SENECA Z-KEY 2 Port ModBUS Industrial Gateway or Serial Device Server Instruction Manual
- June 5, 2024
- SENECA
Table of Contents
- PRELIMINARY WARNINGS
- CONTACT INFORMATION
- MODULE LAYOUT
- SIGNALS VIA LED ON FRONT PANEL
- TECHNICAL SPECIFICATION
- IDC10 CONNECTOR
- INSTALLATION REGULATIONS
- ELECTRICAL CONNECTIONS
- WEB SERVER AND PROFINET MODE (Z-KEY-P)
- WEB SERVER
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
**SENECA Z-KEY 2 Port ModBUS Industrial Gateway or Serial Device Server Instruction Manual
**
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol ****indicates conditions or actions that put the user’s safety at risk.
The word ATTENTION preceded by the symbol ****indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.
| WARNING : The full content of this manual must be read before any operation. The module must only be used by
qualified electricians. Specific documentation is available via QR-CODE shown on page 1.
---|---
| The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
| Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.
SENECA s.r.l.; Via Austria, 26 – 35127 –
PADOVA – ITALY;
Tel. +39.049.8705359 –
Fax +39.049.8706287
ISO 9001:205
CONTACT INFORMATION
Technical support| support@seneca.it| Product
information| sales@seneca.it
---|---|---|---
This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised.
The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.
MODULE LAYOUT
Dimensions : 17.5 x 102.5 x 111 mm, Weight: 100 g; Enclosure: PA6, black 102.5 mm
SIGNALS VIA LED ON FRONT PANEL
LED | STATUS | LED meaning |
---|---|---|
PWR | ON | The device is powered correctly |
COM
Z-KEY-P version only
| Flashing| Profinet communication active
Off| No Profinet communication
TX1| Flashing| Data transmission on port #1 RS485
RX1| Flashing| Data receipt on port #1 RS485
TX2| Flashing| Data transmission on port #2 RS485/RS232
RX2| Flashing| Data reception on port #2 RS485/RS232
ETH ACT Green| Flashing| Packet transmission on Ethernet port
ETH LNK Yellow| ON| Ethernet connection present
TECHNICAL SPECIFICATION
CERTIFICA- TIONS| | |
---|---|---|---
https://www.seneca.it/products/z-key/doc/CE_declaration
INSULATION|
ENVIRONMENTAL CONDITIONS| T emperature : -25 °C – + 65 °C;
Humidity :;30%– 90% non condensing. Altitude: Up to 2000 m above sea
level; Storage temperature: -30 °C – + 85 °C Protection rating: IP20 (Not
evaluated by UL)
ASSEMBLY| IEC EN60715, 35mm DIN rail in vertical position.
POWER SUPPLY| Voltage: 11 – 40 Vdc; 19 – 28 Vac 50 – 60 Hz; Absorption:
Max. 1,5W
**CONNECTIONS**| 3-way removable screw terminals, pitch 5 mm Rear
connector IDC10 for DIN bar 46277 RJ45 front connector
COMMUNICATION PORTS
| RS232 or RS485 switchable on terminal 10 – 11 – 12 (serial port 2) Maximum
Baud rate 115 k, maximum cable length RS232 < 3m
| RS485 IDC10 rear connector: Maximum Baud rate 115 k. (serial port 1)
| RJ45 front Ethernet connector: 100 Mbit/s, maximum distance 100 m
**CONFIGURATION**| Configuration and FW update via webserver; Via DIP –
SWITCH Via EASY SETUP 2 configuration software
ATTENTION
The device may only be powered by a power supply unit with a limited energy
electric circuit max.
40Vdc / 28Vac Max output in accordance with CAN/CSA-C22.2 No. 61010-1-12 / UL
Std. No. 61010-1 (3rd Edition) chapter 6.3.1/6.3.2 and 9.4 or class 2
according to CSA 223/UL 1310.
FACTORY IP ADDRESS
The default module IP address is static: 192.168.90.101
WEB SERVER
To access the maintenance Web Server with 192.168.90.101 factory IP address:
Default user: admin, Default password: admin, http://192.168.90.101
SETTING THE DIP-SWITCHES
WARNING.
The DIP-switch settings are read only at boot time. At each change, perform a restart.
SW2 DIP-SWITCH:
Through DIP-SWITCH-SW1 it is possible to set the IP configuration of the
device:
KEY
1| ON|
0| OFF|
DESCRIPTION | DIP 1 | DIP 2 |
---|
To obtain the configuration from the Flash memory, both SW1 DIP switch selectors must be set to OFF|
|
To reset the device to factory settings both SW1 DIP switches must be set to ON|
|
To force the device’s IP address to the standard value of SENECA Ethernet products: 192.168.90.101|
|
Reserved|
|
RS232/RS485 SETTING: RS232 or RS485 configuration on terminals 10-11-12 (serial port 2).
SW2
1| ON| | RS232 ACTIVATION
0| OFF| | | | RS485 ACTIVATION
IDC10 CONNECTOR
The illustration shows the meanings of the various IDC10 connector pins if
signals are to be sent via them directly
INSTALLATION REGULATIONS
The module has been designed for vertical installation on a DIN 46277 rail. For optimal operation and long life, adequate ventilation must be provided. Avoid positioning ducting or other objects that obstruct the ventilation slots.
Avoid mounting modules over heat-generating equipment. Installation in the bottom part of the electrical panel is recommended.
ATTENTION
These are open-type devices and intended for installation in an end enclosure / panel offering mechanical protection and protection against spread of fire.
ELECTRICAL CONNECTIONS
CAUTION
To meet the electromagnetic immunity requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc…).
**POWER SUPPLY
**
**SERIAL PORT 2: RS485 SW2 = OFF
**
**SERIAL PORT 2: RS232 SW2 = ON
**
WEB SERVER AND PROFINET MODE (Z-KEY-P)
The device is normally in Profaned mode; in Profaned mode the device can be
configured only through the Easy Setup 2 software.
In order to access the internal webserver it is necessary to put the device in
Webserver mode using the Easy Setup 2 or Seneca Device Discovery software. It
is also possible to change the operating mode by pressing the side button
following the procedure:
To force webserver mode:
- Keep the “PS1” button pressed until all LEDs are switched off
- Release the button
- The device restarts and the PWR and COM LEDs flash slowly to indicate webserver mode
To force Profinet mode:
- Keep the “PS1” button pressed until all LEDs are switched off
- Release the button
- The device restarts and the PWR and COM LEDs stop flashing slowly to indicate Profinet mode
WEB SERVER
To access the maintenance Web Server with the factory IP address above, use
the following credentials:
Username: admin; Password: admin
N.B.: For the Z-KEY-P version it is first necessary to activate webserver
mode
CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.