Deltaohm HD2013-3 Precipitation detector Instruction Manual
- June 5, 2024
- DeltaOHM
Table of Contents
- INTRODUCTION
- TECHNICAL SPECIFICATIONS
- INSTALLATION
- CONFIGURATION AND MEASUREMENT
- PROPRIETARY PROTOCOL
- MODBUS-RTU PROTOCOL
- MAINTENANCE
- SAFETY INSTRUCTIONS
- ORDERING CODES
- WARRANTY
- TECHNICAL INFORMATION
- DISPOSAL INFORMATION
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Operating manual
Precipitation detector
HD2013.3
www.deltaohm.com
Keep for future reference.
INTRODUCTION
HD2013.3 is a precipitation detector based on the capacitive principle. The
capacity value of the sensitive element changes according to the surface
dampened by raindrops.
An integrated heater keeps the detector dry, evaporates water, and prevents
false signals caused by fog or dew. The heater also activates at low
temperatures, melting the snow and allowing detection of snow precipitations
by using an ambient temperature sensor.
The instrument’s external circular dome acts as a windshield for the sensor,
preventing false indications.
An auto-calibration algorithm compensates for variations in the response due
to the dirt that can accumulate on the sensitive surface.
The instrument has a digital RS485 output with MODBUS-RTU or proprietary
protocol, a 0/4…20 mA (0…10 V on request when ordering) analog output and a
voltage-free contact output. The contact output is activated when the sensor
detects precipitation in progress.
The detector has an IP68 protection degree.
Supplied with fixing bracket for ∅ 30…50 mm mast.
Optional bird spikes (to be requested when ordering the detector) can be
mounted.
TECHNICAL SPECIFICATIONS
Precipitation sensor Type
Dimensions
Angle
Sensitive area| Capacitive, with an integrated heater of 6.6 cm2
30°
0.05 crn2 min.
---|---
Temperature sensor| NTC 10Ki2 @ 25 °C
Measuring range
Precipitation detection
Temperature| ON / OFF (precipitation in progress / no precipitation)
Percentage of dry sensitive surface of the sensor
-40…+60 °C
Resolution
Precipitation detection
Temperature| Configurable 1 % (default) or 0.1 % of dry sensitive surface of
the sensor
0.1 °C
Output| RS485 is not isolated, from MODBUS-RTU or proprietary protocol
Analog 0/4…20 mA (RLmax = 500 11) or on request 0…10 V (Rolm = 10 kit)
Voltage-free normally opens contact max. 200 mA @ 30 Vdc resistive load
Power supply| 12…30 Vdc
Consumption| With heating OFF: 18 mA @24 Vdc
With heating ON: 230 mA max @24 Vdc
The indicated consumption does not include the consumption due to the analog
output
Connection| 8-pole circular connector
Operating conditions| -40…+60 °C / 0…100 0/0RH
Storage temperature| -40…+60 °C
Dimensions| 0 70 x 70 mm (only the instrument without a mounting
bracket)
Weight| 450 g approx.
Protection degree| IP 68
Housing material| Technopolymer ASA
INSTALLATION
Use the supplied accessories to mount the instrument. The bracket can be fixed
to a ∅ 30…50 mm mast, both vertical and horizontal, thanks to the double
drilling on the bracket. Place the detector far from buildings, trees, etc…,
taking care that the space above is free from any object that could obstruct
the detection of the precipitation. Keep the sensor clean.
3.1 ELECTRICAL CONNECTIONS
The instrument has an 8-pole circular connector and uses the CP2013.2… optional cables, with the 8-pole connector on one side and open wires on the other side.
Connector| Function| Wire color
CP2013.2… cable
---|---|---
1| Voltage-free contact| Green
2| Power supply positive (+Vdc)| Red
3| RS485 B/+| White
4| Voltage-free contact| Blue
5| RS485 A/-| Brown
6| Analog output positive| Yellow
7| Power supply negative (GND)| Grey
8| Serial ground| Black
To ensure good noise immunity, it is recommended to connect the cable shield to the ground (GND).
RS485 connection:
By default, the instrument has MODBUS address 1 and communication parameters
19200, 8E1. Different parameters can be set using the proprietary protocol or
the MODBUS-RTU protocol. Current analog output: By default, the current analog
output is 4…20 mA, with
4 mA = sensor-sensitive surface completely wet
20 mA = sensor-sensitive surface completely dry
With the commands of the proprietary protocol, it is possible to set the range
0…20 mA for the output and reverse the direction of the output, so that when
the sensor-sensitive surface is completely wet the output is 20 mA. In case of
measurement error, the output goes to 22 mA. Voltage analog output
(optional):
By default, the voltage analog output is 0…10 V, with
0 V = sensor-sensitive surface completely wet and
10 V = sensor-sensitive surface completely dry
With the commands of the proprietary protocol, it is possible to set the range
2…10 V for the output and reverse the direction of the output so that when the
sensor-sensitive surface is completely wet the output is 10 V.
In case of measurement error, the output goes to 11 V. Contact output:
There is a normally open voltage-free contact between pins 1 and 4 of the
connector (green and blue wires of the optional CP2013.2… cable). The contact
closes when the sensor detects precipitation in progress.
CONFIGURATION AND MEASUREMENT
The configuration of the instrument and the reading of the measurements can be
done via the RS485 serial output, both with the proprietary protocol and with
the MODBUS RTU protocol. In the first 10 seconds after the instrument power
on, it is always active the proprietary protocol.
After 10 seconds from power on, the operating protocol is activated, which by
default is the MODBUS-RTU protocol.
It is possible to keep the proprietary protocol active even after 10 seconds
from power on by sending before the 10 seconds expire, the command @ of the
proprietary protocol. The proprietary protocol can be set as operating
protocol by means of the CP0 command.
The commands of the proprietary protocol and the registers of the MODBUS-RTU
protocol are described in detail in the following chapters.
Precipitation measurement: To determine if precipitation is in progress, the
instrument detects the percentage of dry sensitive surface of the sensor:
100% = sensitive surface of the sensor completely dry
0% = sensitive surface of the sensor completely wet
When the percentage of dry sensitive surface of the sensor falls below a
configurable threshold value (default 95%), the instrument indicates that
precipitation is in progress. The threshold value can be modified with the
command CRTnn of the proprietary protocol or by using the MODBUS holding
register with address 5.
The indication of precipitation in progress ceases when the percentage of dry
sensitive surface of the sensor rises above the threshold plus a configurable
hysteresis value (default 2%) and after a configurable delay time (default 2
minutes).
The resolution with which the percentage of dry sensitive surface of the
sensor is detected is 1% by default. The resolution can be set to 0.1% with
the command CRLRn of the proprietary protocol or by using the MODBUS holding
register with address 16.
The instrument discriminates between rainfall and snowfall based on the
measured ambient temperature. If the ambient temperature is lower than a
configurable reference temperature (default 2 °C), the precipitation is
considered snowy.
The detection sensitivity can be adjusted with the command DRSn of the
proprietary protocol or by using the MODBUS holding register with address 20.
Automatic calibration of the precipitation sensor:
The instrument can be set so that the precipitation sensor calibration is
automatically performed at regular intervals; this allows compensating for any
drift of the sensor due to temperature changes, aging, and dirt deposited on
the sensitive surface.
The correction applied by each automatic calibration is limited to a maximum
value (configurable), so as to avoid erroneous calibrations when the detected
value differs too much from the estimated value.
By default, the automatic calibration is enabled, with 30 minutes intervals
and 0.1% maximum correction. In order to change the automatic calibration
settings, see the chapters on the proprietary protocol and MODBUS-RTU
protocol.
PROPRIETARY PROTOCOL
To use the proprietary protocol, it is necessary to connect the instrument to
the PC via an RS485/USB (e.g. RS51K) or RS485/RS232 converter and use a
standard serial
communication program. In the serial communication program, set the COM port
number to which the instrument is connected and the communication parameters
as follows:
-
If the MODBUS-RTU protocol is set as the operating protocol in the instrument (default), set the Baud Rate 57600 and the parameters 8N2 in the serial communication
program, then power cycle the instrument and send the command @ within 10 seconds from the instrument power on. -
If the proprietary protocol is already set as the operating protocol in the instrument, it is possible to operate with Baud Rate 57600 and parameters 8N2 by sending the command @ within 10 seconds from the instrument power on, or you can let the 10 seconds pass without sending the command @ and operate with the communication parameters set in the instrument (default 19200, 8E1).
To change the instrument configuration, the serial command CAL USER ON must be
sent first (the instrument replies with USER CAL MODE ON). The command CAL
USER ON is automatically disabled after a few minutes of inactivity. If the
settings should be only read, the command CAL USER ON is not required.
Below is the list of the serial commands.
Instrument information:
Command | Reply | Description |
---|---|---|
G0 | Model | Instrument model |
G1 | & Revision | Instrument hardware revision |
G2 | SN=nnnnnnnn | Instrument serial number |
G3 | Firm.Ver.=x.y | Instrument firmware revision |
G4 | Firm.Date=yyyy/mm/dd | Date of firmware revision |
GC | Fact.Caleb.Date= yyyy/mm/dd | Date of factory calibration |
Protocol:
Command | Reply | Description |
---|---|---|
@ | & | Keeps the proprietary protocol operational even after 10 seconds from |
the instrument’s power on. It must be sent within 10 seconds from the
instrument power on.
CPn| &|| Sets the operating protocol:
• Proprietary if n=0
•MODBUS-RTU if n=1
Default : MODBUS-RTU (n=1)
RP| & n|| Reads the operating protocol set in the instrument.
SM| &|| Activates the MODBUS-RTU protocol immediately.
CMA| &|| Sets the instrument address for the MODBUS-RTU pro- tool to n.
The address should range between 1 and 247.
Default : 1
RMA| & n|| Reads the instrument address for the MODBUS-RTU pro- tool.
Note: After sending the CP1 command, the instrument remains with the
proprietary protocol.
Send the command SM to activate the MODBUS-RTU protocol immediately, or power
cycle the instrument.
RS485 communication parameters:
Command | Reply | Description |
---|---|---|
CMBn | & | Sets the Baud Rate: |
• 1200 if n=0
•2400 if n=1
•4800 if n=2
•9600 if n=3
• 19200 if n=4
•38400 if n=5
•57600 if n=6
• 115200 if n=7
Default : 19200 (n=4)
RMB| & n|| Reads Baud Rate setting
CMPn| &|| Sets parity and stop bits:
• 8N1 if n=0 [No parity, 1 stop bit] • 8N2 if n=1 [No parity, 2 stop bits] • 8E1 if n=2 [Even parity, 1 stop bit] • 8E2 if n=3 [Even parity, 2 stop bits] •8O1 if n=4 [Odd parity, 1 stop bit] •8O2 if n=5 [Odd parity, 2 stop bits] The number of data bits is fixed to 8. Default : 8E1 (n=2)
RMP| & n|| Reads the setting of parity and stop bits.
CMWn| &|| Sets waiting time after transmission with MODBUS-RTU protocol:
• Immediate reception if n=0 (violates protocol)
• Waiting 3.5 characters if n=1 (respects protocol)
Default : Immediate reception (n=0)
RMW| & n|| Reads the setting of waiting time after transmission with MODBUS-
RTU protocol.
Precipitation detection settings:
Command | Reply | Description |
---|---|---|
CRLRn | & | Sets the resolution with which the percentage of dry sensitive |
surface of the sensor is detected:
• 1% if n=0
•0.1% if n=1
Default : 1% (n=0)
RRLR| & n|| Reads the resolution with which the percentage of dry sensitive
surface of the sensor is detected.
CRT| &|| Sets the precipitation detection threshold to n value, where n is the
percentage of dry sensitive surface of the sensor below which the instrument
indicates that a pre- cipitation is in progress.
If the 0.1% resolution is set, the value must be ex- pressed in tenths (for
example, write 970 to indicate 97.0%).
Default : 97 (=97% with 1% default resolution)
RRT| & n|| Reads the setting of the precipitation detection threshold.
Crohn| &|| Sets the hysteresis of the precipitation detection threshold to n
value.
The value should range between 0 and 20%.
If the 0.1% resolution is set, the value must be ex- pressed in tenths (for
example, write 10 to indicate 1.0%).
Default : 1 (=1% with 1% default resolution)
---|---|---
RRH| & n|| Reads the setting of the hysteresis of the precipitation detection
threshold.
CST| &|| Sets the reference temperature to discriminate between rainfall and
snowfall to n value expressed in tenths of °C.
The value should range between -50 (=-5 .0 °C) and 50 (=+5.0 °C).
Default : 20 (=+2.0 °C)
RST| & n|| Reads the setting of the reference temperature to dis- criminate
between rainfall and snowfall.
Cian| &|| Sets the hysteresis of the reference temperature to dis- to
criminate between rainfall and snowfall to n value ex-pressed in tenths of °C.
The value should range within -5 (=-0 ,5 °C) and 5 (=+0,5 °C).
Default : 5 (=+0,5 °C)
RSH| & n|| Reads the setting of the hysteresis of the reference temperature to
discriminate between rainfall and snowfall.
CRADn| &|| Sets the delay in indicating the beginning of precipitation, both
rainy and snowy, to n seconds (0…32767 s).
The indication of precipitation in progress is generated only if the
precipitation lasts longer than the set time.
Default : 0
RRAD| & n|| Reads the setting of the delay in indicating the beginning of
precipitation.
CRABn| &|| Sets the delay in indicating the end of precipitation, both rainy
and snowy, to n seconds (0…32767 s).
The indication of precipitation in progress ceases only after the set time has
elapsed from the end of the precipitation.
Default : 120
RRAB| & n|| Reads the setting of the delay in indicating the end of
precipitation.
CTADn| &|| Sets the delay in indicating the transition from rainfall to
snowfall, when the temperature drops below the reference temperature, to n
seconds (0…32767 s).
Default : 0
RTAD| & n|| Reads the setting of the delay in indicating the transition from
rainfall to snowfall, when the temperature dops be- low the reference
temperature.
CTABn| &|| Sets the delay in indicating the transition from snowfall to
rainfall, when the temperature rises above the reference temperature plus the
hysteresis, to n seconds (0…32767 s).
Default : 0
---|---|---
RTAB| & n|| Reads the setting of the delay in indicating the transition from
snowfall to rainfall, when the temperature rises above the reference
temperature plus the hysteresis.
DRSn| &|| Sets the sensitivity of the precipitation detection to n value
(10…1000). The greater the n value, the greater the sensitivity.
Default : 100
GRS| & n|| Reads the setting of the sensitivity of the precipitation
detection.
Contact output:
Command | Reply | Description |
---|---|---|
CRSn | & | Sets the contact output activation mode: |
• Output disabled if n=0
• Output activated in case of rainfall if n=1
• Output activated in case of snowfall if n=2
Note: precipitation is considered a rainfall if the measured temperature is
higher than the reference temperature, and a snowfall if the measured
temperature is lower than the reference temperature.
Default : Output activated in case of rainfall (n=1)
RRS| & n|| Reads the setting of the contact output activation mode.
Analog output:
Command | Reply | Description |
---|---|---|
CAOE | & | Adds the offset to the analog output: 4…20 mA or 2…10 V. |
CAOD | & | Remove the offset from the analog output: 0…20 mA or 0…10 V. |
CAOR | & n | Reads the setting of the offset for the analog output: |
• Without offset, if n=0 ( default for voltage output )
• With offset, if n=1 ( default for current output )
CASE| &|| Sets the following correspondence for the analog output: 4 mA / 0 V
Þ 100% of the dry sensitive surface 20 mA / 10 V Þ 0% of the dry sensitive
surface
CASD| &|| Sets the following correspondence for the analog output: 4 mA / 0 V
Þ 0% of the dry sensitive surface 20 mA / 10 V Þ 100% of the dry sensitive
surface
CASR| & n|| Reads the setting of the correspondence between analog output and
percentage of dry sensitive surface:
• 4…20 mA / 0…10 V Þ 0…100% if n=0 ( default )
• 4…20 mA / 0…10 V Þ 100…0% if n=1
Units of measurement:
Command | Reply | Description |
---|---|---|
TTn | & | Sets the temperature unit of measurement: |
•°C if n=0
• °F if n=1
Default : °C (n=0)
HH| & n|| Reads the setting of the temperature unit of measurement.
Reading of the measurement information:
Command | Reply | Description |
---|---|---|
S0 | & | Disable the sending of the measurement information. |
S1 | & | Enable the sending of the measurement information at regular |
intervals.
To set the sending interval, use the command MT. For the meaning of the information sent by the instrument, see the command S2.
S2| & RAIN_RAW RAIN_LEVEL RAIN_STATUS RAIN_VALIDITY PRECIPITATION_TYPE
AMB_TEMP VOLTAGE HEATER_TEMP MICRO_TEMP HEATER_MODE HEATER_PERCENTAGE|| Prints
the list of the measurement information sent by the instrument:
RAIN_RAW = number of 12-bit ADC counts, proportional to the percentage of dry
sensitive surface of the sensor
RAIN_LEVEL = percentage of dry sensitive surface of the sensor
RAIN_STATUS = indication of no precipitation (0) or precipitation in progress
(1)
RAIN_VALIDITY = validity of the precipitation indication (0=no, 1=yes)
PRECIPITATION_TYPE = indication of the type of precipitation (0=rainfall,
1=snowfall)
AMB_TEMP = ambient temperature VOLTAGE = power supply voltage HEATER_TEMP =
heater temperature MICRO_TEMP = internal board temperature HEATER_MODE =
heating operating mode
HEATER_PERCENTAGE = percentage of heating power used
MTn| &|| Sets the interval for sending the measurement information to n
seconds (1…30 s).
Default : 1
NT| & n|| Reads the setting of the interval for sending the measurement
information.
Heating:
Command | Reply | Description |
---|---|---|
CHMn | & | Sets the heating operating mode: |
• Manual if n=0
• Always on if n=1
• Always off if n=2
• Automatic if n=3
If the manual mode is set, the heating power set with the command CHP is used.
Default : Automatic (n=3)
RHM| & n|| Reads the setting of the heating operating mode.
CHPn| &|| Sets the heating power for the manual operating mode to n value, as
a percentage of the maximum power (0…100%)
Default : 50 (=50% of the maximum power)
RHP| & n|| Reads the setting of the heating power for the manual operating
mode.
Advanced functions:
Command | Reply | Description |
---|---|---|
DFLT | & | Restores the factory configuration. |
CU4 | & | Calibrates the instrument. |
Send the command only if the sensor-sensitive surface is completely dry.
CRBSn| &|| Enable/disable the precipitation sensor automatic calibration at
regular intervals:
• Disable if n=0
• Enable if n=1
Default : Automatic calibration enabled
RRBS| & n|| Reads the enabling status of the precipitation sensor automatic
calibration.
CRBTn| &|| Sets the time interval between two consecutive precipi- tation
sensor automatic calibrations to n seconds (300…64800 s).
Default : 1200 (=20 minutes)
RRBT| & n|| Reads the setting of the time interval between two consecutive
precipitation sensor automatic calibrations.
CRBMCn| &|| Sets the maximum correction that can be applied by each
precipitation sensor automatic calibration to n value ex-pressed in tenths of
%.
The value should range within 1 (=0.1%) and 200 (=20.0%).
Default : 4 (=0.4%)
RRBMC| & n|| Reads the maximum correction that can be applied by each
precipitation sensor automatic calibration.
CHDTn| &|| Sets the temperature difference (ΔT) that is maintained between the
sensor heated base, in the automatic heat- ing operating mode, and the
environment to n value ex-pressed in tenths of °C.
Note : the greater the ΔT, the greater the drying speed of the sensor and
the greater the detection of the end of precipitation; on the other hand, the
greater the possibility that very light precipitation is not detected or
causes an oscillation in indicating the presence/absence of pre- cipitation.
The ΔT setting is therefore a compromise be- tween the opposite needs. If the
difference ΔT is too low, condensation can form on the sensor surface, which
can be detected as precipitation.
Default : 250 (=25.0 °C)
---|---|---
RHDT| & n|| Reads the setting of the temperature difference (ΔT) that is
maintained between the sensor heated base and the environment.
GRC| & x y|| Reads the number of reboots (x) and watchdog timeouts
(y) that occurred.
MODBUS-RTU PROTOCOL
By default, the instrument has MODBUS address 1 and communication parameters
19200, 8E1. The address and the communication parameters can be changed by
using the appropriate serial commands of the proprietary protocol or,
alternatively, directly with MODBUS commands by changing the value of the
Holding Registers described later.
The MODBUS-RTU protocol, if set as the operating protocol (default), is active
after 10 seconds from the instrument power on.
In order to change the instrument configuration using the MODBUS-RTU protocol,
the value 1 must be written first in the Coil number with address 1.
Below is the list of registers.
Discrete inputs:
Address | Description | Format |
---|---|---|
0 | Indication of no precipitation (0) or precipitation in progress (1). | Bit |
1 | Validity of the precipitation indication: 0=no, 1=yes. | Bit |
2 | Indication of the type of precipitation: 0=rainfall, 1=snowfall. | Bit |
Input Registers:
Address | Description | Format |
---|---|---|
0 | Instrument model identification. | 16-bit Integer |
1 | Instrument hardware revision. | 16-bit Integer |
2,3 | Instrument serial number. (*) | 16-bit Integer |
4 | Instrument firmware revision. The most significant byte indicates the major | |
revision; the less significant byte indicates the minor revision. | 16-bit |
Integer
5| A number of reboots occurred.| 16-bit Integer
6| A number of watchdog timeouts occurred.| 16-bit Integer
7| Power supply voltage in Volt (x10).| 16-bit Integer
8| Internal board temperature (x10).| 16-bit Integer
9| A number of 12-bit ADC counts are proportional to the percentage of dry
sensitive surface of the sensor.| 16-bit Integer
10| Percentage of dry sensitive surface of the sensor (x10 if the resolution
is 0.1%).| 16-bit Integer
11| A number of MODBUS communication errors.| 16-bit Integer
12| Ambient temperature (x10).| 16-bit Integer
13| Heater temperature (x10).| 16-bit Integer
14| Percentage of heating power used.| 16-bit Integer
15| Indication of precipitation absent/in progress and type of precipitation:
0=no precipitation
1=rainfall
2=snowfall| 16-bit Integer
(*) The Instrument serial number has 8 digits. Two consecutive registers must be accessed to read the number. The register with a lower address contains the most significant 4 digits.
Coils:
Address | Description | Format |
---|---|---|
0 | Set 1 to restore the factory configuration. Bit zeroing is automatic. | Bit |
1 | Enable configuration change: |
0=no (default), 1=yes.
The changes to Coils and Holding Registers will be accepted only if this
register is set to 1.| Bit
2| Sets waiting time after transmission with MODBUS-RTU protocol: 0=immediate
reception (default);
1 waiting 3.5 characters.| Bit
3| Set 1 to calibrate the instrument. Bit zeroing is automatic. Set 1 only if
the sensor-sensitive surface is completely dry.| Bit
Holding Registers:
Address | Description | Format |
---|---|---|
0 | RS485 Baud Rate: 0=1200; |
1=2400;
2=4800;
3=9600;
4=19200 (default);
5=38400;
6=57600;
7=115200.| 16-bit Integer
1| RS485 parity and stop bits: 0=8N1;
1=8N2;
2=8E1 (default);
3=8E2;
4=8O1;
5=8O2.
[N=no parity, E=even parity, O=odd parity]| 16-bit Integer
2| Instrument address for the MODBUS-RTU protocol (1…247, de- fault=1).|
16-bit Integer
3| Heating operating mode:
0= Manual;
1= Always on;
2= Always off;
3= Automatic (default).
If the manual mode is set, the heating power set in the next register is
used.| 16-bit Integer
4| Heating power for the manual operating mode as a percentage of the maximum
power (default=50%).| 16-bit Integer
5| Precipitation detection threshold as a percentage (x10 if the resolution is
0.1%) of dry sensitive surface of the sensor below which the instrument
indicates that precipitation is in progress (default=97%).| 16-bit Integer
6| Hysteresis (x10 if the resolution is 0.1%) of the precipitation de- tection
threshold (0…20%, default=1%).| 16-bit Integer
7| Precipitation detection interval (1…30 s, default=1 s).| 16-bit Integer
---|---|---
8| The reference temperature, expressed in tenths of the set unit of
measurement, to discriminate between rainfall and snowfall
(-50…+50=-5.0…+5.0 °C, default=+2.0 °C).
| 16-bit Integer
9| Hysteresis of the reference temperature, expressed in tenths of the set
unit of measurement, to discriminate between rainfall and snowfall
(-5…+5=-0.5…+0.5 °C, default=+0.5).| 16-bit Integer
10| Delay in indicating the beginning of precipitation, both rainy and snowy
(0…32767 s, default 0).
The indication of precipitation in progress is generated only if the
precipitation lasts longer than the set time.| 16-bit Integer
11| Delay in indicating the end of precipitation, both rainy and snowy
(0…32767 s, default 120 s).
The indication of precipitation in progress ceases only after the set time has
elapsed from the end of the precipitation.| 16-bit Integer
12| Delay in indicating the transition from rainfall to snowfall, when the
temperature drops below the reference temperature (0…32767 s, default 0).|
16-bit Integer
13| Delay in indicating the transition from snowfall to rainfall, when the
temperature rises above the reference temperature plus the hysteresis (0…32767
s, default 0).| 16-bit Integer
14| Temperature unit of measurement: 0=°C, 1=°F (default °C).| 16-bit Integer
15| Contact output activation mode:
0= Output disabled;
1= Output activated in case of rainfall (default); 2= Output activated in case of snowfall.
Note: precipitation is considered a rainfall if the measured temperature is higher than the reference temperature, and a snowfall if the measured temperature is lower than the reference temperature.
| 16-bit Integer
16| Resolution with which the percentage of dry sensitive surface of the
sensor is detected:
0= 1% (default); 1= 0.1%.
| 16-bit Integer
17| Enable the precipitation sensor automatic calibration at regular
intervals: 0=no, 1=yes (default).| 16-bit Integer
18| The time interval between two consecutive precipitation sensor au-
automatic calibrations (300…64800 s, default 1200=20 minutes).| 16-bit Integer
19| The maximum correction that can be applied by each precipitation sensor
automatic calibration is expressed in tenths of % (1…200=0.1…20.0%,
default=4).| 16-bit Integer
20| Temperature difference (ΔT) that is maintained between the sensor heated
base, in the automatic heating operating mode, and the environment expressed
in tenths of °C (default 250=25.0 °C).
Note : the greater the ΔT, the greater the drying speed of the sensor and the greater the detection of the end of precipitation; on the other hand, the greater the possibility that a very light pre- cipitation is not detected or causes an oscillation in indicating the presence/absence of precipitation. The ΔT setting is therefore a compromise between opposite needs. If the difference ΔT is too low, condensation can form on the sensor surface, which can be detected as precipitation.
| 16-bit Integer
21| Sensitivity of the precipitation detection (10…1000, default 100). The
greater the value, the greater the sensitivity.| 16-bit Integer
---|---|---
MAINTENANCE
In principle, the precipitation detector is maintenance-free thanks to an adaptive self-correction algorithm. However, it is advisable to carry out a periodical (at least every two years) visual inspection to check for any soiling of the sensitive surface. If necessary, clean the sensor surface with a moistened soft cloth. For more resistant dirt, a non-aggressive detergent or ethyl alcohol can be used.
SAFETY INSTRUCTIONS
General safety instructions
The instrument has been manufactured and tested in accordance with the safety
standard EN61010-1:2010 “Safety requirements for electrical equipment for
measurement, control and laboratory use” and has left the factory in perfect
safety technical conditions.
The instrument’s proper operation and operating safety can be ensured only if
all standard safety measures, as well as the specific measures described in
this manual, are followed.
The instrument’s proper operation and operating safety can be ensured only in
the climatic conditions specified in this manual.
Do not use the instruments in places where there are:
- Corrosive or flammable gases.
- Direct vibrations or shocks to the instrument.
- High-intensity electromagnetic fields, static electricity.
User obligations
The instrument operator shall follow the directives and regulations below that
refer to the treatment of dangerous materials:
- EEC directives on workplace safety.
- National law regulations on workplace safety.
- Accident-prevention regulations.
ORDERING CODES
HD2013.3| Rainfall/snowfall detector. IP68. RS485 output with MODBUS-RTU or
proprietary protocol, 0/4…20 mA (0…10 V on request when ordering) analog
output, and voltage-free contact output. Supplied
with mounting bracket and 8-pole watertight female free connector. Optional
bird spikes (to be requested when ordering).
CP2013.2… cable has to be ordered separately.
---|---
HD2013.2D| Bird spikes (6 spikes ∅ 3 mm, height 60 mm). To be requested when
ordering the instrument.
CP2013.2.5| Cable with the 8-pole watertight connector on one end, free wires
on the other end. Length 5 m.
CP2013.2.10| Cable with the 8-pole watertight connector on one end, free wires
on
the other end. Length 10 m.
DELTA OHM metrology laboratories LAT N° 124 are ISO/IEC 17025 accredited by ACCREDIA for Temperature, Humidity, Pressure, Photometry / Radiometry, Acoustics, and Air Velocity. They can supply calibration certificates for the accredited quantities.
EU DECLARATION OF CONFORMITY
Document-No. / Month. Year : 5140 / 01.2020
We declare as manufacturer herewith under our sole responsibility that the
following products are in compliance with the protection requirements defined
in the European Council directives: HD2013.3
Codice prodotto: Product identifier :
Product description: Rivelatore di precipitazione Precipitation detector
The products conform to the following European Directives:
Directives
2014/30/EU| EMC Directive
2014/35/EU| Low Voltage Directive
2011/65/EU – 2015/863/EU| RoHS
Applied harmonized standards or mentioned technical specifications:
Harmonized standards
EN 61010-1:2010| Electrical safety requirements
EN 61326-1:2013| EMC requirements
EN 50581:2012| RoHS
The manufacturer is responsible for the declaration released by:
Johannes Oyerhues
Chief Executive Officer
Caselle di Selvazzano, 16/01/2020
This declaration certifies the agreement with the harmonization legislation
mentioned, contained however no warranty of characteristics.
WARRANTY
Delta OHM is required to respond to the “factory warranty” only in those cases
provided by Legislative Decree 6 September 2005 – n. 206. Each instrument is
sold after rigorous inspections; if any manufacturing defect is found, it is
necessary to contact the distributor where the instrument was purchased from.
During the warranty period (24 months from the date of invoice) any
manufacturing defects found will be repaired free of charge. Misuse, wear,
neglect, lack or inefficient maintenance as well as theft and damage during
transport are excluded. Warranty does not apply if changes, tampering, or
unauthorized repairs are made on the product. Solutions, probes, electrodes,
and microphones are not guaranteed as improper use, even for a few minutes,
may cause irreparable damages.
Delta OHM repairs the products that show defects of construction in accordance
with the terms and conditions of the warranty included in the manual of the
product. For any dispute, the competent court is the Court of Padua. The
Italian law and the “Convention on Contracts for the International Sales of
Goods” apply.
TECHNICAL INFORMATION
The quality level of our instruments is the result of continuous product
development. This may lead to differences between the information reported in
the manual and the instrument you have purchased. In case of discrepancies
and/or inconsistencies, please write to
sales@deltaohm.com.
Delta OHM reserves the right to change technical specifications and dimensions
to fit the product requirements without prior notice.
DISPOSAL INFORMATION
Disposing of electrical and electronic equipment separately from normal waste helps to preserve natural resources and allows materials to be recycled in an environmentally friendly way without risks to human health.
V1.7
02/2022 GHM GROUP
Phone +39 049 8977150
Fax +39 049 635596
www.deltaohm.com
sales@deltaohm.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>