HOMCOM 821-030V70WT Portable Dehumidifier Instruction Manual

June 13, 2024
HOMCOM

HOMCOM 821-030V70WT Portable Dehumidifier Instruction Manual
HOMCOM 821-030V70WT Portable Dehumidifier

Thank you for choosing this dehumidifier. Please read this instruction manual carefully before installing this appliance. Keep this manual safe for future reference.

Read all instructions carefully before using or repairing this dehumidifier.

The refrigerant used in this dehumidifier is the environmentally friendly hydrocarbon R290, which is odourless and ozone-free.

Note: Drawings provided in the manual may differ from the actual appliance, so please refer to the actual appliance for accurate information.

SECURITY WARNINGS

  • Do not use any methods, which are not recommended by the manufacturer, to speed up defrosting or cleaning.
  • Store the appliance in a room WITHOUT continuous ignition sources, such as open flames, operating gas appliances or electric heaters.
  • Do not puncture or burn the appliance.
  • Note that refrigerants may not have an odour.
  • Ensure the appliance is installed, operated and stored in a room with a floor area larger than 2m².
  • Do not obstruct any required ventilation openings.
  • Only service the appliance as recommended by the manufacturer.
  • Store the appliance in a properly ventilated area, where the room size corresponds to the specified operation area.
  • Anyone working on breaking into a refrigerant circuit should have a currently valid certificate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely.
  • Maintenance and repair requiring the assistance of other skilled personnel should be supervised by someone competent in the use of flammable refrigerants.
  • All work affecting safety equipment must be carried out by competent individuals.
  • When moving the appliance, be careful to avoid bumping and causing leakage in the refrigeration line.

Flammable material. This appliance contains R290/ Propane a flammable refrigerant

Refer operators manual

Read technical manual

Read operators manual

Notes:

  • This dehumidifier is suitable for indoor use only. Do not use outdoors.
  • When installing the dehumidifier, follow local grid interconnection rules and ensure that it is properly grounded. For any questions on electrical installation, refer to the manufacturer’s instructions or consult with a professional electrician. If necessary, hire a professional electrician to install it for you.
  • Place the appliance on a flat, dry surface. Ensure there is at least 30cm of space between the appliance and surrounding objects (walls, furniture, curtains, etc).
  • After the dehumidifier is installed, ensure the power plug is intact and firmly plugged into the power outlet. Place the power cord neatly to prevent someone from tripping over it or pulling it out of the socket.
  • Do not put any object into the air inlet and outlet of the dehumidifier. Keep the air inlet and outlet free from obstruction.
  • When installing drainage pipes, ensure they are properly connected and are not twisted or bent.
  • When moving the appliance, keep it in an upright position.
  • Keep the appliance away from gasoline, flammable gas, stoves and other heat sources.
  • Do not disassemble, overhaul or modify the appliance on your own. This can cause the machine to malfunction and may harm individuals or property. For damages or failure to the appliance, get the manufacturer or a professional to repair it. Attempting to repair the machine yourself can be dangerous.
  • Do not pull the cord to turn off the appliance.
  • To prevent water or other liquids from spilling into the air conditioning, do not place cups or other objects on the appliance.
  • Do not use insecticide sprays or other flammable substances near the dehumidifier.
  • Do not clean this appliance with chemical solvents, such as gasoline or alcohol. To clean the appliance, you must disconnect it from the power supply first, then clean it with a slightly damp cloth. If it is really dirty, scrub the appliance with a mild detergent.
  • Under guided supervision, this appliance can be used by children aged eight years and above, provided they understand the potential risks and hazards. Under guided supervision, this appliance can be used with persons with disabilities or persons without experience, provided they understand the potential risks and hazards.
  • Damaged supply cords must be replaced by the manufacturer, its service agent or similarly qualified personnel to avoid hazards.
  • Install this appliance following national wiring regulations.

Transportation, marking and storage for units

  • Transport: Comply with all transport regulations when transporting equipment containing flammable refrigerants.
  • Marking: Comply with local regulations for marking equipment with signs, which indicate the presence of flammable refrigerants.
  • Disposal: Comply with national regulations for the safe disposal of equipment containing flammable refrigerants.
  • Storage: Store equipment following manufacturer’s instructions, ensuring safe and effective operation.
  • Storage of packed equipment: Protect the equipment inside the package from mechanical damage, so it does not leak.

FUNCTION INTRODUCTION

This dehumidifier has three modes: dehumidify, air supply and clothes dryer. The fan has two adjustable wind speeds. The set humidity range is 35-85%RH. The ambient humidity display range is 30-90%RH (When the ambient humidity is below 30%, it displays 30%; when the ambient humidity is above 90%, it displays 90%).
The dehumidifier also features a 0-24 hour timing on/off function, a sensor that automatically detects ambient temperature and a ‘water full’ automatic protection function. The appliance operates within a working temperature range of 5-32°C . The working environment humidity range is 10-95%RH.

PRODUCT PARTS

PRODUCT PARTS

  1. Top cover
  2. Vane
  3. Front shell
  4. Chassis
  5. Wheels
  6. Control panel
  7. Back shell
  8. Filter
  9. Water tank
  10. Drain port

NOTE:
All the pictures in the manual are for explanatory purposes only. The actual shape of the unit you purchased may be slightly different, but the operations and functions are the same.

CONTROL PANEL

CONTROL PANEL

BUTTONS

  1. POWER button
    After the power is turned on, the indicator light will turn green.

  2. MODE button
    There are three working modes: Dehum, fan and laundry.

  3. DOWN button
    Reduce the humidity or timing.
    Hold this button for three seconds to activate the mould removal function. The ‘DRY INSIDE’ light will be on. This function only works when the power is on. If the function is on and the appliance is turned off later, the fan motor will stop working after a fiveminute delay (only the power indicator will be on during this process). This feature is off by default and needs to be manually activated.

  4. UP button
    Increase the humidity or timing.

  5. FAN SPEED button
    Press to select the high or low fan speed.

  6. TIMER button
    Press the timing key to set timer, query timer and to cancel the timer.

  7. CHILD-LOCK
    Press ‘TIMER’ and ‘FAN SPEED’ at the same time to start and stop the child- lock function.

  8. Compound key
    Press ‘UP and ‘DOWN’ at the same time to start and stop the viewing temperature function. When turned on, the temperature indicator light is on, the digital tube displays the ambient temperature, then it automatically switches to the humidify display after displaying for 10 seconds.

OPERATIONS

  • Ensure the unit’s power matches the local power grid.

  • Press both sides of the swing to manually adjust the swing leaf to the desired angle.
    OPERATIONS

WORKING MODES

DEHUMIDIFY MODE

When turned on for the first time, its default mode is the dehumidify mode – this can also be selected through the mode selection. The default humidity setting is 40% – this will be shown on the display. The high wind setting will also be activated.

  • When the relative humidity (Hr) exceeds the set humidity (Hs) by 3% or more, the compressor starts and the fan operates at the set wind speed. When Hr is lower than Hs by 3% or more, the compressor stops and the fan automatically switches to low wind speed (the wind speed can be adjusted at any time). When Hr is within 3% of Hs, the dehumidifier remains in its current operating state
  • The set humidity (CO-35-85%RHY) is displayed. You can adjust the setting by pressing ‘UP’ and ‘DOWN’.
  • The fan speed is adjustable.
  • Child-lock and timer functions can be set.
  • When the ambient humidity is below the set humidity, the red ‘OK’ indicator light on the display panel will be off. When the ambient humidity reaches the set humidity, the red ‘OK’ light on the display panel will be on.
  • When the humidity is set to ‘CO’, the compressor runs continuously without being limited by the set humidity (ensuring a three-minute delay protection for the compressor). The fan speed is adjustable – the display will show ‘CO’. Child-lock and timer functions can be set in this mode.

FAN SPEED

  • Enter the air supply mode through the mode conversion (the compressor will not operate). The default fan speed is low, but it can be adjusted. The display will show the ambient humidity range of 30-90%RH.

LAUNDRY MODE

  • Enter the drying mode through the mode conversion (the dehumidifier runs continuously without being limited by the set humidity). The default fan speed is high, which cannot be adjusted. The display will show the ambient humidity
    LAUNDRY MODE 

FUNCTIONS

TIMER FUNCTION

  • Press the timer button to start this function. You can set the timer and query timer. Press again to cancel the timer.
  • When entering this function, the timer light will be on and the digital tube will flash five times to display the timer. During the flashing, press ‘UP’ or ‘DOWN’ to set the timer between 0-24 hours. The selected time will be confirmed after the display flashes five times.
  • When in this function, press the TIMER button for the query timer. The digital tube will flash five times to display the timer. Press the TIMER button again during the flashing period to cancel the timer.
  • When the timer is set, the timer indicator light will be on. After the time is up, the indicator will turn off.
  • Setting the on/off timer will not affect the current on/off state of the dehumidifier. The timer function is only valid for the next scheduled operation and can only be set once. If you manually turn the appliance on/off, all timer settings will be cleared.

CHILD LOCK FUNCTION

  • Press the ‘TIMER’ and ‘FAN SPEED’ buttons simultaneously to activate the child-lock function. The child-lock indicator light will be on and all buttons will be disabled. Press ‘TIMER’ and ‘FAN SPEED’ again to deactivate the function. The indicator light will turn off.

WATER FULL ALARM FUNCTION

When the water tank is full (detected by the water switch being disconnected) for five seconds, the dehumidifier will turn off completely. The alarm will sound five times, the ‘water full’ light will be on and ‘FL’ will flash on the display. This will continue until the water is emptied from the tank.

DRAINAGE

To empty the water tank, place your hand on the depression at the bottom of the tank and gently remove it. Tilt the tank and pour out the water through the drain. After emptying the tank, carefully push it back into its correct position. Then, turn on the dehumidifier again.

NOTE: Ensure the tank is emptied before placing it back into the appliance. Ensure the cover and tank are securely installed and the handle is back in its original position. Gently push the tank into its correct position using both hands.
FUNCTIONS

For continuous drainage:

  • Connect a continuous drainage pipe (inner diameter: 10mm).
  • This pipe does not come with the appliance. It must be purchased separately.
  • This is ideal if you do not want to drain the tank frequently.
    1. Step 1: Locate the drain at the back of the appliance.
    2. Step 2: Use a drain pipe that is a suitable length to firmly connect it to the drain port.
    3. Step 3: Before use, ensure the water pipe is firmly connected to prevent water leakage
      FILTER CLEANING

FILTER CLEANING

Note: The machine is equipped with a removable and washable filter. Remove the filter, put it in water to clean or rinse, then place it back. It is recommended to clean at least once every two weeks.
If the filter is only slightly dirty, it can be cleaned with a vacuum cleaner.

If the filter is very dirty, wash it with warm water that does not exceed 40 C.

Note: The filter needs to dry naturally to prevent deformation. Never use a dryer.
Keep the filter away from alcohol, gasoline, benzene and other chemical solvents.

MAINTENANCE

  • Before cleaning and maintenance, unplug the appliance to avoid electric shock.
  • If not in use for long periods, unplug the appliance.
  • Do not use alcohol, gasoline, benzene and other chemical solvents to clean the appliance.

Cleaning the appliance:
For cleaning the water tank, use cold or warm water to rinse out any remaining water to prevent mould. If the appliance is really dirty, use a mild detergent to clean it.

Nylon filter cleaning
The filter should be cleaned once every two weeks, using water that does not exceed 40℃.

Storage
After drained and cleaned, place the power cord in the water tank. Pack the unit inside a plastic bag to avoid dust and other debris.

TROUBLE SHOOTING

If the following problems occur with the dehumidifier, please check the machine and solve the problem as follows.

Trouble Cause Remedy
The appliance produces hot air. Dehumidifier’s cold air turns hot by absorbing
heat in the compressor. This normal. No action needs to be taken.
The unit does not turn on. Unit is not connected to the mains. Connect the

unit to the mains.
Water tank is full. Water tank is incorrectly installed.| Empty the water tank. Ensure the tank is properly installed.
Dehumidification does not work.| The room is already dry and cool.| During the dryer seasons, the capacity of the dehumidifier will be reduced
The air outlet or intake is blocked.| Clear the outlet or intake.
There is no wind.| Air filter is blocked.| Clean the filter as described in this manual.
The appliance is noisy.| The appliance is titled or unstable.| Put the unit upright on a flat and stable surface.
Filter is blocked.| Clean the filter as described in this manual.

NOTE:
Do not attempt to disassemble or repair the appliance yourself. Improper repairs can cause injury to persons and property damage. If there is a problem that is not listed or the solution did not work, please contact the manufacturer, its service agent or similarly qualified personnel.

Information on servicing:
Before working on flammable refrigerants, safety checks are necessary to minimise ignition risk.
The following precautions must be taken before repairing the refrigerating system.
To reduce the risk of flammable gas or vapour during work, a controlled procedure must be followed

  • Ensure all maintenance staff and others working in the area are aware of the work being carried out. Avoid working in confined spaces, section off the area around the workspace and ensure conditions within the area are safe.
  • To detect potentially flammable atmospheres, check the area with an appropriate refrigerant detector (non-sparking and tightly sealed) before and during work.
  • Have appropriate fire extinguishing equipment available if any hot work is being conducted.
  • Keep all possible ignition sources, including cigarette smoking, sufficiently far away from the site of installation, repair, removal and disposal, as flammable refrigerant could be released into the surrounding space. Before work, check the area around the equipment to ensure there are no flammable hazards or ignition risks. ‘No Smoking’ signs must be displayed in the working area.
  • Before breaking into the system or conducting hot work, ensure the area is in the open and properly ventilated, so any released refrigerant can be safely dispersed.
  • When changing electrical components, ensure they are fit for purpose and have the correct specification.
  • Follow the below maintenance and service guidelines. If in doubt, contact the manufacturer’s technical department for assistance.
  • Charge size must be appropriate for the room size where refrigerant-containing parts are installed.
  • Ventilation machinery and outlets must be functioning properly and not be obstructed.
  • If an indirect refrigerating circuit is used, check the secondary circuit for refrigerants.
  • Equipment markings should be visible and legible. Illegible markings and signs must be corrected.
  • Refrigeration pipes or components must be installed in a way that minimises exposure to corrosive substances.

During repairs and maintenance for electrical components, initial safety checks and inspections must be performed. If there is a fault that could compromise safety, the electrical supply must not be connected until the issue is resolved. If the fault cannot be fixed immediately, an adequate temporary solution should be used – the owner of the equipment must be informed.

Initial safety checks include:

  • Refrigeration pipes or components must be installed in a way that minimises exposure to corrosive substances.
  • During repairs and maintenance for electrical components, initial safety checks and inspections must be performed. If there is a fault that could compromise safety, the electrical supply must not be connected until the issue is resolved. If the fault cannot be fixed immediately, an adequate temporary solution should be used – the owner of the equipment must be informed.

Initial safety checks include:

a) Ensuring capacitors are safely discharged to avoid sparking.
b) Ensuring no live electrical components and wiring are exposed while charging, recovering or purging the system.
c) Ensuring there is continuity of earth bonding.

Repairs to sealed components:

  • When repairing sealed components, all electrical supplies must be disconnected from the equipment before removing sealed covers, etc. If it is absolutely necessary to have an electrical supply connected during servicing, then a permanent leak detection must be located at the most critical point to warn of any hazardous situations.

  • When working on electrical components, ensure the casing is not altered in any way.
    This includes damage to cables, an excessive number of connections, terminals not matching original specifications, damage to seals and incorrect fitting of glands. This is to ensure the level of protection is not affected. Ensure the apparatus is mounted securely.

  • Ensure the seals or sealing materials have not deteriorated to the point where they no longer stop flammable gases from getting inside.

  • Replacement parts must match the manufacturer’s specifications.
    NOTE: Using silicon sealant can interfere with some types of leak detection equipment. Intrinsically safe components do not need to be isolated before maintenance.

  • Repairing intrinsically safe components can be done while they are live in the presence of a flammable atmosphere.
    However, before applying any permanent inductive or capacitance loads to the circuit, ensure this will not exceed the permitted voltage and current for the equipment in use. Also, ensure the test apparatus is rated correctly. Do not work on non-intrinsically safe components in the presence of a flammable atmosphere.

  • Only replace components with parts specified by the manufacturer. Non-specified parts could release flammable components into the atmosphere.

  • Keep cabling away from sharp edges, vibrations and excessive pressure. Check for damages and wear and tear to the cabling.

  • Never use sources of ignition (halide torches or other naked flames) to search for refrigerant leaks. It is acceptable to use the following leak detection methods for systems containing flammable refrigerants:

    • Electronic leak detectors: Be aware, the sensitivity of electronic detectors may need to be recalibrated. Ensure the equipment is not a potential source of ignition. Equipment must be calibrated in a refrigerant-free area and set at a percentage of the LFL of the refrigerant, with a maximum of 25% gas.
    • Leak detection fluids: These can be used, but detergents with chlorine should be avoided to prevent corrosion of copper pipework.
    • If a leak is suspected, all naked flames must be removed and extinguished. If a refrigerant leakage is found that requires brazing, it must be removed from the system or isolated using shut-off valves in a remote part of the system. Oxygen-free nitrogen (OFN) should then be purged through the system before and during the brazing process.
  • When accessing the refrigerant circuit for repairs or any other purpose, it is crucial to follow proper procedures with safety in mind. To ensure the safety of the personnel involved, the following steps must be taken:

  1. Remove refrigerant.
  2. Purge the circuit with inert gas.
  3. Evacuate the circuit.
  4. Purge again with inert gas.

Open the circuit by cutting or brazing.
The refrigerant must be removed and collected in the correct cylinders. The system then needs to be flushed with oxygen-free nitrogen (OGN) until no refrigerant remains. This is done by filling the system with OFN, venting into the atmosphere and repeating until no refrigerant is left. Do not use compressed air or oxygen. This flushing process must be repeated several times and the charge of OFN must be vented into the atmosphere. It is important to make sure the vacuum pump outlet is not near any ignition sources and that there is enough ventilation available. Flushing is crucial before brazing the pipework.

Charging procedures
When charging a refrigeration system, it is important to follow these additional requirements:

  • Use charging equipment that prevents contamination of different refrigerants. Keep hoses or lis as short as possible, minimising the amount of refrigerant they contain.
  • Keep cylinders upright.
  • Before charging the system with refrigerant, ensure the refrigeration system is properly grounded.
  • Label the system after charging is complete (if it wasn’t labelled already).
  • Be careful not to overfill the refrigeration system.
  • Before charging the system, it should be pressure tested with OFN, ensuring it is safe and leak-free. After charging is complete but before commissioning, the system should be leak tested again. A final follow-up leak test should be conducted before leaving the site.

Decommissioning

Before performing this procedure, the technician must have a thorough understanding of the equipment and its specifications. All refrigerants must be recovered safely. Before starting the task, take samples of oil and refrigerant for analysis, in case further examination is needed before reusing the reclaimed refrigerant. It is important to ensure that electrical power is available before beginning the task

  • Become familiar with the equipment and its operation.

  • Isolate system electrically.

  • Before attempting the procedure ensure that:
    a) Mechanical handling equipment is available, if required, for handling refrigerant cylinders.
    b) All personal protective equipment is available and being used correctly.
    c) The recovery process is supervised at all times by a competent person.
    d) Recovery equipment and cylinders conform to the appropriate standards.

  • Using a pump, remove as much refrigerant as you can from the system.

  • If a vacuum is not possible, create a manifold that allows you to remove refrigerant from different parts of the system.

  • Before starting the recovery process, ensure the cylinder is placed on the scales.

  • Following the manufacturer’s instructions, start and operate the recovery machine.

  • Do not overfill the cylinders (no more than 80 % of the cylinder’s volume).

  • Do not exceed the maximum working pressure of the cylinder, even temporarily.

  • Once the cylinders are correctly filled and the process is complete, remove the cylinders and equipment from the site. Ensure all isolation valves on the equipment are closed.

  • Do not use recovered refrigerant in another refrigeration system, unless it has been thoroughly cleaned and checked.

Labelling
Label all equipment stating that it has been decommissioned and emptied of refrigerant. The label must be dated and signed.

Recovery

  • Ensure refrigerants are removed from a system in a safe manner.
  • When transferring refrigerant into cylinders, use appropriate refrigerant recovery cylinders, which are specifically designated for that purpose.
  • Ensure you have the correct number of cylinders to hold the total system charge.
  • Cylinders must be labelled for the specific refrigerant being recovered. Cylinders must be equipped with a pressure relief valve and working shut-off valves.
  • Before recovery, empty cylinders should be evacuated and, if possible, cooled.
  • Recovery equipment must be in good working condition, suitable for handling flammable refrigerants. It must come with proper instructions.
  • Calibrated weighing skills and hoses with leak-free disconnect couplings must be available and in good condition
  • Before using the recovery machine, ensure it is in good working condition, properly maintained and electrical components are sealed to prevent ignition in case of a refrigerant release.
  • If you have any doubts, consult the manufacturer.
  • Return the recovered refrigerant to the refrigerant supplier in the appropriate cylinder. A Waste Transfer Note should be arranged accordingly.
  • Never mix refrigerants in recovery units or cylinders.
  • To remove compressors or compressor oils, ensure they have been properly evacuated to remove any remaining flammable refrigerant from the lubricant. This should be done before returning the compressor to the supplier.
  • When draining oil from a system, it must be done safely and following proper procedures.

APPENDIX

Schematic diagram of the dehumidifier
APPENDIX

For specific technical parameters of the model, refer to rating label on the product.

Correct Disposal of this product Waste electrical products should not be disposed of with household waste.
Please recycle where facilities exist. Check with your local authority or retailer for recycling advise

If you have any questions, please contact our customer care center.
Our contact details are below:

0044-800-240-4004

enquiries@mhstar.co.uk

IMPORTER ADDRESS:
MH STAR UK LTD
Unit 27, Perivale Park,
Horsenden lane South
Perivale, UB6 7RH
MADE IN CHINA

HOMCOM logo

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals