SENECA R-8AI-8DIDO IO module analog inputs 8 digital Installation Guide

June 5, 2024
SENECA

SENECA R-8AI-8DIDO IO module analog inputs 8 digital

SENECA R-8AI-8DIDO IO module analog inputs 8 digital
PRODUCT

PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that put the user’s safety at risk. The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

WARNING
The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available using the QR CODE. The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation. Electrical and electronic waste disposal applicable in the European Union and other countries with recycling. The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.

R-8AI-8DIDO DOCUMENTATION

SENECA R-8AI-8DIDO IO module analog inputs 8 digital 1
SCAN R-8AI-8DIDO-P DOCUMENTATION

MODULE LAYOUT

SENECA R-8AI-8DIDO IO module analog inputs 8 digital 1

  • Weight: 170 g
  • Enclosure: UL94-V0 self extinguishing..
  • PC/ABS material black.

SIGNALS VIA LED ON FRONT PANEL

LED STATUS LED meaning
PWR On Device powered
Off Device not powered
IO1/IO8 On Digital input/output active
Off Digital input/output not active
OUT SUP On Digital inputs/outputs powered
Off Non-digital inputs/outputs powered

STS

(Status)

| On| IP address set
Flashing| Waiting for the IP address from the DHCP
COM

R-8AI-8DIDO-P version only

| On| Verification of RS485 connection
Flashing| Data packet transmission over RS485
FAIL| On| Digital output in FAIL
Off| Digital output OK
RX

R-8AI-8DIDO version only

| On| RS485 port wiring error
Flashing| Reception of data packet completed on RS485
TXR-8AI-8DIDO version only| Flashing| Reception of data packet completed on RS485
ETH TRF Yellow| Flashing| Packet transit on Ethernet port
ETH LNK Green| Flashing| Ethernet port connected

TECHNICAL SPECIFICATIONS

CERTIFICATIONS

|

https://www.seneca.it/products/r 8ai 8dido/doc/CE declaration

---|---

INSULATION

|
POWER SUPPLY| Voltage: 10÷40 Vdc; 19÷28 Vac; 50÷65 Hz; Absorption: 3 W

ENVIRONMENTAL CONDITIONS

| Operating temperature: from -25°C to +65 °C Humidity: 10%– 90% non condensing.

Storage temperature: from -30°C to +85 °C

Protection rating: IP20

ASSEMBLY| 35mm DIN rail IEC EN60715
CONFIGURATION| With integrated WEB Server R-8AI-8DIDO version only
CONNECTIONS COMMUNICATION PORTS| 3.5 mm pitch terminal block, 1.5 mm2 max cable section

1 micro USB port for programming R-8AI-8DIDO version only 2 Ethernet (with LAN fault-bypass function 100 base T on RJ45

RS485 port on terminals R-8AI-8DIDO version only

AUXILIARY VOLTAGE OUTPUT| Max voltage/current: 12 Vdc / 20 mA
DIGITAL INPUTS| Number of channels: 8; Voltage: Threshold ON: > 9 V; Threshold OFF: < 4 V; Vmax: 24 V

Impedance 9 kΩ

DIGITAL OUTPUTS| Number of channels: 8, MOSFET, PNP Max voltage/current: 0.2 A / 24 V

ANALOGUE INPUT

| Number of channels: 8; Type: voltage, current, thermocouple, thermoresistance Measuring range: Voltage: -30 V ÷ -30 V; -120m V ÷ +120 mV

Current: -24 mA ÷ +24 mA Thermocouple: J, K, T, E, N, R, S, B, L. Thermoresistance: PT100: -200 °C ÷ +200 °C only for cold junction offset

ELECTRICAL CONNECTIONS

The upper power supply limits must not be exceeded, as this could cause serious damage to the module. Switch the module off before connecting inputs and outputs. To meet the electromagnetic immunity requirements use shielded signal cables; connect the shield to a preferential instrumentation earth system;  separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc.

POWER SUPPLY| | RS485 SERIAL PORT

Connection to the RS485 port. Polarity is not standardised and in some devices may be inverted.

| CURRENT mA

Passive transmitter,with external power supply

---|---|---|---
| |

| |
| | The relative dip switch goes to the ON position
| |

ANALOGUE INPUTS

The device has 8 analogue inputs that can be configured via DIP SDWITCH

mA

Transmitter active


The relative dipswitch goes to the ON position

| VOLTAGE V ±30V



The relative dip-switch goes to the OFF position

| THERMOCOUPLE Tc mV


The relative dip-switch goes to the OFF position

---|---|---
DIGITAL INPUTS PNP| | DIGITAL INPUTS PNP| | DIGITAL OUTPUTS PNP

With external power

The digital outputs must be powered

externally to function properly.

With external power| | With internal power|
| | |
| | |
| | |
| | |
| | |
| | |
| | |

CAUTION
The input for the RTD thermoresistance is available only for the first channel. For channels 2 to 8 it is not available.

WARNING
The product is not suitable for connection to a dangerous voltage conductor. The maximum allowable voltage is 50 Vac.

THERMORESISTANCE

The relative dip-switch goes to the OFF position. Function valid only for analogue input 1.

INSTRUCTIONS FOR ANALOGUE INPUTS

SENECA R-8AI-8DIDO IO module analog inputs 8 digital
15

The analogue inputs of this device are designed to measure voltages/currents on floating circuits that is not electrically connected to each other. It is also possible to measure
currents/voltages on non-floating circuits, with a potential difference between negative terminals not exceeding 200 mV. In the case of measurement with thermocouples it is possible to obtain correct measurements even if they are applied to common metal parts. The temperature measurement using thermocouples can be affected by measurement errors due to the determination of the cold junction temperature carried out near the terminal. To eliminate any measurement errors it is necessary to wir  the thermocouples on an isothermal terminal board separate from the device.Input No. 1 set as Pt100 will then be used to measure the cold junction temperature of said terminal block.

FEATURE SUMMARY

ANALOGUE INPUTS

| Range| Resolution| Impedance| Precision| Temperature drift| Ext. current
Voltage (V)| -30+30 Vdc| 1 mV| > 200 kohm| 0.1% f.s.| 100 ppm|
Voltage (mV)| -120+120 mV| 4 uV| > 10 Mohm| 0.1% f.s.| 100 ppm|
Current (mA)| -24..-+24 mA| 0.8 uA| 20 Ohm| 0.2% f.s.| 100 ppm|
Thermocouple| -120+120 mV| 4 uV| > 10 Mohm| 0.1% f.s.| 100 ppm|
PT100| -200..200 °C| 0.05 °C| | 0.5°C| 50 ppm| 0.5 mA
THERMOCOUPLE TYPE

| Range °C| Resolution °C| Impedance Mohm| Precision f.s.| Temperature Drift| Standard| cold junction error °C
J| -210..1200| 0.1| > 10| 0.1%| 100ppm| EN 60584| 2
K| -200..1372| 0.1| > 10| 0.1%| 100ppm| EN 60584| 2
T| -200..400| 0.1| > 10| 0.1%| 100ppm| EN 60584| 2
E| -200..1000| 0.1| > 10| 0.1%| 100ppm| EN 60584| 2
N| -200..1300| 0.1| > 10| 0.1%| 100ppm| EN 60584| 2
R| -50..1768| 0.3| > 10| 0.1%| 100ppm| EN 60584| 2
S| -50..1768| 0.5| > 10| 0.1%| 100ppm| EN 60584| 2
B| 250..1820| 0.5| > 10| 0.1%| 100ppm| EN 60584| 2
L| -200..800| 0.1| > 10| 0.1%| 100ppm| GOST:8.585| 2

SETTING THE DIP SWITCHES

The DIP-SWITCHES on the back of the device have the following functions:

DIP-SWITCH SW1 AND SW2

ANALOGUE INPUT/OUTPUT CONFIGURATION

SW1 SW2
1 2
AI1 AI2
SW3 DIP-SWITCH

DEFAULT SETTINGS

SW3

DI1| ON| DEFAULT SETTINGS
DIP1| ON

DIP SWITCH positions

SENECA R-8AI-8DIDO IO module analog inputs 8 digital
16

DAISY CHAIN ETHERNET CONNECTION

CAUTION
IT IS NOT ALLOWED TO CREATE LOOPS WITH ETHERNET CABLES. Using the daisy chain connection it is not necessary to use switches to connect the devices.
The following examples show the correct connections.

SENECA R-8AI-8DIDO IO module analog inputs 8 digital
17

There must be no loops in the Ethernet cabling, otherwise the communication will not work. The modules and switches must be connected eliminating any loops. The following examples show the incorrect connections.

SENECA R-8AI-8DIDO IO module analog inputs 8 digitalKKThe LAN fault bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the event of a power failure. If a device turns off, the chain is not interrupted and the devices downstream of the switched-off one will still be accessible. This function has a limited duration: the connection remains active for a few days, typically .The fault-bypass function requires that the sum of the lengths of the two cables connected to the switched off module is less than 100m

ETHERNET CONNECTION RULES

For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required.

FACTORY IP ADDRESS
The default module IP address is static: 192. 168. 90. 101

WEB SERVER
To access the maintenance Web Server with the 192.168.90.101 factory IP address Default user: admin; Default password: admin http://192.168.90.101

CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SENECA User Manuals

Related Manuals