RF solutions PRO-EZTEXT26 2 IP 6 OP Channel Remote Control System Instruction Manual
- June 5, 2024
- RF SOLUTIONS
Table of Contents
- RF solutions PRO-EZTEXT26 2 IP 6 OP Channel Remote Control System
- Features
- Applications
- Description
- Ordering Information
- Safety Information
- Electrical Safety
- Optional External Antenna
- Using Additional Input / Output Modules
- Insert SIM Card
- User Set-Up Commands
- System Commands
- Technical Specifications
- Disclaimer
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
RF solutions PRO-EZTEXT26 2 IP 6 OP Channel Remote Control System
Features
- Two way remote control Via SMS Text
- Easy to install and configure using only SMS text messages
- Modular Expandable System
- 2-18 digital inputs (volt free)
- 2-18 Relay Changeover contacts rated 240Vac 5A
- Text on Power Restore
- Integral Antenna supplied (External Option) Optional Temperature Sensor
- User can set inputs and outputs names Worldwide quad-band GSM.
- O2 SIM Card Included
Applications
- Plant Maintenance
- Warnings / Alarms/ Reset
- Irrigation Systems
- Security Systems
- Heating Control
- World-wide Telemetry Signals
Description
A GSM Remote Control System operated by SMS text message. Available as DIN Rail Modules or a ready made System within an IP56 enclosure Mains power supply and bundled SIM card ready to go. The user can switch the relay changeover contacts by sending a simple or custom text of their choice. EZTEXT will send an SMS text to up to five numbers on activation of one of its inputs or temperature set points. The user can give custom names to Inputs/outputs and create Custom messages. Setup is easy with a few simple SMS Text Commands.
Ordering Information
- PART No Description
- EZTEXT-DIN DIN Rail SMS Control System
- PRO-EZTEXT26 2 IP 6 OP Channel Remote Control System
Safety Information
Carefully read the following safety information before proceeding with installation, operation, or maintenance of RF Solutions product. Failure to follow these warnings could result in death or serious injury
- This radio system must not be used in areas where there is a risk of explosion.
- Only qualified personnel should be permitted to access the transmitter and operate the equipment.
- Always follow operating information as well as all applicable safety procedures and requirements.
- You must satisfy the age requirements in your country for operating the equipment.
- Store in a safe place.
- Keep a clear view of the work area at all time before using, check it is safe to do so
Before maintenance intervention on any remote controlled equipment
- Do not open the receiver enclosure unless you are qualified.
- Disconnect all electrical power from the equipment.
- Check the enclosure and cable for damage regularly, do not use if there is evidence of damage
Electrical Safety
ISOLATE the mains electricity supply before removing the cover and observe any relevant safety information.
- Maintenance to the product that involves removal of the cover should only be carried out by a competent person or qualified electrician.
- Ensure adequate protection on the Load circuit
- Refer to Product Datasheet for MAX operating Load.
- Product must be installed in accordance with the local country electrical regulations.
- A current limiting supply must be used in accordance with the datasheet
- 110-230Vac Power Supply Fused 5A
- 2 No Volt Switch inputs
- 6 Outputs Relay Changeover Contacts 240Vac 5A
- Enclosure IP56
- No PC required.
- SIM Card Bundled
- Dims 315 x 235 x 130mm
Supplied as a self contained two way Remote Control System which provides two ‘no volt’ switch detect inputs and 6 changeover relay contacts as outputs. The system comes supplied in an IP56 Enclosure with integral 12V power supply. Containing industrial standard ‘DIN Rail’ modules
Additional Input and Output Modules
The Add-on Modules simply plug into the EZTEXT-DIN Ribbon Connector socket.
Once connected the EZTEXT automatically recognizes them and the additional
inputs and outputs become available to use.
4 x Inputs Module
- 4 x Additional No-Volt Inputs
- Plug ‘n’ Play using ribbon cable supplied
- Up to 4 additional Input Modules can be Daisy Chained to provide 16 additional Inputs
- Inputs are opto-isolated
Part Number Description
725-IP 4 input Add-on Module
4 x Relay Output Module
- 4 x Relay Changeover Contacts
- Connecting ribbon cable supplied
- Up to four Output Modules can be Daisy Chained to provide an additional 16 Outputs.
- Up to 4 x 725-OP can be Daisy Chained to provide 18 outputs.
- Provides a simple extension to the number of Inputs
Part Number Description
725-OP 4 Output Add-on Module
Temperature Measurement Probe Cable
Using the cable adaptor CBA-EZTEMP provides a 1metre plug in cable with
temperature probe. This enables the EZTEXT temperature monitor temperature and
automatically send notification of high and low user selectable trigger level.
Part Number Description
CBA-EZTEMP2 Temperature sensor cable
Optional External Antenna
Using an external antenna can provide a better signal reception than the on- board antenna. Using Cable adaptor CBA-UFLSMA provides a panel mounted SMAconnector for external antenna connection. To connect, carefully unplug the existing antenna UFL and push on the CBA-UFLSMA UFL connector.
ANT-GSM5WM
A compact PCB Antenna for GSM Cellular applications where high performance is
required from a small size. Using the ANT-GSMQB will give optimum range and
reliability to your application
ANT-GSMPUKS-IP67
A compact Antenna for GSM applications where high performance is required
from a small size. The antenna includes a Low Noise Amplifier and is housed in
a rugged low profile UV resistant case, this antenna is compact and resistant
to Vandalism
Part Number Description
ANT-GSMPUK-SMA +3dBm Gain antenna Rugged PUCK
Alternative Antenna
We offer an extensive range of GSM antenna in many shapes and sizes please see
our Website or contact our Sales Dept with your requirements and we will try
to help.
Using EZTEMPR2 Thermocouple
Attach the Thermocouple cable to the Connector marked “SENSE” This is now
ready to use:
Notes:
- Temperatures are measured to 1 Decimal point
- Temperature Triggers can be set to whole number values only
- A hysteresis of –2oC is built into the EZTEXT
Example 1
SET TEMP MAX is set to +30oCAs the actual temperature measured increases,
EZTEXT will trigger ‘over Temperature’ at 30.1oC As the actual temperature
measured decreases EZTEXT will trigger at 27.9oC
Example 2
SET TEMP MIN is set to +10oC As the actual temperature measured decreases,
EZTEXT will trigger ‘under Temperature’ at 9.9oC As the actual temperature
measured increases EZTEXT will trigger ‘Good’ at 12.1oC
Using Additional Input / Output Modules
Input and Output modules can be added in any order by connecting with theRibbon cables supplied. On initial Powerup EZTEXT automatically interrogates and configures additional modules. (all LEDS Flash). After approx. 60seconds the LEDs stop flashing to indicate the module is ready to use
Notes:
- Any combinations of 725-IP and 725-OP modules can be added, the Maximum is four, 725-IP Modules and four 725-OP modules in the ‘Daisy Chan’ link (8 modules in total)
- When using 725-IP / OP modules there are some limitations (compared with the two input and outputs on the ETEXT-DIN)
725-OP Additional 4 Outputs Module
- Each 725-OP module must have a different address Link setting to other 725-OP modules (For the application shown address Link 2 is fitted this sets the outputs to be numbers 7-10)
- Each Relay Changeover contacts Output can only be switched “On” or “Off”.
- Functions such as time delays cannot be used.
- A single telephone OPNUM number applies per output
Example : the number allocated to an output board that you would use to send a text message to activate an output
Insert SIM Card
Please note:
- Insert NANO SIM Card before applying power (standard 3 Volt SIM only).
- The message memory of the SIM card should be clear before it is fitted.
- Ensure that the SIM card has not been PIN code protected!
- Beware of Pay-as-you-go SIM which require regular top-up to remain active.
- It is recommended to bar Incoming voice calls to the SIM card to avoid error messages being sent back to the user. This can be achieved with the service provider.
The SIM card should be inserted into EZTEXT-DIN before applying power
- RF Solutions recommends O2 and Vodaphone SIM card and has carried out extensive testing using the SIM cards we have for these two networks.
- No guarantee can be given for the operation of this product with any network except those that have been tested by RF Solutions.
Connect Inputs/Outputs and Power Connections
The EZTEXT-DIN unit can be powered from 12 to 24Vdc
LED Indication At Start Up
LED Indication After Start Up (Normal Operation)
Error Messages & Factory Reset
There are three error messages
- NO AUTHORISATION Means that EZTEXT did not accept the password
- UNRECOGNIZED COMMAND Password correct but the command isincorrect
- UNRECOGNIZED VARIABLE Password and command OK but the variable data is incorrect
Factory reset:
Hold down the RESET button for approx10 seconds until all LEDs flash, then
release. This will reset EZTEXT to factory default settings and restart.
User Set-Up Commands
INPUT Commands
Output Commands
Power Fail Commands
Temperature Commands
System Commands
Technical Specifications
- Storage Temperature: -10 to +70˚C.
- Operating Temperature: 0 to +55˚C.
- EZTEXT Dimensions: 136 x 78 x 42 mm
Notes
Figures refer to maximum supply current required with all components idle.
Figures refer to peak supply current required with all components operating.In
practice internal reservoir capacitance limits the instantaneous peak current
to less than 500 mA. Temperature accuracy +/- 0.5 degrees between –10 to
+80-degree Centigrade +/- 2.0 degrees between –55 to +110-degree Centigrade
The relay contacts in this unit are for functional switching only and must not
be used for isolation purposes Hereby, RF Solutions Limited declares that the
radio equipment type defined within this document is in compliance with
Directive 2014/53/ EU. The full text of the EU declaration of conformity is
available at the following internet address:
www.rfsolutions.co.uk
RF Solutions Ltd. Recycling Notice
Meets the following EC Directives:
DO NOT
Discard with normal waste, please recycle.
ROHS Directive 2011/65/EU as amended by 2015/863/EU
Specifies certain limits for hazardous substances.
WEEE Directive 2012/19/EU
Waste electrical & electronic equipment. This product must be disposed of
through a licensed WEEE collection point. RF Solutions Ltd., fulfills its WEEE
obligations by membership of an approved compliance scheme. Environment agency
registration agency number: WEE/JB0104WV.
Disclaimer
Whilst the information in this document is believed to be correct at the time of issue, RF Solutions Ltd does not accept any liability whatsoever for its accuracy, adequacy or completeness. No express or implied warranty or representation is given relating to the information contained in this document. RF Solutions Ltd reserves the right to make changes and improvements to the product(s) described herein without notice. Buyers and other users should determine for themselves the suitability ofany such information or products for their own particular requirements or specification(s). RF Solutions Ltd shall not be liable for any loss or damage caused as a result of user’s own determination of how to deploy or use R F Solutions Ltd’s products. Use of RF Solutions Ltd products or components in life support and/or safety applications is not authorised except with express written approval. No licences are created, implicitly or otherwise, under any of RF Solutions Ltd’s intellectual property rights.Liability for loss or damage resulting or caused by reliance on the information contained herein or from the use of the product (including liability resulting from negligence or where RF Solutions Ltd was aware of the possibility of such loss or damage arising) is excluded. This will not operate to limit or restrict RF Solutions Ltd’s liability for death or personal injury resulting from its negligence.
RF Solutions Ltd
William Alexander House, William Way, Burgess Hill, West Sussex, RH15 9AG
Sales: +44 (011444 227900 Support: +44 (01444 227909
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>