SUNPOWER 536685 SunVault Storage Torque Values Installation Guide
- June 5, 2024
- SUNPOWER
Table of Contents
- Installation Guide Appendix H
- 1–#6 AWG: 275| 31.1| 22.9| 120 – 600
- 8: 25
- 6: 35
- 4: 45| 2.2
- 8: 25
- 6: 35
- 4: 4| 2.2
- 3 AWG:
- 2–#6 AWG: 275| 31.1| 22.9| 0 – 150
- 2–#6 AWG: 275| 31.1| 22.9| 120 – 600
- H.2 ESS Enclosures
- 8 AWG: 40| 4.5| 3.3| 0–150
- 6–#4 AWG: 45| 5.1| 3.7| 0–150
- 8 AWG: 25| 3.9
- 3–#2 AWG: 50| 5.6| 4.2|
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SUNPOWER 536685 SunVault Storage Torque Values
Installation Guide Appendix H
All conductors must be torqued and clearly paint marked. For conductor torque values into breaker terminals, see values specified on each breaker for the specific wire size (AWG) being used.
H.1 Hub+
For the Hub+ tables in this section, refer to the following numbered diagram:
Hub+: Typical Field-Wired Terminations and Connections
Connection| **Tool| Torque| ****Diag. #| Torque
Tool Range
---|---|---|---|---
in-lb| N-m| ft-lb| in-lb (ft-lb)
Hub+ PVS Plastic Cover Screws (quantity two, #6 screws)| T15 Torx
(11-in-1)| 12| 1.3| 1.0| N/A| 0 – 40
(0 – 4)
Hub+ Dead Front Screws| 5/16” nut driver (11-in- 1)| 12| 1.3| 1.0| N/A|
0 – 40
(0 – 4)
Ungrounded Conductors into Top of Hub+ Factory Line-Side Lugs (L1/L2
incoming feeders)| 3/8” Allen| #1 AWG to 300 kcmil: 375| 42.4| 31.2| 7**|
120 – 600
(10 – 50)
1–#6 AWG: 275| 31.1| 22.9| 120 – 600
(10 – 50)
Hub+ Ground Bar, Main Ground Lug| 5/16” standard (flathead) screwdriver|
2/O to #4 AWG: 50| 5.6| 41.6| **15| 120 – 600
(10 – 50)
Hub+ Ground Bar, Branch Circuit Wire Holes| ** #2 square| #14–#10: 20
8: 25
6: 35
4: 45| 2.2
2.8
3.9
5.0| 1.6
2.1
2.9
3.7| **16| 0 – 150
(0 – 12)
Hub+ Neutral Bar, Main Neutral Lug| ** 1/4” Allen| 300 kcmil to #1
AWG: 50| 5.6| 4.1| 17| 0 – 150
(0 – 12)
Hub+ Neutral Bar, Branch Circuit Wire Holes| **** #2 square| #14–#10: 20
8: 25
6: 35
4: 4| 2.2
2.8
3.9
5.0| 1.6
2.1
2.9
3.7| ****
19
| 0 – 150
(0 – 12)
Hub+ Neutral Bar, Pass-Through Neutral Lug| 1/4” Allen| 2/O to
3 AWG:
50 #6–#4 AWG: 45| 5.6
5.0| 4.1
3.7| 20| 0 – 150 (0 – 12)
RPO cable conductors (ferruled conductors into green connector)|
Precision flat screwdriver| 3| .34| NA| N/A| 0 – 40 (0
– 4)
Hub+: When Field Changes Necessitate Engaging or Disturbing Factory Connections
Connection| Tool| Torque| Diag. #| Torque Tool
Range
---|---|---|---|---
in-lb| N-m| ft-lb| in-lb (ft-lb)
Hub+ Consumption CT Mounting Bracket to Hub+ Backplate (quantity two,
8/32” nuts)| 11/32”
nut driver
| 12| 1.3| 1.0| 3| 0 – 40
(0 – 4)
Optional Hub+ Main Breaker
Ungrounded conductors into breaker (L1/L2 incoming feeders)
| 1/4” Allen| #2 AWG to 300
kcmil: 250| 28.2| 20.8| 23| 120 – 600
(10 – 50)
Optional Hub+ Main Breaker Power tabs to Hub+ Line Side Busing (quantity
two, 1/4”-20 threaded studs)| ****
7/16” socket
| ****
48
| ****
5.4
| ****
4.0
| ****
11
| 0 – 150
(0 – 12)
Optional Hub+ main breaker
Housing to Hub+ backplate (quantity one 8/32 nut)
| 11/32” nut driver| ****
12
| ****
1.3
| ****
1.0
| ****
4
| 0 – 40
(0 – 4)
Hub+ MID Line-Side Factory Conductors to Hub+ Non-
Backup Pan
#1 AWG conductors into line lugs (L1/L2, if removed and used to wire to
alternate flex subpanel or directly to flex pan 125 A breaker)| 3/8”
Allen| #3 AWG to 250
kcmil: 375| 42.4| 31.2| 10| 120 – 600
(10 – 50)
2–#6 AWG: 275| 31.1| 22.9| 0 – 150
(0 – 12)
MID Load Side Lugs for Generation Pan
Conductors into lugs (quantity two; L1 factory-routed through production CT)
| 5/16” standard (flathead) screwdriver| #4–#6 AWG: 45| 5.0| 3.7| 13| 0
– 150
(0 – 12)
MID Load-Side Busing Lugs (Open lugs are hidden behind shroud—optional
use to wire to alternate backed-up subpanel.)
Important! Downstream subpanel must have OCPD if conductors are landed
on these lugs instead of from a breaker in the Backup Pan.| 3/8” Allen| #3 AWG
to 250 kcmil: 375| 42.4| 31.2| 14| 120 – 600
(10 – 50)
2–#6 AWG: 275| 31.1| 22.9| 120 – 600
(10 – 50)
Flex Pan Hold-Down Bracket (to hold down ESS or 125 A breakers)| Precision
flat screwdriver| 10| 1.1| NA| **24**| 0 – 40
(0 – 4)
Hub+: Additional Factory Connections
Connection| Tool| Torque| Diag. #| Torque Tool
Range
---|---|---|---|---
in-lb| N-m| ft-lb| in-lb (ft-lb)
PVDR to Hub+ Backplate
(quantity four, 8/32 nuts)| 11/32” nut driver| 12| 1.3| 1.0| 1| 0 –
40
(0 – 4)
MIDC to Hub+ Backplate
(quantity two 8/32 nuts)| 11/32” nut driver| 12| 1.3| 1.0| 2| 0 – 40
(0 – 4)
Ungrounded Conductors into PVDR
(quantity four)| #2 Phillips screwdriver| 24| 2.7| 2.0| 5| 0 – 40
(0 – 4)
Grounded (Neutral) #16 AWG Conductor into PVDR| #0 Phillips screwdriver|
3| 0.34| 0.25| 6| 0 – 40
(0 – 4)
PVDR Grounded (Neutral) #16 AWG Conductor into Hub+ Neutral Bar| #2
square| 20| 2.2| 1.6| 18| 0 – 40
(0 – 4)
Hub+ Line-Side Feeder Lugs to MID Line Side Busing
(quantity two 5/16-18 HH nuts; L1/L2 lugs)| 1/2” socket| 132| 14.9| 11.0|
8| 0 – 150
(0 – 12)
Hub+ Line-Side Lugs for Hub+ Non-Backup Pan, Line Lug to Line
Busing
(quantity two 5/16-18 HH nuts)| 1/2” socket| 132| 14.9| 11.0| 9| 0 –
150
(0 – 12)
Hub+ MID Contactor
(quantity four, 1/4”-20 nuts and bolts)| 7/16” socket| 72| 8.1| 6.0|
12| 0 – 150
(0 – 12)
Generation Pan Conductor Terminals
(feed comes from the PVDR)| 5/16” standard (flathead) screwdriver| #4 AWG:
45| 5.0| 3.7| 21| 0 – 150
(0 – 12)
Hub+ Non-Backup Pan Bus Lugs| 5/16” standard (flathead) screwdriver|
55| 6.2| 4.6| **22**| 0 – 150
(0 – 12)
H.2 ESS Enclosures
The following tables provide torque values for the ESS enclosure(s):
Connection| in-lb| N-m| ft-lb| Torque Tool Range
in-lb (ft-lb)
---|---|---|---|---
Battery Grounding Wire at Each Battery in Each ESS| 44| 5.0| 3.6| 0–150
(0–12)
AC Terminals in Inverter Compartment and at Ground Bar| #14–#10 AWG:
35| 3.9| 2.9| 0–150
(0–12)
8 AWG: 40| 4.5| 3.3| 0–150
(0–12)
6–#4 AWG: 45| 5.1| 3.7| 0–150
(0–12)
AUX cable conductors (ferruled conductors into green connector)| 3| .34|
NA| 0–40
(0–40)
Battery Cables at Inverter DC Busbars in BASE ESS (only if ENERGY ESS is
present)| 220| 24.8| 18.4| 120–600
(10–50)
Battery Cables (DC) at ENERGY ESS Terminal Block (only if ENERGY ESS
is present)| 87| 9.8| 7.2| 0–150
(0–12)
AC Fan conductors at ENERGY ESS Terminal Block (only if ENERGY ESS is
present)| 6| 7| NA| 0–40
(0–4)
Grounding Wire ENERGY ESS (only if ENERGY ESS is present)| #6 AWG: 35
8 AWG: 25| 3.9
2.8| 2.9
2.1| 0–40
(0–4)
ESS Pedestal Floor Mount Concrete Wedge Anchor Nuts (in concrete)| 480|
54.2| 40| 120–600
(10–50)
ESS to Pedestal Mount Base Plate| | | | 120–720
(0–60)
(quantity eight, 1/2″ bolts that secure the ESS to the mounting plate)| 685|
77.3| 57
SunPower DC Busbars into Inverter 3/8” bolt (only BASE ESS and only if
disturbed)|
180
| 20.3| 15.0| 0–150
(0–12)
Inverter Chassis Ground Lug (factory- torqued but may be disturbed in
field)| #6–#4 AWG: 45| 5.1| 3.7| 0–150
(0–12)
3–#2 AWG: 50| 5.6| 4.2|