SENECA Z-KEY Gateway ModBUS Instruction Manual
- June 4, 2024
- SENECA
Table of Contents
SENECA Z-KEY Gateway ModBUS
PRELIMINARY
WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that
put the user’s safety at risk. The word ATTENTION preceded by the symbol
indicates conditions or actions that might damage the instrument or the
connected equipment. The warranty shall become null and void in the event of
improper use or tampering with the module or devices supplied by the
manufacturer as necessary for its correct operation, and if the instructions
contained in this manual are not followed.
| WARNING : The full content of this manual must be read before any operation. The module must only be used by
qualified electricians. Specific documentation is available via QR-CODE shown on page 1.
---|---
| The module must
be repaired and damaged parts replaced by the Manufacturer. The product is
sensitive to electrostatic discharges. Take appropriate measures during any
operation.
| Electrical and electronic waste disposal (applicable in the European Union
and other countries with recycling). The symbol on the product or its
packaging shows the product must be surrendered to a collection centre
authorized to recycle electrical and electronic waste.
-
DOCUMENTATION Z-KEY
-
DOCUMENTATION Z-KEY-P
CONTACT INFORMATION
Technical support| support@seneca.it| Product
information| sales@seneca.it
---|---|---|---
This document is the property of SENECA srl. Copies and reproduction are
prohibited unless authorised. The content of this document corresponds to the
described products and technologies. Stated data may be modified or
supplemented for technical and/or sales purposes.
MODULE LAYOUT
Dimensions: 17.5 x 102.5 x 111 mm, Weight: 100 g; Enclosure: PA6, black
SIGNALS VIA LED ON FRONT PANEL
LED | STATUS | LED meaning |
---|---|---|
PWR | ON | The device is powered correctly |
SD / COM
Z-KEY version only
| Flashing| Accessing the microSD card
SD / COM
Z-KEY-P version only
| Flashing| Profinet communication active
Off| No Profinet communication
TX1| Flashing| Data transmission on port #1 RS485
RX1| Flashing| Data receipt on port #1 RS485
TX2| Flashing| Data transmission on port #2 RS485/RS232
RX2| Flashing| Data reception on port #2 RS485/RS232
ETH ACT Green| Flashing| Packet transmission on Ethernet port
ETH LNK Yellow| ON| Ethernet connection present
TECHNICAL SPECIFICATIONS
STANDARDS| EN61000-6-4 Electromagnetic emissions, industrial environment. EN61000-6-2 Electromagnetic immunity, industrial environment. EN60950-1 Security in information processing equipment
Additional notes: a 1 A delayed fuse must be installed near the module, in series with the power supply connection.
---|---
INSULATION|
ENVIRONMENTAL CONDITIONS| T emperature :
-25 °C – + 65 °C
Humidity : 30%– 90% non condensing.
Altitude: Up to 2000 m above sea level
Storage temperature: -30 °C – + 85 °C
Protection rating: IP20 (Not evaluated by UL)
ASSEMBLY| IEC EN60715, 35mm DIN rail in vertical position.
CONNECTIONS| 3-way removable screw terminals, pitch 5 mm Rear connector
IDC10 for DIN bar 46277 RJ45 front connector
SMA antenna connector side micro USB port
microSD card slot
POWER SUPPLY| Voltage: 11 – 40 Vdc; 19 – 28 Vac 50 – 60 Hz Absorption:
Max. 1,5W
COMMUNICATION PORTS| RS242 or RS485 switchable on terminal 10 – 11
– 12
Maximum Baud rate 115 k, maximum cable length RS232 < 3m
RS485 IDC10 rear connector : Maximum Baud rate 115 k.
RJ45 front Ethernet connector : 100 Mbit/s, maximum distance 100 m
ATTENTION
The device may only be powered by a power supply unit with a limited energy
electric circuit max. 40Vdc / 28Vac Max output in accordance with
CAN/CSA-C22.2 No. 61010-1-12 / UL Std. No. 61010-1 (3rd Edition) chapter
6.3.1/6.3.2 and 9.4 or class 2 according to CSA 223/UL 1310.
FACTORY IP ADDRESS
The default module IP address is static: 192.168.90.101
WEB SERVER
To access the maintenance Web Server with 192.168.90.101 factory IP address:
Default user: admin, Default password: admin, http://192.168.90.101
IDC10 CONNECTOR
The illustration
shows the meanings of the various IDC10 connector pins if signals are to be
sent via them directly.
SETTING THE DIP-SWITCHES
SETTINGS OF FACTORY PARAMETERS
This procedure returns the IP to the factory one (192.168.90.101) and the Web
Server/FTP server access credentials to user: admin and password: admin.
KEY
1| ON| | |
0| OFF|
- Turn the module off and set all eight SW1 DIP-switches to ON.
- Turn on the module and wait 10 seconds.
- Turn the module off and set all eight SW1 DIP-switches to OFF.
RS232/RS485 SETTING: RS232 or RS485 configuration on terminals 10-11-12 (serial port 2)
SW2
1| ON| | RS232
ACTIVATION
0| OFF| | | | RS485 ACTIVATION
INSTALLATION REGULATIONS
The module has been designed for vertical installation on a DIN 46277 rail.
For optimal operation and long life, adequate ventilation must be provided.
Avoid positioning ducting or other objects that obstruct the ventilation
slots. Avoid mounting modules over heat-generating equipment. Installation in
the bottom part of the electrical panel is recommended.
ATTENTION
These are open-type devices and intended for installation in an end enclosure
/ panel offering mechanical pro-tection and protection against spread of fire.
ELECTRICAL CONNECTIONS
CAUTION
To meet the electromagnetic immunity requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc…).
POWER SUPPLY
| SERIAL PORT 2: RS485 SW2 = OFF
|
SERIAL PORT 2: RS232 SW2 = ON
---|---|---
ATTENTION
Use only copper or copper-clad aluminium or AL-CU or CU-AL conductors