SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
- June 9, 2024
- SIEMENS
Table of Contents
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD
Wireless room thermostat with LCD
Non-programmable, for heating systems
- 2-position or PID control to switch on/off heating systems
- Large LCD display
- Minimum and maximum setpoint limitation
- RDH100RF, transmitter, battery powered
- RCR100/433, receiver, mains powered
Use
The device comprises of 1 RDH100RF (transmitter) and 1 RCR100/433 (receiver), is used to control the room temperature in heating systems.
Typical applications:
-
Homes
-
Residential buildings
-
Schools
-
Offices
The device can be used together with the following equipment: -
Thermal valves or zone valves
-
Combi boilers
-
Gas or oil burners
-
Pumps
Functions
Temperature control
RDH100RF/SET offers both 2-position and PID intelligent learning temperature
control, configurable via parameter P01 (control behavior).
2-position control algorithm to switch on and off the heating system within a
switching differential (SD) as per the difference between setpoint setting and
measured room temperature.
PID intelligent learning control algorithm periodically switches on and off
the heating system.
The period time (T) and pulse length (P) of the control signal (PWM) are
determined by the setpoint and the measured room temperature.
In general, PID control provides more comfort and is more energy efficient than 2-position control.
Control behavior (P01)
The factory setting for control is “PID slow”, ideal for most heating systems. Optimum control can be selected if control does not provide the desired result:
2-position, 1 K
2-position controller with 1 [K] switching hysteresis
-
For systems with small capacity that appear slow
-
For applications requiring extended runtimes or where frequent switching causes problems
-
For difficult control loops where hunting may result
Typical applications: -
Dry floor heating systems
-
Heat pumps
-
Electric heating with contactors
2-position, 0.5 K
- 2-position controller with 0.5 [K] switching hysteresis.
- For general control situations. Provides better comfort than 1 [K] switching hysteresis.
- Can also be used for difficult control situations.
PID slow
PID control behavior for slow heating systems that require longer minimum
On times and a limited number of switching cycles per hour.
Typical applications:
- Wet floor heating systems, oil fired boilers
- Can also be used for all other types of heating applications. (Alternative setting)
Minimum switch on/off time | > 4 minutes |
---|---|
Minimum period | Approximately 12 minutes |
PID fast
PID control behavior for fast heating systems that tolerate a high number of
switching cycles.
Typical applications:
- Electric heaters with current valve
- Gas boilers
- Fast thermal actuators
Minimum switch on/off time | > 1 minute |
---|---|
Minimum period | Approximately 6 minutes |
WARNING
| Do not use PID fast for oil boilers or electric mechanical actuators!
Backup
When removing the batteries, the setpoints and information required for
operating mode changeover are retained for max. 2 minutes.
Commissioning notes
Parameter list
Parameter| Description| Factory setting| Setting range|
Remark
---|---|---|---|---
P01| Control behavior| PID slow (4)| 0 = 2P, 1.0 K
1 = 2P, 0.5 K
2 = PID fast 4 = PID slow
|
P02| Maximum temperature range| 30 °C| P03…30 °C| Limit of comfort and economy
setpoint
P03| Minimum temperature range| 5 °C| 5 °C…P02| Limit of comfort and economy
setpoint
End| Exit parameter setting| | |
Parameter setting
The parameter setting remains in non-volatile memory and is not erased when
the battery is removed. The reset function on the rear of the thermostat
reloads the factory settings.
|
Parameter setting mode
1. Press LEARN on the rear for 5 seconds until “P01”
appears.
2. Press LEARN again and, the parameter value on the second line flashes and is ready for adjustment.
3. Adjust the parameter using setting knob.
4. Press LEARN once to confirm the setting.
5. Rotate the setting knob clockwise to next parameter and repeat steps 2 to 4.
6. Exit parameter setting mode by rotating the setting knob
clockwise to “End” and pressing LEARN once.
---|---
Note: The thermostat automatically exits parameter setting mode one minute after the last action.
Equipment combinations
Description | Product number | *Data sheet )** |
---|---|---|
Electrothermal actuator (for radiator valves) | ** | |
** | STA321 | A6V12986007 |
Electrothermal actuator (for small valves 2.5mm) | **** | STP321 |
Electromotoric actuator | **** | SFA21.. |
*) The documents can be downloaded from http://siemens.com/bt/download.
Display
The digital display shows the current room temperature and the comfort
temperature setpoint. When the heating output is active, the triangle symbol
is displayed.
Ordering
When ordering, specify both name and product number, e.g. room temperature
controller RDH100RF/SET.
Order valves and actuators as separate items.
Mechanical design
The transmitter consists of 4 parts:
- Plastic housing with digital display containing the electronics, operating elements and built-in room temperature sensor
- Baseplate (mounting base)
- Battery compartment
- Fold-out stand
The housing engages in the baseplate and snaps on. There is a reset button on the rear of the transmitter.
Elements| 1| | Display of the room temperature in
°C / °F
---|---|---|---
2| | Indicates a request for heating
3| | Temperature setting knob
4| | Battery compartment
5| | Comfort temperature setpoint
6| | Indicates RF signal test
7| | Indicates low battery power; replace batteries
The receiver is located in a plastic housing with LEDs and buttons.
The transmitter is located in a plastic housing. Two buttons are visible on the rear when removing the baseplate.
OVERRIDE
Override allows for temporarily overriding the active value from the sender. Override responds differently depending on the radio connection (normal or fault).
Example A: Normal connection between sender and receiver
Press the OVERRIDE button to overwrite the value for ca. 14 minutes. The value
then returns to the setpoint.
Example B: Faulty connection between sender and receiver
Press the OVERRIDE button to permanently override the value. The value returns
to the setpoint after the connection between sender and receiver works again.
RF LED
RF state | RF LED |
---|---|
Power up (first 5 seconds) | Flash RED |
Power up (after 5 seconds) | RED |
Press OVERRIDE switch | Flash RED + ORANGE (amber) (4 seconds) |
Learning period | No LED |
Software reset | RED |
RF receive | GREEN |
No RF within last 25 minutes | RED |
Manual override (RF receive) | Flash ORANGE |
Relay LED
Relay state | Relay LED |
---|---|
From OUT to ON (first 5 seconds) | Flash ORANGE |
ON | ORANGE |
From ON to OFF (after 5 seconds) | Flash ORANGE |
OFF | OFF |
Mounting
DANGER
Electric shock on directly touches of EMI filter
- Disconnect from power supply before connecting EMI filter.
- Make sure EMI filter is out of reach after installation.
If the reference room contains thermostatic radiator valves, set them to their fully open position.
For commissioning, refer to the operating instructions A6V101035988.
Communication of the RDH100RF/SET (transmitter and receiver) is paired ex
factory.
- The devices are suitable for wall mounting.
- Recommended height: 1.5 m above the floor.
- Do not mount the devices in recesses, shelves, behind curtains or doors, or above or near heat sources.
- Avoid direct solar radiation and drafts.
- Seal the conduit box or the installation tube if any, as air currents can affect sensor readings.
- Adhere to allowed ambient conditions.
Change of batteries
If the battery symbol appears, the batteries are almost empty and must be
replaced.
Reset
Simultaneously press the TEST and LEARN buttons on the rear of the transmitter
to reset it.
Simultaneously press the OVERRIDE and LEARN buttons to reset the receiver.
This resets all individual settings to their default values.
Maintenance
The transmitter and receiver are maintenance-free except for the transmitter
battery.
Disposal
This symbol or any other national label indicate that the product, its
packaging, and, where applicable, any batteries may not be disposed of as
domestic waste. Delete all personal data and dispose of the item(s) at
separate collection and recycling facilities in accordance with local and
national legislation.
For additional details, refer to Siemens information on disposal.
Instructions for the replacement of alkaline batteries
WARNING
| Explosion due to fire or short-circuit, even with discharged batteries
Risk of injury due to flying parts
● Prevent the batteries from coming into contact with water.
● Do not recharge batteries.
● Do not damage or disassemble batteries.
● Do not heat batteries over 85°C.
**| Leakage of electrolyte**
Severe burns
● Handle damaged batteries only wearing suitable protective gloves.
● In case of contact with electrolyte, rinse eyes immediately with plenty of water. Consult a doctor.
---|---
Observe the following:
- Use only a battery of the same type and from the same manufacturer as a replacement.
- Observe the polarities (+/-).
- The batteries must be new and undamaged.
- Do not mix new and used batteries.
- Store, transport and dispose of the batteries in compliance with local requirements,regulations and laws. Also observe the instructions of the battery manufacturer.
Product documentation
Power supply
Operating voltage| DC 3 V (2 x 1.5 V AA alkaline batteries)
Battery life| >1 year (with AA alkaline batteries)
Related documents such as CE declarations, etc., can be downloaded from the following address: http://siemens.com/bt/download.
Technical data
Power supply
Operating voltage| DC 3 V (2 x 1.5 V AA alkaline batteries)
Battery life| >1 year (with AA alkaline batteries)
Sensor inputs
Internal thermistor| 10 kΩ ± 1% at 25 °C
Radio frequency
Frequency band| ISM 433MHZ
Maximum radio-frequency power| 4.19 dBm
Operational data
PID control: Minimum period
Minimum pulse length
| Slow 4 min
12 min
| Fast 2 min
6 min
Setpoint setting range| 5…30 °C
Factory setting comfort setpoint| 20 °C
Environmental conditions
Resolution of settings and displays Setpoints
Actual value displays
| ****
0.5 °C
0.5 °C
Operation| IEC 60721-3-3
Climatic conditions| Class 3K5
Temperature| 0…+40 °C
Humidity| <90% r.h.
Transport| IEC 60721-3-2
Climatic conditions| Class 2K3
Temperature| -25…+60 °C
Humidity| <95% r.h.
Mechanical conditions| Class 2M2
Storage| IEC 60721-3-1
Climatic conditions| Class 1K3
Temperature| -10…+60 °C
Humidity| <90% r.h.
Standards, directives and approvals
EU conformity (CE)| A6V101123354 )
RCM conformity to EMC emission standard| A6V101123355 )
Safety class| III as per EN 60950-1
Pollution degree| 2
Degree of protection of housing| IP20
Environmental compatibility| The product environmental declaration
(A6V101123359 *) contains data on environmentally compatible product design
and assessments (RoHS compliance, materials composition, packaging,
environmental benefit, disposal).
*) The documents can be downloaded from: http://siemens.com/bt/download.
Eco design and labeling directives
| Based on EU Regulation 813/2013 (Eco design directive) and 811/2013
(Labeling directive) concerning space heaters, the following classes apply:
Application with On/Off operation of a heator| Class I| Value 1%
PWM (TPI) room thermostat, for use with On/Off output heaters| Class IV| Value
2%
General
Weight (including package) RDH100RF/SE|
475 g
Color of housing front| Signal-white RAL9003
Housing material| ABS (LCD lens:PC)
Receiver RCR100/433
General unit data
Operating voltage *)| AC 230 V +10/-15%
Power| <10 VA
Frequency| 50…60 Hz
EMI filter (e.g., KEILS EMI CW4L2-3-R) can be used to reduce EMI disturbance. See Connection diagram [▶ 14].
Outputs
Switching capacity of relays|
Voltage Current| AC 24…250 V
8 (3) A
No internal fuse!
External preliminary protection with max. C 10 A circuit breaker required for all cases.
Switching outputs (LX, L1, L2)
Relay contacts| Switching voltage| Max. AC 250 V; Min. AC 24 V
Switching current| Max. 8 A res., 3 A ind.
At AC 250 V| Min. 10 mA
Contact life at AC 250 V| At 5 A res.| 1 x 105 cycles (guide value)
Insulating strength| Between relay contacts and coil| AC 5,000 V
Between relay contacts (same pole)| AC 1,000 V
Electrical connections
Connections terminals (via baseplate) For solid wires
For stranded wires
| Screw terminals 2 x 1.5 mm2
1 x 2.5 mm2(min. 0.5 mm2)
Operation | IEC 60 721-3 |
---|---|
Climatic conditions | Class 3K3 |
Temperature | 0…+45 °C |
Humidity | <85% r.h. |
Storage and transport | IEC 60 721-3 |
Climatic conditions | Class 2K3 |
Temperature | -25…+70 °C |
Humidity | <93% r.h. |
Mechanical conditions | Class 2M2 |
Standards, directives and approvals
EU conformity (CE)| A6V101123354
Safety class| II as per EN 60 730-1
Degree of pollution| 2
Color
Unit front| Signal-white RAL 9003
Base| Gray RAL 7035
Dimensions| 83x104x32 mm
Connection diagram
| L| Live, AC 230 V
---|---|---
Lx| Live, AC 24…250 V
L1| N.O. contact, AC 24…250 V / 8 (3) A
L2| N.C. contact, AC 24…250 V / 8 (3) A
PE| Protective ground
M1| Circulating pump
N| Neutral conductor
Nx| Neutral conductor
N2| Receiver RCR100/433
Y1| Actuating device
Application examples
| ****
---|---
Wireless room temperature controller with receiver control of a gas-fired
wall-hung boiler| Wireless room temperature controller with receiver control
of atmospheric gas burner
****|
Wireless room temperature controller with receiver control of a heating
circuit pump (precontrol by manual mixing valve)|
F1| Thermal reset limit thermostat| N1| Room temperature controller RDH100RF
(Transmitter)
F2| Safety limit thermostat| N2| RCR100/433 (Receiver)
M1| Circulating pump| Y1| 3-port valve with manual adjustment
Y2| Magnetic valve| |
Dimensions
[mm] Room temperature controller
Room temperature controller mounting plate
Room temperature receiver with mounting plate
Product history
Index 1) | Date | Changes |
---|---|---|
≥C | June 2018 | ● Add new function min/max temperature limitation, |
selectable control behavior and parameter settings.
Z, A| March 2017| First release.
- Product index can be found next to the production date on the rear of the device “YYMMDDX”.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies