SUNPOWER SPR-E Series Semi Flexible Solar Panel PV Modules Instruction Manual
- June 9, 2024
- SUNPOWER
Table of Contents
Safety and Installation Instructions
for Europe, Asia, Australia, Latin America and Africa
This document applies to SunPower PV Modules
Safety and Installation Instructions
( IEC version)
This document includes references to SunPower E‐series (SPR‐ Eyy‐zzz),
X‐series (SPR‐Xyy‐zzz), P‐Series (SPR‐Pyy‐zzz, SPR‐P3‐ zzz), SPR‐MAX2‐zzz,
SPR‐MAX3‐ zzz PV Modules.
Do not mix E, X, MAX2, MAX3, P Series and P3 in one System.
All module series does not require functional grounding and are compatible
with transformer‐less inverters (ref. section 4.1)
1.0 Introduction
This manual provides safety and installation instructions for IEC
certified SunPower photovoltaic modules carrying the TUV logo on the product
label (Figure 1).
www.tuv.com
ID 00000022009
Important! Please read this instruction sheet in its entirety before
installing, wiring, or using this product in any way.
Failure to comply with these instructions will invalidate the SunPower Limited
Warranty for PV Modules.
1.1 Disclaimer of Liability
The installation techniques, handling and use of this product are
beyond company control. Therefore, SunPower does not assume
responsibility for loss, damage or expense resulting from improper
installation, handling or use.
1.2 Conformity to International Electrotechnical Commission (IEC)
standards
This product meets or exceeds the requirements set forth by IEC
61215 Edition 2‐2005 and Edition 3‐2016 for PV Modules, as well as IEC 61730
Edition 1 and 2 series for Class II applications. The IEC Standard
covers flat‐plate PV modules intended for installation on buildings
and those intended to be freestanding. This product is not intended for use
where artificially concentrated sunlight is applied to the module.
This manual shall be used in combination with industry recognized
best practices. Modules should be installed by certified professionals only.
1.3 Limited Warranty
Module limited warranties are described in the SunPower warranty
document obtainable at www.sunpower.com. Please
read this document for more information.
Warranties do not apply to any of the following;
PV modules which in SunPower’s absolute judgment have been subjected to:
misuse, abuse, neglect or accident; alteration, improper installation,
application or removal (including but not limited to installation,
application or removal by any party other than a qualified personnel;
non‐observance of SunPower’s installation, users and/or maintenance
instructions; repair or modifications by someone other than an
approved service technician; power failure surges, lightning, flood, fire,
accidental breakage or other events outside SunPower’s control.
Safety Precautions
Before installing this device, read all safety instructions in this manual.
Danger! Module interconnects pass direct current (DC) and are sources of
voltage when the module is under load and when it is exposed to light.
Direct current can arc across gaps and may cause injury or death if
improper connection or disconnection is made, or if contact is made with
module components that are damaged. Do not connect or disconnect modules when
current
from the modules or an external source is present.
- Cover all modules in the PV array with an opaque cloth or material before making or breaking electrical connections.
- Do not disconnect any modules when its inverter is feeding in to the grid. Switch off the inverter before disconnecting, reinstalling or making any action with the modules.
- For connectors, which are accessible to untrained people, it is imperative to use the locking connectors and safety clips, if applicable, in order to defend against untrained personnel disconnecting the modules once they have been installed.
- All installations must be performed in compliance with all applicable regional and local codes.
- There are no user serviceable parts within the module. Do not attempt to repair any part of the module.
- Installation should be performed only by qualified personnel.
- Remove all metallic jewelry prior to installing this product to reduce the chance of accidental exposure to live circuits.
- Use insulated tools to reduce your risk of electric shock.
- Do not stand on, walk, drop, and scratch or allow objects to fall on the glass surface of the modules.
- Damaged modules (broken glass, torn back sheet, broken j‐boxes, broken connectors, etc) can be electrical hazards as well as laceration hazards. Contact with damaged module surfaces or module frame can cause electric shock. The dealer or installers should remove the module from array and contact the supplier for disposal instructions.
- Unconnected connectors must always be protected from pollution (e.g dust, humidity, foreign particles, etc), prior to installation. Do not leave unconnected (unprotected) connectors exposed to the environment. A clean assembly environment is therefore essential to avoid performance degradation.
- Do not install or handle the modules when they are wet or during periods of high wind.
- Do not block drain holes or allow water to pool in or near module frames
- SunPower recommend to not mix 160mm cells and 166mm cells modules in a cosmetically sensitive application.
- Contact your module supplier if maintenance is necessary.
- Save these instructions!
Electrical Characteristics
The module electrical ratings are measured under Standard Test
Conditions (STC) of 1 kW/m² irradiance with AM 1.5 spectrum and a cell
temperature of 25 °C. SunPower modules have specific electrical
characteristics as shown on the datasheets.
A photovoltaic module may produce more current and/or voltage than
reported at STC. Sunny, cool weather and reflection from snow or water can
increase current and power output. Therefore, the values of Isc and Voc marked
on the module should be multiplied by a factor of 1.25 when determining
component voltage ratings, conductor ampacities, fuse sizes, and size of
controls connected to PV output. An additional 1.25 multiplier may be
required by certain local codes for sizing fuses and conductors. SunPower
recommends the use of open circuit voltage temperature coefficients listed on
the datasheets when determining Maximum System Voltage.
Electrical Connections
Modules may be connected in series and/or parallel to achieve the
desired electrical output as long as certain conditions are met. Please use
only the same type of modules in a combined source circuit. SunPower
recommends that all wiring be double insulated with a minimum rating
of 85° C (185° F).
All wiring should use flexible copper (Cu) conductors. The minimum size
should be determined by the applicable codes. We recommend a size
not less than 4mm . The insulation type should be appropriate for
the type of installation method used and must meet SCII (Safety
Class II) and IEC 61730 requirements.
SunPower recommends a conservative minimum cable bend radius of equal to or
greater than 40mm, to avoid exposure of electrical connections to
direct sunlight and not to place connector in location where water could
easily accumulate.
4.1 System & Equipment Grounding
Please refer to the applicable regional and local codes on grounding PV
arrays and mounting frames for specific requirements (e.g. lightning
protection).
Module Types
SPR E, X , P series modules and our Maxeon and Performance Product Line are
compatible with Transformer Less (TL) inverters, when used as an
ungrounded PV source.
No frame grounding requirements (including functional frame grounding), but
may be subjected to local regulation.
Functional system grounding of a polarity (positive or negative) is optional
and may be subject to local requirements.
E Series:
SPR‐Eyy‐zz SPR‐Eyy‐zzz‐BLK SPR‐Eyy‐zzz‐COM
X Series:
SPR‐Xyy‐zzz SPR‐Xyy‐zzz‐BLK SPR‐Xyy‐zzz‐COM
P Series/ Performance Product Line:
SPR‐Pyy‐zzz‐COM SPR‐Pyy‐zzz SPR‐Pyy‐zzz‐BLK SPR‐P3‐zzz‐COM
SPR‐P3‐zzz SPR‐P3‐zzz‐BLK
Maxeon Product Line:
SPR‐MAX2‐zzz SPR‐MAX2‐zzz‐COM SPR‐MAX3‐zzz SPR‐MAX3‐zzz‐BLK
SPR‐MAX3‐zzz‐COM
Note: If you are installing an older Module Type than above
mentioned, please refer to different/previous applicable Safety and
Installation Manual.
If you are doing a frame grounding connection, avoid the direct
contact between Aluminum and Copper using an intermediate metal like steel or
tin.
4.2 Series Connection
The modules may be wired in series to produce the desired voltage output. Do
not exceed the maximum system voltage specified in module datasheet.
4.3 Parallel Connection
The modules may be combined in parallel to produce the desired
current output. Series string must be fused prior to combining with other
strings if the resulting maximum reverse current exceeds the fuse
rating as shown in the datasheets. Bypass diodes are factory
installed in the modules. Please refer to the applicable regional and local
codes for additional fusing requirements and limitations on the maximum
number of modules in parallel.
Module Mounting
The SunPower Limited Warranty for PV Modules is contingent upon modules being mounted in accordance with the requirements described in this section.
5.1 Site Considerations
SunPower modules should be mounted in locations that meet the
following requirements:
Operating Temperature: All SunPower modules must be mounted in environments
that ensure SunPower modules will operate within the following maximum and
minimum operating temperatures:
Maximum Operating Temperature | +85 °C (+185 °F) |
---|---|
Minimum Operating Temperature | ‐40 °C (‐40 °F) |
Care should be taken to provide adequate ventilation behind the modules, especially in hot environments.
Design Strength: SunPower modules are designed to meet a positive or
negative (upward and downward, e.g. wind) withstanding test pressure
load and a negative (or downward, e.g. static load or snow load) withstanding
test pressure load, as per IEC 61215, when mounted in the
configurations specified in Section 5.2 and Tables 1.2 or 1.3 below.
When mounting modules in snow prone or high wind environments, special care
should be taken to mount the modules in a manner that provides sufficient
design strength while meeting local code requirements.
Additional authorized Operating Environments:
Modules can be mounted in the following aggressive environment
according to the test limits mentioned below Salt mist corrosion testing: IEC
61701 Severity 6 Ammonia Corrosion Resistance: IEC 62716 Concentration:
6,667ppm
Excluded Operating Environments:
Certain operating environments are not recommended for specific
SunPower modules and are excluded from the SunPower Limited Warranty
for these modules.
No SunPower module should be mounted at a site where it may be subject to
direct contact with salt water, or other aggressive environment.
Modules should not be installed near flammable liquids, gases, or
locations with hazardous materials; or moving vehicules of any type.
Performance Series Mounting Orientation
Performance Series (P‐Series) modules are designed to be installed in
landscape orientation. In landscape orientation, P‐series modules
maintain higher power under row to row shading and edge soiling.
5.2 Mounting Configurations
Mounting system must provide a flat plane for the modules to be
mounted on and must not cause any twist or stress to be placed on the Module,
even in case of thermal expension. Modules may be mounted at any angle
from horizontal to vertical.
Select the appropriate orientation to maximize sunlight exposure.
SunPower recommends for a good performance of the system (reduction of
soiling effect) a minimum of 5˚ tilt angle. The cleaning frequency must be
increased for modules installed with a very low angle.
Commercial modules (96 & 128 cells) frames have permanently attached
stacking pins. Mounting system hardware used with commercial modules
must account for the presence of these stacking pins (see Table 2). There is a
20mm zone on the long side frame at 388‐408 mm (“D” area in Figure 2).
Specific information on module dimensions and the location of mounting
and grounding holes is provided in Figures 2 and Table 2.
In order to prevent water from entering the junction box, which could present
a safety hazard, modules should not be mounted such that the front/top glass
faces downward (e.g., on a tracking structure that positions the module
with the junction box facing skyward during sleep mode).
We also want to remind that the watertightness is not ensured by the modules
but by the mounting system and that drainage should be well designed for
Modules.
Clearance between the module frames and structure or ground is
required to prevent wiring damage and allows air to circulate behind the
module. The recommended assembling clearance between modules installed
on any mounting system is a minimum of 5 mm distance.
When installed on a roof, the module shall be mounted according to the local
and regional building and fire safety regulations. In case the module is
installed in a roof integrated PV‐System (BIPV), it shall be mounted over a
watertight and fire‐resistant underlayment rated for such application.
Modules mounting systems should only be installed on building that have been
formally considered for structural integrity, and confirmed to be capable of
handling the additional weighted load of the Modules and mounting systems, by
a certified building specialist or engineer.
Mounting system supplier shall manage the galvanic corrosion which can occur
between the aluminium frame of the Modules and mounting system or
grounding hardware if such devices is comprised of dissimilar metals.
The module is only certified for use when its factory frame is
fully intact. Do not remove or alter the module frame. Creating additional
mounting holes or removing the stacking pins may damage the module
and reduce the strength of the frame, therefore are not allowed.
Using mounting Clamps or clips with additional grounding bolts or
grounding metal sheets could be in compliance with this Safety and
Installation Instructions manual subject to conditions of Section 4.1
Modules may be mounted using the following methods only:
- Frame Holes: Secure the module to the structure using the factory mounting holes. Four M6 (¼”) stainless steel bolts, with nuts, washers, and lock washers are recommended per module. Refer to Table 2 for the module dimensions and mounting hole locations. (Please refer to the arrows on the Table 2, E1&E2&E3&E4).
- Pressure Clamps or Clips: Mount the module with the opposite clips on the longer and/or shorter side of the frame of the module. The clips allowed location should be according to Table 1.1. Installers should ensure the clamps are of sufficient strength to allow for the maximum design pressure of the module. Clips and clamps are not provided by SunPower. Clamps that secure to the top of the frame must not deform the top flange. Clamps must apply force collinear with the ‘wall’ of the module frame and not only to the top flange. Clamps or installation procedures that put excessive force on the top flange will deform the frame, void the module warranty and risk glass breakage. Figure 1a illustrates locations for top frame clamp force. Avoid clamping within 50mm of module corners to reduce risk of frame corner deflection and glass breakage. When clamping to the module frame, torque should never exceed 15 N.m to reduce chances of frame deformation. Mounting systems should be evaluated for compatibility before installing specially when the system is not using Clamps or clips.
- End Mount: End mounting is the capture mounting of the length of the module’s shorter frames with clamps on each shorter sides of the frame. Three different configurations are possible: 1) with two mounting rails under the complete length of each shorter side of the Modules, (See Table 1.2), 2) with two mounting rails parallel to the long side of the Modules (See Table 1.2) and 3) without any mounting rail (See Table 1.2). The end‐mounting rails and clips or clamps (identified as A(1&2&3&4) in Table 1.1) must be of sufficient strength to allow for maximum designed test pressure of the module. Verify this capacity with the mounting system of vendor before installation.
- Center Mount: (Only for Oasis Trackers): A continuous clamp may be used to clamp the bottom flange of the frame at the center of the long sides (identified as F1&2). Minimum clamping length shall be 150 mm on top of flange and 100 mm on bottom.
- Hybrid Mount: Combination with clamps or clips located on longer or shorter sides of Modules are also possible, see Table 1.2 for allowed configurations. In any case, four clampings points are needed.
- SunPower specified or SunPower supplied mounting systems. Modules mounted with strict adherence to SunPower documentation, using hardware systems supplied by or specified by SunPower
Figure 2 and Table 1.1 below demonstrate the mounting locations and Tables 1.2
and 1.3 give allowed load ratings (designed test value) for SunPower modules.
Figure 2: Mounting Zone locations for SunPower modules
For 96 cells,P‐Series and 104c:
For 128 cells and P‐Series Commercial:
Table 1: Mounting allowed clamping Zone Locations
Module Configuration| Mounting zone distance from corner in (mm)1| Frame holes
E (1&2&3&4)| Oasis center mount F(1&2)
---|---|---|---
Module size| Frame type| A (1&2&3&4)| B (1&2&3&4)| C (1&2&3&4)
96 cells, P- Series Residential and 104
cells and P3 BLK| G3 (Black)
Silver &
G4.1 &
G4.2 &
G4.3| 50-350| 150-380| 50-150| As per Drawing in the Table2 Not| eapplicabl
128 cells and P19/P3- COM| G4 &
G4.1 &
G4.2| 50-350| 408-880| 50-375| Refer to 5.2,4
D ‐ There is a 20mm zone at 388‐408mm from the corner where mounting is not
allowed due to the module stacking pin feature. Not applicable for residential
P19 Series
and 96 cells residential modules and all 104 cells.
- No part of the module clamp may extend beyond this area.
Table 1.2: Mounting Zone Load Ratings (test pressure) for Racking system without rail support.
Module Configuration | Wind (up & down) / Snow (down) (units in Pa) (***) |
---|---|
Module size | Frame type |
(1&2&3&4) | C(1sasaik4) or B + C |
(B1&3 +C2&4 or B2&4 +C1&3) OrA+B
t/4, A 1&31-D . r, 2&4 or A28,4 +BM)
OrA+C (A18,3 +C2&4 or A2&4 +C1&3)
96 cells, PSeries Residential White and P3 BLK| G3
Black &
Silver &
G4.1 &
G4.2 &
G4.3| 2400/2400(‘)| 2400/5400| 2400/5400| 2400/2400
104 cells and PSeries Black| G4.2 G4.| 2400/2400
128 cells, P19/P3- COM| G4 &
G4.1 &
G4.2| Not applicable (**)| 2400/5400| 3600/3600| 2400/2400
(): 5400Pa is allowed with clamps and mounting rails along the longer side of
the frame
(): 2400/2400Pa are allowed with clamps and mounting rails along the longer
side of the frame
() Safety factor of 1.5 included
Table 1.3: Mounting Zone Load Ratings for Racking system with an
additional support rail underneath length of frame and parallel to the short
side and suitably located
Module Configuration | Wind (up & down) /Snow (down) (units in Pa) |
---|---|
Module size | Frame type |
96 cells, P-Series Residential and 104 cells and P3 BLK | G3 (Black &Silver) & |
G4.1 & G4.2 & G4.3 | 2400 / 5400 |
128 cells and P-series 19/P3-COM | G4 & G4.1 & G4.2 |
5.3 Handling of Modules during Installation
Do not place modules face forward in direct contact with abrasive
surfaces like roofs, driveways, wooden pallets, railings, stucco walls, etc…
The module front surface glass is sensitive to oils and abrasive
surfaces, which may lead to scratches and irregular soiling.
During storage, modules need to be protected from rain or any kinds of
liquids. Required storage temperature is between 10°C to 40°C in a dry
environment (humidity between 30 to 80%). Do not store modules outdoor to
avoid moisture and wet conditions.
Modules that feature antireflective coated glass are prone to visible finger
print marks if touched on the front glass surface. SunPower
recommends handing modules with anti‐reflective glass with gloves (no leather
gloves) or limiting touching of the front surface. Any finger print marks
resulting from installation will naturally disappear over time or can be
reduced by following the washing guidelines in Section 6.0 below. Any
module coverage (colored plastic tarps or similar) during installation
can lead to permanent front glass discoloration and is not recommended. The
use of vacuum lifting pads can cause permanent marks on the front
glass.Never lift or move the module using the cables or the junction box
under any‐circumstances. Shading incidence need to be avoided during PV
system operation. The system is not supposed to be energized until
the mounting scaffolding, fences or railing have been removed from the roof.
Systems should be disconnected in any cases of maintenance which can cause
shading (e.g. chimney sweeping, any roof maintenance, antenna/dish
installations, etc).
Maintenance
SunPower recommends visual inspection on a regular basis of all
modules for safe electrical connections, sound mechanical connection,
and freedom from corrosion. This visual inspection should be performed by
trained personnel. The standard frequency is once a year according to
environmental conditions.
Periodic cleaning of modules is recommended but is not required.
Periodic cleaning has resulted in improved performance levels,
especially in regions with low levels of annual precipitation (less than
46,3cm (18,25 inches)). Consult your dealer or supplier about
recommended cleaning schedules for your area.
To clean a module, wash with potable, non‐heated, water. Normal water
pressure is more than adequate, but pressurized water up to 100 bar (min.50
cm distance) may be used. SunPower recommends using a large hosepipe and
not to perform cleaning at high outside temperatures. Fingerprints,
stains, or accumulations of dirt on the front surface may be removed as
follows: first rinse off area and let soak for a short period of time (5
mins). Re‐wet and use a soft sponge or seamless cloth to wipe glass surface in
a circular motion.
Fingerprints typically can be removed with a soft cloth or sponge and water
after wetting. Do not use harsh cleaning materials such as scouring
powder, steel wool, crapers, blades, or other sharp instruments to
clean the glass surface of the module. Use of such materials or
cleaning without consultation will invalidate the product warranty.
Table 2: Module Frame Details
Platform | RESIDENTIAL G3 FRAME ONLY 96 CELL MODULE FRAME DETAIL | Frame Profile |
---|---|---|
Residential Modules |
FOR COMMERCIAL (SILVER FRAME) MODULES ONLY, INCLUDES STACKING PINS
Commercial Modules
FOR P‐SERIES GEN 4.0 FRAME MODULES
Commercial Modules
Platform| Module mounting and ground hole detail
FOR P‐SERIES COMMERCIAL GEN 4.1 FRAME MODULES| Frame Profile
---|---|---
Commercial Modules|
FOR P‐SERIES COMMERCIAL GEN 4.2 FRAME MODULES
Commercial Modules
FOR P‐SERIES GEN 4.1 FRAME MODULES ( WHITE)
Residential Modules
Platform| Module mounting and ground hole detail
FOR P‐SERIES GEN 4.2 FRAME MODULES ( BLACK)| Frame Profile
---|---|---
Residential Modules|
FOR 104c GEN 4.2 FRAME MODULES
Residential/ Commercial Modules
FOR P3 MODULES
Residential/ Commercial Modules
Measurement Tolerances are +/‐3 mm for the Length and Width of the Module.
Contents of this manual are subject to change without notice.
In case of inconsistencies or conflicts between the English version and any
other versions of this manual (ordocument), the English version shall prevail
and take control in all respects.
For the latest Europe, Asia, Australia, Latin America and Africa please refer
to www.sunpower.com/PVInstallGuideIEC
SunPower Corporation
www.sunpower.com
©November 2019 SunPower Corporation.
All rights reserved. Specifications included in this manual are subject to
change without notice.
Documents / Resources
|
SUNPOWER SPR-E Series Semi Flexible Solar Panel PV
Modules
[pdf] Instruction Manual
SPR-Eyy-zzz, SPR-Xyy-zzz, SPR-Pyy-zzz, SPR-P3-zzz, SPR-MAX2-zzz, SPR-MAX3-zzz,
SPR-E Series Semi Flexible Solar Panel PV Modules, SPR-E Series, Semi Flexible
Solar Panel PV Modules
---|---
References
- Home Solar plus Storage Solutions | SunPower
- Home Solar plus Storage Solutions | SunPower
- 産業用・住宅用ソーラーパネル | マキシオン | Maxeon Japan
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>