SUNPOWER Maxeon 3 Solar Panel Instruction Manual
- June 4, 2024
- SUNPOWER
Table of Contents
FROM MAXEON SOLAR TECHNOLOGIES
NEW REVISION: V
Safety and Installation Instructions
This document includes references to Maxeon E-series (SPR-Eyyxxx), X-series (SPR-Xyy-xxx), P-Series (SPR-Pyy-xxx, SPR-P3-xxx, SPR-Pyy-xxx-UPP, SPR-Pyy- xxx-COM-M-BIF), SPR-MAX2-xxx, SPRMAX3-xxx, SPR-MAX5-xxx PV Modules. Do not mix E, X, MAX2, MAX3, MAX5, P Series, P3 , P5 and P6 in one System. All module series does not require functional grounding and are compatible with transformer-less inverters (ref. section 4.1)
Introduction
This manual provides safety and installation instructions for IEC-certified Maxeon photovoltaic modules carrying the TUV logo on the product label (Figure 1).
Important! Please read this instruction sheet in its entirety before
installing, wiring, or using this product in any way. Failure to comply with
these instructions will invalidate the Maxeon Limited Warranty for PV Modules.
1.1 Disclaimer of Liability
The installation techniques, handling and use of this product are beyond
company control. Therefore, Maxeon does not assume responsibility for loss,
damage or expense resulting from improper installation, handling or use.
1.2 Conformity to International Electrotechnical Commission (IEC) standards
This product meets or exceeds the requirements set forth by IEC 61215 Edition
3-2016 for PV Modules, as well as IEC 61730 Edition 1 and 2 series for Class
II applications. The IEC Standard covers flat-plate PV modules intended for
installation on buildings and those intended to be freestanding. This product
is not intended for use where artificially concentrated sunlight is applied to
the module. This manual shall be used in combination with industry-recognized
best practices. Modules should be installed by certified professionals only.
1.3 Limited Warranty
Module limited warranties are described in the Maxeon warranty document
obtainable at www.sunpower.maxeon.com.
Please read this document for more information. Warranties do not apply to any
of the following; PV Modules subjected to: (i) misuse, abuse, neglect or
accident;
(ii) alteration or improper installation (improper installation includes,
without limitation, installation or array that does not comply with all Maxeon
installation instructions and operations and maintenance instructions of any
type (as may be amended and updated from time to time at Maxon’s sole
discretion), and all national, state, and local laws, codes, ordinances, and
regulations);
(iii) repair or modification by someone other than an approved service
technician of Maxeon;
(iv) conditions exceeding the voltage, wind, snow load specifications; and
any other operational specification;
(v) power failure surges, lightning, flood, or fire; (vi) damage from persons,
biological
MAXEON SOLAR TECHNOLOGIES, LTD.
Safety and Installation Instructions – Document 001-15497 Rev.V activity, or
industrial chemical exposure; (vii) glass breakage from impact or other events
outside Maxeon’s control.
Safety Precautions
Before installing this device, read all safety instructions in this manual.
Danger! Module interconnects pass direct current (DC) and are sources of
voltage when the module is under load and when it is exposed to light. Direct
current can arc across aps and may cause injury or death if improper
connection or disconnection is made, or if contact is made with modular
components that are damaged. Do not connect or disconnect modules when current
from the modules or an external source is present.
- Cover all modules in the PV array with an opaque cloth or material before making or breaking electrical connections.
- Do not disconnect any modules when its inverter is feeding into the grid. Switch off the inverter before disconnecting, reinstalling, or making any action with the modules.
- For connectors, which are accessible to untrained people, it is imperative to use the locking connectors and safety clips, if applicable, in order to defend against untrained personnel disconnecting the modules once they have been installed.
- All installations must be performed in compliance with all applicable regional and local codes.
- There are no user-serviceable parts within the module. Do not attempt to repair any part of the module.
- Installation should be performed only by qualified personnel.
- Remove all metallic jewelry prior to installing this product to reduce the chance of accidental exposure to live circuits.
- Use insulated tools to reduce your risk of electric shock.
- Do not stand on, walk, drop, and scratch or allow objects to fall on the glass surface of the modules.
- Damaged modules (broken glass, torn back sheet, broken j-boxes, broken connectors, etc) can be electrical hazards as well as laceration hazards. Contact with damaged module surfaces or module frames can cause electric shock. Damaged modules should be immediately disconnected from the electric system. The module should be removed from the array as soon as possible and contact the supplier for disposal instructions.
- Unconnected connectors must always be protected from pollution (e.g dust, humidity, foreign particles, etc), prior to installation. Do not leave unconnected (unprotected) connectors exposed to the environment. A clean assembly environment is therefore essential to avoid performance degradation
- Do not allow the connectors to come in contact with chemicals such as greases, oils and organic solvents which may cause stress cracking.
- Do not install or handle the modules when they are wet or during periods of high wind.
- Do not block drain holes or allow water to pool in or near module frames
- Maxeon recommends to not mixing 160mm cells and 166mm cells modules in a cosmetically sensitive application.
- Contact your module supplier if maintenance is necessary.
- Save these instructions!
Electrical Characteristics
The module electrical ratings are measured under Standard Test Conditions (STC) of 1 kW/m² irradiance with AM 1.5 spectrum and a cell temperature of 25 °C. Maxeon modules have specific electrical characteristics as shown on the datasheets. A photovoltaic module may produce more current and/or voltage than reported at STC. Sunny, cool weather and reflection from snow or water can increase current and power output. Therefore, the values of Isc and Voc marked on the module should be multiplied by a factor of 1.25 when determining component voltage ratings, conductor ampacities, fuse sizes, and size of controls connected to PV output. An additional 1.25 multiplier may be equired by certain local codes for sizing fuses and conductors. Maxeon recommends the use of open-circuit voltage temperature coefficients listed on the datasheets when determining Maximum System Voltage.
Electrical Connections
Modules may be connected in series and/or parallel to achieve the desired
electrical output as long as certain conditions are met. Please use only the
same type of modules in a combined source circuit. Even if allowed by local
regulation, Plug and Socket connectors mated together in a PV system must be
of the same type (model, rating) from the same manufacturer i.e. a plug
connector from one manufacturer and a socket connector from another
manufacturer, or vice versa, shall not be used to make a connection. Maxeon
recommends that all wiring be double insulated with a minimum rating of 85° C
(185° F). All wiring should use flexible copper (Cu) conductors. The minimum
size should be determined by the applicable codes. We recommend a size not
less than 4mm. The insulation type should be appropriate for the type of
installation method used and must meet SCII (Safety Class II) and IEC 61730
requirements. To minimize the risk of indirect lightning strikes (Voltage
surges), the system should be designed to avoid loops in the wiring. Maxeon
recommends a conservative minimum bending radius (R) 5x cable diameter must be
maintained and must not be bent on the direct exit of the connector or
junction box. Avoid exposure of electrical connections to direct sunlight and
do not place the connector in a location where water could easily accumulate.
Installers must refer to the connector manufacturer’s instructions for further
installation and connection requirements. Connectors are factory assembled
with intentional gaps between the cable nut and the body of the connector. Do
not retighten module connector nuts as this may lead to stress cracking of the
connector assembly and will void the warranty.
4.1 System & Equipment Grounding
Please refer to the applicable regional and local codes on grounding PV arrays
and mounting frames for specific requirements (e.g. lightning protection).
Module Types
SPR E, X, P series modules and our Maxeon and Performance Product Line are
compatible with Transformer Less (TL) inverters when used as an ungrounded PV
source.
No frame grounding requirements (including functional frame grounding), but
may be subjected to local regulation. Functional system grounding of polarity
(positive or negative) is optional and may be subject to local requirements. E
Series:
SPR-Eyy-xxx SPR-Eyy-xxx-BLK SPR-Eyy-xxx-COM
X Series:
SPR-Xyy-xxx SPR-Xyy-xxx-BLK SPR-Xyy-xxx-COM
P Series/ Performance Product Line:
SPR-Pyy-xxx-COM SPR-Pyy-xxx SPR-Pyy-xxx-BLK SPR-P3-xxx-COM
SPR-P3-xxx-COM-1500 SPR-P3-xxx SPR-P3-xxx-BLK SPR-Py-xxx-UPP
SPR-Py-xxx-COM-M-BIF
Maxeon Product Line:
SPR-MAX2-xxx SPR-MAX2-xxx-COM SPR-MAX3-xxx SPR-MAX3-xxx-
BLK SPR-MAX3-xxx-COM SPR-MAX5-xxx-COM
Note: If you are installing an older Module Type than the above-
mentioned, please refer to the different/previous applicable Safety and
Installation Manual.
If you are doing a frame grounding connection, avoid the direct contact
between Aluminum and Copper using an intermediate metal like stainless steel
or tin.
4.2 Series Connection
The modules may be wired in series to produce the desired voltage output. Do
not exceed the maximum system voltage specified in the module datasheet.
4.3 Parallel Connection
The modules may be combined in parallel to produce the desired current output.
The series string must be fused prior to combining with other strings if the
resulting maximum reverse current exceeds the fuse rating as shown in the
datasheets. Bypass diodes are factory installed in the modules. Please refer
to the applicable regional and local codes for additional fusing requirements
and limitations on the maximum number of modules in parallel.
Module Mounting
The Maxeon Limited Warranty for PV Modules is contingent upon modules being mounted in accordance with the requirements described in this section.
5.1 Site Considerations
Maxeon modules should be mounted in locations that meet the following
requirements:
Operating Temperature: All Maxeon modules must be mounted in environments that
ensure Maxeon modules will operate within the following maximum and minimum
operating temperatures:
Maximum Operating
Temperature (Ambient)| +85 °C (+185 °F)
---|---
Minimum Operating
Temperature (Ambient)| -40 °C (-40 °F)
Care should be taken to provide adequate ventilation behind the modules,
especially in hot environments.
Shading: Modules should be installed so that permanent shading of cells
is avoided and partial shading that may occur during certain times of the day
or year is minimized. Permanent shading is defined as a shade that is cast
over the same position (of constant area) of the solar module throughout the
generation hours of the day. Shading may induce in certain cases strong energy
production reduction, even in the case of small shading, and should be avoided
as much as possible, especially at mid-day when the production is maximum.
Design Strength: Maxeon modules are designed to meet a positive or
negative (upward and downward, e.g. wind) withstanding test pressure load and
a negative (or downward, e.g. static load or snow load) withstanding test
pressure load, as per IEC 61215 when mounted in the configurations specified
in Section 5.2 and Tables 1.2 or 1.3 below.
When mounting modules in snow-prone or high-wind environments, special care
should be taken to mount the modules in a manner that provides sufficient
design strength while meeting local code requirements.
Additional authorized Operating Environments: Modules can be mounted in
the following aggressive environment according to the test limits mentioned
below Salt mist corrosion testing: IEC 61701 Severity 6 Ammonia Corrosion
Resistance: IEC 62716 Concentration: 6,667ppm
Excluded Operating Environments: Certain operating environments are not
recommended for specific Maxeon modules and are excluded from the Maxeon
Limited Warranty for these modules. No Maxeon module should be mounted at a
site where it may be subject to direct contact with salt water, or another
aggressive environment. Modules should not be installed near flammable
liquids, gases, or locations with hazardous materials; or moving vehicles of
any type.
Performance Series Mounting Orientation
Performance Series (P-Series) modules are designed to be installed in
landscape orientation. In landscape orientation, P-series modules maintain
higher power under row-to-row shading and edge soiling.
5.2 Mounting Configurations
Mounting system must provide a flat plane for the modules to be mounted on
and must not cause any twist or stress to be placed on the Module, even in
case of thermal expansion.
Modules may be mounted at any angle from horizontal to vertical. Select the
appropriate orientation to maximize sunlight exposure. Maxeon recommends for a
good performance of the system (reduction of soiling effect/water pooling) a
minimum of 5˚ tilt angle.
The cleaning frequency must be increased for modules installed with a very low
angle.
Commercial modules (96 & 128 cells) frames have permanently attached stacking
pins located a 20mm zone on the long side frame at 388-408 mm (“D” area in
Figure 2) . Mounting system hardware used with commercial modules must
account for the presence of these stacking pins (see Table 2).
Specific information on module dimensions and the location of mounting and
grounding holes is provided in Figures 2 and Table 2. In order to prevent
water from entering the junction box, which could present a safety hazard,
modules should not be mounted such that the front/top glass faces downward
(e.g., on a tracking structure that positions the module with the junction box
facing skyward during sleep mode).
We also want to remind you that the watertightness is not ensured by the
modules but by the mounting system and that drainage should be well-designed
for Modules.
Clearance between the module frames and structure or ground is required to
prevent wiring damage and allows air to circulate behind the module. The
recommended assembling clearance between modules installed on any mounting
system is a minimum of 5 mm distance.
When installed on a roof, the module shall be mounted according to local and
regional building and fire safety regulations. In case the module is installed
in a roof-integrated PV-System (BIPV), it shall be mounted over a watertight
and fire-resistant underlayment rated for such application Module mounting
systems should only be installed on buildings that have been formally
considered for structural integrity, and confirmed to be capable of handling
the additional weighted load of the Modules and mounting systems, by a
certified building specialist or engineer. The mounting system supplier shall
manage the galvanic corrosion which can occur between the aluminum frame of
the Modules and
the mounting system or grounding hardware if such devices is comprised of
dissimilar metals. The module is only certified for use when its factory frame
is fully intact. Do not remove or alter the module frame. Creating additional
mounting holes or removing the stacking pins may damage the module and reduce
the strength of the frame, therefore are not allowed. Using mounting Clamps or
clips with additional grounding bolts or grounding metal sheets could be in
compliance with this Safety and Installation Instructions manual subject to
conditions of Section 4.1 Modules may be mounted using the following methods
only:
-
Frame Holes: Secure the module to the structure using the factory mounting holes. Four M6 or M8 stainless steel bolts, with nuts, washers, and lock washers are recommended per module. Bolts are to be fastened according to racking supplier recommendations. Refer to Table 2 for the module dimensions and mounting hole locations. (Please refer to the arrows in Table 2, E1&E2&E3&E4).
-
Pressure Clamps or Clips: Mount the module with the opposite clips on the longer and/or shorter side of the frame of the module. The clips allowed location should be according to Table 1.1. Installers should ensure the clamps are of sufficient strength to allow for the maximum design pressure of the module. Clips and clamps are not provided by Maxeon. Clamps must apply force collinear with the ‘wall’ of the module frame and not only to the top flange. Clamps shall not apply excessive force to the top frame, warp the top flange, or contact the glass- these practices void the module warranty and risk glass breakage. Figure 1a Force must not deform top frame flange or glass may break illustrates locations for top frame clamp force. Avoid Force has to be applied in line with frame wall clamping within 50mm of module corners to reduce risk of frame corner deflection and glass breakage. When clamping to the module frame, torque should never exceed 15 N.m to reduce the chances of frame deformation. A calibrated torque wrench must be used. Mounting systems should be evaluated for compatibility before installation especially when the system is not using Clamps or clips. Please contact Maxeon for the approval of the use of nonstandard pressure clamps or clips where torque values are Figure 1a: Clamp Force Locations higher than otherwise stated.
-
End Mount: End mounting is the capture mounting of the length of the module’s shorter frames with clamps on each shorter side of the frame. Three different configurations are possible: 1) with two mounting rails under the complete length of each shorter side of the Modules, (See Table 1.2), 2) with two mounting rails parallel to the long side of the Modules (See Table 1.2) and 3) without any mounting rail (See Table 1.2). The end-mounting rails and clips or clamps (identified as A(1&2&3&4) in Table 1.1) must be of sufficient strength to allow for the maximum designed test pressure of the module. Verify this capacity with the mounting system of vendor before installation.
-
Hybrid Mount: Combination with clamps or clips located on longer or shorter sides of Modules are also possible, see Table 1.2 for allowed configurations. In any case, four clamping points are needed.
-
Maxeon specified or Maxeon-supplied mounting systems. Modules mounted with strict adherence to Maxeon documentation, using hardware systems supplied by or specified by Maxeon.
Figure 2 and Table 1.1 below demonstrate the mounting locations and
Tables 1.2 and 1.3 give allowed load ratings (designed test value) for
Maxeon modules.
Figure 2: Mounting Zone locations for Maxeon modules
For 96 cells, P-Series,104 and 112 cells:
Table 1: Approved module clamping/direct fixation zones
Module Configuration| Mounting zone distance from a corner in (mm)1|
Frame holes E
---|---|---
Module size| Frame
type| A| B| C
(1&2&3&4)| (18,28.38.4)| (1&2&3&4)| (1&2&3&4)
96 cells, 104 cells (MAX2 and MAX3),112 cells, P3 BLK and P3 RES+| G3 (Black)
Silver & G4.1 & 64.2 & G4.3| 50-350| 150-380| 50-150| As per
Drawing in
the Table 2
128 cells and P19-COM| G4 &
G4.1 &
G4.2| 50-350| 408-880| 50-375
P3-COM| 64.2 &
G4.3| 50-350| 408-833| 50-375
MAXS-COM| G4.2| 50-350| 296-796| 50-296
D – There is a 20mm zone at 388-408mm from the corner where mounting is not
allowed due to the module stacking pin feature. Not applicable for all P19
Series, all P3
Series, 96 cells residential modules, all 104 cells and MAX5 modules.
- No part of the module clamp may extend beyond this area.
Figure 3: Mounting Configurations
Configurations 1 and 2 show mounting with rail support, and 3 and 4 show
mounting without rail support. In “With Rail Support” the rails become
conventional or rails transverse while “Without Rail Support” becomes end
mounted on the long or short side. In the case when the glass deflects it
would not deflect in the rails for additional
support.
Table 1.2: Mounting Zone Design Load Ratings for Racking system without rail
support underneath the module. Refer to configurations 3 and 4 in Fig.3
Module
Configuration| Wind (up & down) / Snow (down)
(units in Pa) (•)
---|---
| | End| Frame| | 01142/4364)
or B+C
Module| Frame| Mount| Holes| B| (Bia3+C28„, or B264 +CI13)
| | | | | Or A + B
size| type| A| E| 1&1&3&41|
| | 16’14 31441| utztuto| | (Ate.3 +Bud or Ant. +818.3)
Or A + C
| | | | | (Alia +Cu. or A264+0363)
| G3| | | |
| Black &| | | |
| Silver &| 2400/| | |
96 cells, and P3 BLK| G4.1 &
G4.2 &| 2400′.)| 2400/| 2400/|
| G4.3| | 5400| 5400| 2400/2400
104 cells
and 112-| | 1800/| | |
cells| G4 2
.| 1800| | |
(MAX3)| | | | |
P3 RES+| G4.3| 1300/| 1600/| 1600/| 1300/
| | 1600| 2400| 2400| 1600
| G &| Nt| | |
128 cells,
P19-COM| G44 .1 &
G4.2| applicable
()| 5400| 3600| 2400/2400
| 64.2 &| 1600/| 1600/| 1600/|
P3-COM| | | | | 1600/1600
| G4.3| 1600| 2400| 2400|
MAX5-| | 1600/| 2400/| 3600/|
| G4.2| | | | 1600/1600
COM| | 2400| 5400| 3600|
(): 5400Pa is allowed with clamps and mounting rails along the longer side of
the frame
(): 2400/2400Pa are allowed with clamps and mounting rails along the longer
side of the frame
For Rooftop application, 1200/1200Pa is allowed with only clamps () Safety
factor of 1.5 included
Table 1.3: Mounting Zone Load Ratings for Racking system with rail support.
Refer to Configuration 1 and 2 in Fig.3
Module Configuration| **Wind (up & down) / Snow (down) (units in Pa)
(*)
---|---
Module size| Frame type| B (1&2&3&4)| C (1&2&3&4)
96 cells and P3 BLK| G3 (Black &Silver) &
G4.1 & G4.2| 2400 / 5400| 2400 / 2400
104 cells and 112-cells
(MAX3)| G4.2| 3600/5400
P3 RES+| G4.3| 1600/3600| 1600/3600
128 cells and P19-COM| G4 & G4.1 & G4.2| 3600 / 5400| 2400/ 3600
P3-COM| G4.2 & G4.3| 2000/2400| 1600/2400
MAXS-COM| G4.2| 3000/5400| 2800/2800
Figure 4: Mounting Zone Locations for Performance modules
For P3, P5 UPP and P6 BIF:
Table 1.4: Mounting Zone Load Ratings for Performance Modules
Applicable
Products2| Mounting
Zone| Distance from
corner (mm)| Wind (up & down) /
Snow(down) (units in Pa)3| Mounting
Method
---|---|---|---|---
P3 UPP (2066x 1160x
3smmi| A| 183-283| 1600/2400| Clamp
B| 466-566| 1600/36004
D| 783- 833| 1600/1600
E| 260-320| 1600/1600
F| 465-565| 1600/2400
Frame
Holes2| 383| 1600/1600|
504| 1600/3600
683| Bolt
1600/1600
833
P5 UPP & P6 Bifacial (2384 x 1092 x 35mm)| A| 442-542| 1600/3600| Clamp
B| 592-692| 1600/3600
D| 967-1017| 1160/1160
E| 243-303| 800/1600
C4| 540-640| 1600/3600
G
Frame
Holes2| 492| 1600/3600| Bolts
642| 1600/3600
992| 1160/1160
2 Refer to Table 2 for different mounting hole locations
3 Safety Factor 1.5 included
4 IEC validated
5 Minimum washer size of 24mm in diameter is required.
5.3 Bifacial Gain
Various environmental and installation parameters affect the bifacial gain.
Albedo is a measure of the amount of light reflected from the ground surface.
A higher albedo factor will increase irradiance on the backside and result in
a higher bifacial gain of the module. The surface conditions, the month of the
year, time of day, GHI, and DNI both influence the amount of incident rear-
side irradiance. Maxeon recommends checking with the solar module mounting
hardware suppliers in order to determine the Structure Shading factor of your
particular installation. The Structure Shading Factor varies with racking
system design, irradiance, albedo, and height of module installation above
ground and has an overall impact on the rear side irradiance mismatch. The
Rear side mismatch losses are proportional to the albedo, height of the
modules above ground, and structure shading factor. The irradiance non-
uniformity on the rear side results in mismatch generally as the albedo
increases and the installation height of the modules is lower to the ground.
5.4 Bifacial Electrical Considerations
The overall electrical bifacial gain is determined by the combination of
albedo, irradiance, shading losses from the rear side, rear side mismatch, and
height of installation above ground. Please refer to the Maxeon datasheet for
the electrical outputs with respect to the overall bifacial gain. Please
utilize a suitable performance software package to simulate the overall
bifacial gain.
5.5 Handling of Modules during Installation
Do not place modules face forward in direct contact with abrasive surfaces
like roofs, driveways, wooden pallets, railings, stucco walls, etc…The module
front surface glass is sensitive to oils and abrasive surfaces, which may lead
to scratches and irregular soiling. During storage, modules need to be
protected from rain or any kind of liquid. The required storage temperature is
between 10°C to 40°C in a dry environment (humidity between 30 to 80%). Do not
store modules outdoors to avoid moisture and wet conditions. Modules that
feature antireflective coated glass are prone to visible fingerprint marks if
touched on the front glass surface. Maxeon recommends handing modules with
anti-reflective glass with gloves (no leather gloves) or limiting touching of
the front surface. Any finger print marks resulting from installation will
naturally disappear over time or can be reduced by following the washing
guidelines in Section 6.0 below. Any module coverage (colored plastic tarps or
similar) during installation can lead to permanent front glass discoloration
and is not recommended. The use of vacuum lifting pads can cause permanent
marks on the front glass. Never lift or move the module using the cables or
the junction box under any circumstances. Shading incidence needs to be
avoided during PV system operation. The system is not supposed to be energized
until the mounting scaffolding, fences or railing have been removed from the
roof. Systems should be disconnected in any cases of maintenance that can
cause shading (e.g. chimney sweeping, any roof maintenance, antenna/dish
installations, etc).
Maintenance
Maxeon recommends visual inspection on a regular basis of all modules for safe
electrical connections, sound mechanical connections, and free from corrosion.
This visual inspection should be performed by trained personnel. The standard
frequency is once a year according to environmental conditions, periodic
cleaning of modules is recommended but is not required. Periodic cleaning has
resulted in improved performance levels, especially in regions with low levels
of annual precipitation (less than 46,3cm (18,25 inches)). Consult your dealer
or supplier about recommended cleaning schedules for your area. To clean a
module, wash it with potable, non-heated, water. Normal
water pressure is more than adequate, but pressurized water up to 100 bar
(min.50 cm distance) may be used. Maxeon recommends using a large hosepipe and
not performing cleaning at high outside temperatures. Fingerprints, stains, or
accumulations of dirt on the front surface may be removed as follows: first,
rinse off the area and let soak for a short period of time (5 mins). Re-wet
and use a soft sponge or seamless cloth to wipe glass surface in a circular
motion. Fingerprints typically can be removed with a soft cloth or sponge and
water after wetting. Do not use harsh cleaning materials such as scouring
powder, steel wool, scrapers, blades, or other sharp instruments to clean the
glass surface of the module. Use of such materials or cleaning without
consultation will invalidate the product warranty. As dry cleaning is also
risky for Anti-Reflective (AR) coated module surfaces, a spinning brush is not
recommended for module cleaning.
Table 2: Module Frame Details
Measurement Tolerances are +/-3 mm for the Length and Width of the Module.
Contents of this manual are subject to change without notice. In case of
inconsistencies or conflicts between the English version and any other
versions of this manual document), the English version shall prevail and take
control in all respects. For the latest Europe, Asia, Australia, Latin
America, and Africa please refer to
www.sunpower.maxeon.com/int/PVInstallGuideIEC
Maxeon Solar Technologies, Ltd.
www.sunpower.maxeon.com
References
- Global Solar Energy Company | Solar Panels | Maxeon US
- Solarmodulhersteller in Deutschland | SunPower Germany
- Compañía de paneles solares en España | SunPower España
- Entreprise d'énergie solaire | Panneaux solaires | SunPower France
- Società di energia solare | Pannelli solari | SunPower Italia
- 産業用・住宅用ソーラーパネル | マキシオン | Maxeon Japan
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>