRC3!.
Extended SDI-12 Commands
The commands explained in the chapter “ASCII PROPRIETARY PROTOCOL” can be sent as extended SDI-12 commands by prefixing the command with as, where a is the instrument address, and terminating the command with the exclamation mark (for example, 0XSCS! to send the command CS to the instrument with address 0). To change the rain gauge parameters, the command aXSCAL USER ON! must be sent first (the instrument replies USER ENABLED). To cancel the command CAL USER ON, send the command aXSCAL END! (the instrument replies LOCKED).
For more information about the SDI-12 protocol, visit the website “www.sdi-12.org“.

NOTES ON WEIGHT MEASUREMENTS

The rain gauge gives three weight measures in mg:

  • Tmg: weight of the current content of the rainfall reservoir.

  • Pmg: total weight of all the rainfall collected from when the rain gauge is in operation.
    The Pmg value is not decreased when the rainfall reservoir is discharged or when the reservoir content evaporates.
    The value can be reset by using the command CLR of the ASCII proprietary protocol or through the holding register with address 9 of the Modbus-RTU protocol.
    The maximum achievable value is 999,999,999 mg (1 mg resolution) corresponding to about 25,000 mm of rainfall.

  • WMG: value used to evaluate the weight changes in the reservoir due to rainfall or evaporation (changes due to water discharge are excluded).
    At the rain gauge power-on, WMG is set equal to Pmg (total weight); subsequently, the value is increased during rainfall and decreased when the reservoir content evaporates.
    The WMG value is not decreased when the rainfall reservoir is discharged. In practice, the change of WMG follows the change of Tmg (weight of the current content of the reservoir) but without taking into account that the water is discharged when the reservoir is full. The WMG value is equal to the value of Pmg minus the weight of all the water evaporated from when the rain gauge is in operation.
    The value is reset when Pmg is reset.

STATUS REGISTER

The 16-bit status register gives the following information:

Bit Description
0 Indicates the presence of an error condition (OR function of the bits 1, 2,

3, 4, 6, 7, 8, 9, 10)
1,2| Error in the values of the configuration parameters in memory
3| Error in the program memory
4| The power supply of the instrument is outside the allowed limits
5| Communication error
6| Error in the pulses counting (contact output)
7| The device has executed a reset
8| Rainfall reservoir not completely emptied (content > 10%)
9| Emptying of rainfall reservoir not activated (content > 80%)
10| Total rainfall overflow
11| The heater is forced into the OFF state
12| Heater state (0=OFF, 1=ON)
13| Rainfall state (0=no raining, 1=currently raining)
14| Emptying rainfall reservoir
15| Invalid data

To ensure the reliability of the measured values, it is recommended to periodically check the content of the status register (especially the bits 0 and 15).

MAINTENANCE

WARNING FOR VERSION HD2016R:
In order to prevent possible burns by coming into contact with the heater, make sure that the heater is NOT powered when the cylindrical cover of the rain gauge is removed for cleaning or maintenance operations.
Verify the upper filter (fig. 9.1) cleanliness periodically; check that there is no debris, leaves, dirt, or anything else that might obstruct the flowing of water. To accurately clean the filter, remove it from the rain gauge and wash it with the help of a brush.

DeltaOHM HD2016 Weighing Rain Gauge - 11

To clean the inside of the rain gauge, loosen the three nuts at the base of the cylindrical cover and remove the cylindrical cover by pulling it upwards (fig. 9.2).

DeltaOHM HD2016 Weighing Rain Gauge - 12

Remove the cover of the rainfall collecting reservoir (fig. 9.3) and check that there are no deposits of soil, sand, or any other obstructing things. To clean the water drain, open the discharge valve by using the serial command CVL of the ASCII proprietary protocol (see chapter 4).

If necessary, the surfaces can be cleaned with nonaggressive detergent.

Checking the operation of the discharge valve:

  1. Connect the rain gauge to the PC.
  2. Enable the ASCII proprietary protocol (see chapter 4).
  3. Disable the upper retention valve by sending the serial command COv 0.
  4. Pour some water into the rain gauge so as to fill the rainfall collecting reservoir partially.
  5. Open the discharge valve by using the serial command CVL and check that the water flows out from the discharge pipe of the rain gauge.
  6. To close the discharge valve, send the serial command CVL again.

Checking the operation of the upper retention valve:

  1. Connect the rain gauge to the PC.
  2. Enable the ASCII proprietary protocol (see chapter 4).
  3. Close the upper retention valve by using the serial command CVH.
  4. Open the discharge valve by using the serial command CVL.
  5. Pour some water into the rain gauge and check that water does not flow out from the discharge pipe of the rain gauge.
  6.  Open the upper retention valve by using the serial command CVH and check that the water flows out from the discharge pipe of the rain gauge.

Checking the overflow drain:

  1. Connect the rain gauge to the PC.
  2. Enable the ASCII proprietary protocol (see chapter 4).
  3. Disable the upper retention valve by sending the serial command COv 0.
  4.  Close the discharge valve by using the serial command CVL.
  5. Pour water in the rain gauge continuously until the water begins to flow out from the overflow drain.
  6.  To empty the rainfall collecting reservoir, open the discharge valve by using the serial command CVL.

Periodic counters reset:
The total weight counter (Pmg) can reach the maximum value of 999,999,999 mg. The counter is not automatically reset when it reaches the maximum value. Before the counter reaches the maximum value, reset it in one of the following ways:

  1. By sending the command CLR of the ASCII proprietary protocol.
  2.  By writing A55Ah in the Holding Register with address 9 of the Modbus-RTU protocol.
  3. By sending the extended command aXSCLR! (a is the instrument address) of the SDI-12 protocol.

TECHNICAL CHARACTERISTICS

Power supply| Measuring circuit: 10…15 Vdc
Heater: 12 Vdc ± 10% ( only HD2016R )
---|---
Consumption| Measuring circuit: ≈ 20 mA (1.5 A while discharging, typically for less than 1 minute with 300 cc and maximum 5 minutes with full reservoir)
Heater: 90 W ( only HD2016R )
Contact output| Isolated NO (Normally Open) contact (RON ≈ 1 kL, TON ≈ 60 ms)
Digital outputs| RS485 with Modbus-RTU or ASCII proprietary protocol SDI-12
Resolution| Rainfall: 0.001 mm
Weight: 1 mg
Rate: 0.001 mm/h or 0.001 mm/min
Temperature: 0.1 °C
Accuracy| Rainfall (*): ± 0.2 mm (wind speed < 30 m/s) Temperature: ± 1 °C
Maximum rainfall rate| 1000 mm/h
Operating temperature| 0…+70 °C without heating

-20…+70 °C with heating ( only HD2016R )

Heater intervention temperature| +4 °C ( only HD2016R )
Capacity| The automatic discharge of the 3000 cc reservoir allows seamless rainfall measurement.
Protection degree| IP 64
Collector area| 400 cm²
Minimum section of the wires of the connecting cable| Measuring circuit: 0.7 mm² (AWG 19) Heater: 2.5 mm² (AWG 13, only HD2016R )

(*) Very light rainfalls (less than about 10 g, corresponding to approx. 0.2 mm) are not detected because the water stagnates in the valves and filters, and does not reach the collecting reservoir.

INSTRUMENT STORAGE

Instrument storage conditions:

  • Temperature: -30…+70 °C.
  • Humidity: less than 90 %RH no condensation.
  • In storage, avoid places where:
    • humidity is high;
    • the instrument is exposed to direct sun radiation;
    • the instrument is exposed to a high-temperature source;
    • high vibration levels are present;
    • the instrument may be exposed to vapor, salt, and/or corrosive gas.

SAFETY INSTRUCTIONS

General safety instructions
The instrument has been manufactured and tested in accordance with the safety standard EN61010-1:2010 “Safety requirements for electrical equipment for measurement, control and laboratory use” and has left the factory in perfect safety technical conditions.
The instrument’s proper operation and operating safety can be ensured only if all standard safety measures, as well as the specific measures described in this manual, are followed. The instrument’s proper operation and operating safety can be ensured only in the climatic conditions specified in this manual. Do not use the instruments in places where there are:

  • Corrosive or flammable gases.
  • Direct vibrations or shocks to the instrument.
  • High-intensity electromagnetic fields, static electricity.

Do not remove the cylindrical cover of the instrument before unplugging the power cable of the heater.
Ensure that there is the system ground (Protective Earth) and the connecting cable is in good condition.

User obligations
The instrument operator shall follow the directives and regulations below that refer to the treatment of dangerous materials:

  • EEC directives on workplace safety.
  • National law regulations on workplace safety.
  • Accident-prevention regulations.

ORDERING CODES

HD2016

DeltaOHM HD2016 Weighing Rain Gauge - 14

Accessories:

CP18.5| 12-pole cable. Length 5 m. 8-pole M12 connector on one end, open wires on the other side.
---|---
CP18.10| 12-pole cable. Length 10 m. 8-pole M12 connector on one end, open wires on the other side.
HD2003.78| A flat base for fastening the support of the rain gauge is raised above the ground.

DELTA OHM metrology laboratories LAT N° 124 are ISO/IEC 17025 accredited by ACCREDIA for Temperature, Humidity, Pressure, Photometry / Radiometry, Acoustics, and Air Velocity. They can supply calibration certificates for the accredited quantities.

DeltaOHM logoUE EU DECLARATION OF CONFORMITY
Document-No. / Month. Year: 5026 / 07.2019
We declare as manufacturer herewith under our sole responsibility that the following products are in compliance with the protection requirements defined in the European Council directives:
Product identifier: HD2016 — HD2016R
Product description: Pluviometro a peseta Weighing rain gauge
The products conform to the following European Directives:

Directive

2014/30/EU| EMC Directive
2014/35/EU| Low Voltage Directive
2011/65/EU – 2015/863/EU| RoHS

Applied harmonized standards or mentioned technical specifications:

Harmonized standards

EN 61010-1:2010| Electrical safety requirements
EN 61326-1:2013| EMC requirements
EN 50581:2012| RoHS

The manufacturer is responsible for the declaration released by:
Johannes Overhues
Chief Executive Officer
19/07/2019 This declaration certifies the agreement with the harmonization legislation mentioned, contained however no warranty of characteristics.

WARRANTY
Delta OHM is required to respond to the “factory warranty” only in those cases provided by Legislative Decree 6 September 2005 – n. 206. Each instrument is sold after rigorous inspections; if any manufacturing defect is found, it is necessary to contact the distributor where the instrument was purchased from. During the warranty period (24 months from the date of invoice) any manufacturing defects found will be repaired free of charge. Misuse, wear, neglect, lack or inefficient maintenance as well as theft and damage during transport are excluded. Warranty does not apply if changes, tampering, or unauthorized repairs are made on the product. Solutions, probes, electrodes, and microphones are not guaranteed as improper use, even for a few minutes, may cause irreparable damages.
Delta OHM repairs the products that show defects of construction in accordance with the terms and conditions of the warranty included in the manual of the product. For any dispute, the competent court is the Court of Padua. The Italian law and the “Convention on Contracts for the International Sales of Goods” apply.

TECHNICAL INFORMATION
The quality level of our instruments is the result of continuous product development. This may lead to differences between the information reported in the manual and the instrument you have purchased. In case of discrepancies and/or inconsistencies, please write to [email protected].
Delta OHM reserves the right to change technical specifications and dimensions to fit the product requirements without prior notice.

DISPOSAL INFORMATION
Electrical and electronic equipment marked with specific symbols in compliance with the 2012/19/EU Directive must be disposed of separately from household waste.
European users can hand them over to the dealer or to the manufacturer when purchasing new electrical and electronic equipment, or to a WEEE collection point designated by local authorities. Illegal disposal is punished by law.
Disposing of electrical and electronic equipment separately from normal waste helps to preserve natural resources and allows materials to be recycled in an environmentally friendly way without risks to human health.

GHM GROUP – Delta OHM | Delta Ohm S.r.l. a socio unico
Via Marconi 5 | 35030 Caselle di Selvazzano | Padova | ITALY
Phone +39 049 8977150 | Fax +39 049 635596
www.deltaohm.com | [email protected] DeltaOHM HD2016 Weighing Rain Gauge -
iconV1.8 06/2022
Members of GHM GROUP
www.deltaohm.com
Keep for future reference.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

DeltaOHM User Manuals

Related Manuals