BLUE JAY CBM3000 Circuit Breaker Manager User Manual

June 10, 2024
BLUE JAY

BLUE-JAY-logo

BLUE JAY CBM3000 Circuit Breaker Manager

CBM3000 Circuit Breaker Manager

The CBM3000 Circuit Breaker Manager is a new generation product designed for 3~35KV indoor switchgear. It is suitable for switchgear cabinet, handcart cabinet, fixed cabinet, RMU, and other types of switchgears. The product provides real-time display for  temperature and humidity, automatic heating dehumidification control, circuit breaker status indication, spring storage and grounding switch indicator, and also shows the circuit diagram and the simulation sub-switch LED to indicate. All products use industrial-grade electronic components with rigorous design and manufacturing processes to ensure high reliability, long life, and strong anti-interference capability. The product meets standards DL/T538-2006 [High voltage live display device technical conditions].

Technical Parameters

  • Voltage level: 3~35KV
  • Temperature range: -40°C~+85°C
  • Humidity range: 0%~100%RH
  • Power supply: AC220V±10% 50Hz
  • Power Consumption: ≤10W
  • Communication interface: RS485 or Ethernet
  • Storage capacity: 2GB SD card

Installation and Start-Up

  1. Connect the power supply in strict accordance with the marked voltage level, and the wiring must be strictly in accordance with the markings on the terminals on the back.
  2. During installation, tighten the terminals and fix the equipment in a place that is strong, fire-resistant, and not easy to vibrate. Install the equipment vertically, with a height of 1.8m.
  3. During the withstand voltage test, disconnect the high voltage live display sensor plug, disconnect the temperature and humidity sensor plug, and the wireless receiving head.
  4. All digital contacts must be passive access.
  5. Wiring according to the actual wiring mark, subject to change without prior notice.
  6. The company is not responsible for improper use or malfunctions not caused by this product.

Note: Please read this user manual carefully and save it for future reference.

Read me
When you use CBM3000, be sure to carefully read this user manual, and be able to fully understand the implications, the correct guidance of operations in accordance with user manual, which will help you make better use CBM3000, and help to solve the various problems at the scene.

  1. The power supply must be connected in strict accordance with the marked voltage level, and the wiring must be strictly in accordance with the markings on the terminals on the back.
  2. During installation, the terminals should be tightened, and the equipment should be fixed in a place that is strong, fire-resistant, and not easy to vibrate. The effect is best when the equipment is looking up, so it should be installed vertically, and the height should be 1.8M.
  3. During the withstand voltage test, it is necessary to disconnect the high voltage live display sensor plug, disconnect the temperature and humidity sensor plug and the wireless receiving head.
  4. All digital contacts must be passive access.
  5. Wiring according to the actual wiring mark, subject to change without prior notice.
  6. The company is not responsible for improper use or malfunctions not caused by this product.
  • Please read this user manual carefully
  • Please save this document

SUMMARIZE

CBM3000 Circuit Breaker Manager is a new generation product mainly design and development for 3 ~ 35KV indoor switchgear, it is suitable for switchgear cabinet, handcart cabinet, fixed cabinet, RMU and other types switchgears. The product provides real-time display for temperature and humidity; automatic heating dehumidification control; circuit breaker status indication; spring storage and grounding switch indicator; also show the circuit diagram and the simulation sub-switch LED to indicate.
Products all use industrial-grade electronic components, Rigorous design and manufacturing process make high reliability, long life, and strong anti- interference capability. Meet standards DL/T538-2006 [High voltage live display device technical conditions].

APPLICATIONS

  • Automatically cut off the power
  • Monitor the operating status of electrical equipment
  • Monitor electrical energy consumption in power systems
  • Power equipment in substations and power plants
  • Ensuring the Safety and Reliability of Power Systems
  • Reduce energy consumption and enhance equipment safety
  • Automated remote control and monitoring

FEATURES

  • Automatically cut off the power
  • With door lock indicator (NC/NO)
  • Optional high voltage indicator
  • Optional RS485 communication
  • Switchgear inside temperature & humidity display (LED or LCD)
  • With electronic thermostat can automatic control fan /heater
  • With primary side analog diagram to show switchgear inner wiring
  • Integrated led indicator to show switch position, breaker position, earth switch position, VCB spring energy state

TECHNICAL PARAMETERS

Basic parameters|
---|---
Auxiliary Power| 85~265Vac/dc
Power consumption| 15VA
Display screen| LCD with 4 button operation key
Communication| RS-485, MODBUS-RTU
Environment temperature| -10 ~ +60°C
Environment humidity| RH 20% ~ 95% (No condensation)
Altitude| <3000m
Withstand voltage| AC2000V/1min
Dielectric strength| 100Mohm
Electromagnetic compatibility| Comply with IEC255-22
Dimensions| 250x190x68mm (WxHxD)
Install hole open| 226x165mm
Temperature protection relay|
Temperature set range| -20C ~80C
Resolution| 0.1C
Humidity set range| 0% ~ 100%
Resolution| 0.1%RH
Integrate power metering|
Network| 1P2W, 3P3W, 3P4W
Rated voltage| AC100V, 220V, 380V depends on VT
Burden| <0.1VA (Per phase)
Rated current| AC1A, 5A depends on CT
Burden| <0.4VA (Per phase)
Accuracy level| full scale 0.5%, RMS
Frequency range| 40~65Hz, accuracy: ±0.02Hz
Power| KW and Kvar, accuracy: 0.5%
Energy| Kwh 0.5S class, Kvarh 2.0 class
Other protection functions|
High voltage indicator sensitive| [Rated voltage] x 0.15~0.65
Door lock relay act voltage| >[Rated voltage] x 0.65

INSTALLATION AND START-UP

The manual you hold in your hands contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions. The instrument must not be powered and used until its definitive assembly on the cabinet’s door.
Whether the instrument is not used as manufacturer’s specifications, the protection of the instrument can be damaged.
When any protection failure is suspected to exist (for example, it presents external visible damages), the instrument must be immediately powered off. In this case contact a qualified service representative.

Dimension:
Installation hole: unit mm

Physical Dimensions: unit mm

BLUE-JAY-CBM3000-Circuit-Breaker-Manager-12

Sensor mounting

  • Using 35mm rail mounting or screw.
  • Fixed installation (pitch 37mm diameter 4mm).
  • Using the interface plug-ins to connect temperature and humidity sensors and instruments

Heater size

BLUE-JAY-CBM3000-Circuit-Breaker-Manager-4

Basic functions introduction
Front panel introduction

BLUE-JAY-CBM3000-Circuit-Breaker-Manager-4

No. Description
1A,4A working position indication
1B,4B test position indication
2A Circuit breaker (VCB) closed indication
2B Circuit breaker (VCB) opened indication
3A Grounding switch closed indication
3B Grounding switch opened indication
5 Voice alarm speaker
6 Spring storage indicator
7 High voltage indicator
9 Door locked indicator
10 Door unlocked indicator
12 Heater_1 working condition indicator
13 Heater_2 working condition indicator
--- ---
14 Fan_1 working condition indicator
15 Fan_2 working condition indicator
16 Cabinet lighting ON indicator
17 Forced Heating
18 Forced cooling
19 Button “open cabinet lighting/ Move the cursor right”
20 LCD screen area
21 Operation button
26 Switch for spring storage Off/On
27 Switch for Remote/local selection
28 Switch for Closing/opening

Rear panel introduction

BLUE-JAY-CBM3000-Circuit-Breaker-Manager-5

No.| Description| | No.| Description|
---|---|---|---|---|---
21| VCB working| ****



DI terminal from VCB

| 33| Switchgear safety locker| ****
















Passive NO node

22| VCB test| 34
23| VCB opened| 44| ****

Phase lose

24| VCB closed| 45
25| Spring storage| 51| ****

Fan 1 controlled by Probe 1

26| Ground switch

Opened/Closed

| 52
27| COM port for VCB| 53| Fan 2 controlled by Probe 2
56| Sensor, disconnect detect loop| Passive DO| 54
57| 35| Heater 1 controlled by Probe 1
15| Light loop| Passive DO| 36
16| 37| Heater 2 controlled by Probe 2
58| RS485 port A| ****


COMM

| 38
59| RS485 port B| 61| A| ****


Wireless probe terminal

60| RS485 GND| 62| B
81| Temperature Humidity Probe 1| ****


Input

| 63| GND
82| Temperature Humidity Probe 2| 64| +
29| Phase A high voltage sensor| Input| 1| Power supply
30| Phase B high voltage sensor| 2| AC/DC110~220V
31| Phase C high voltage sensor| | GND
32| Ground for high voltage sensor| 40~43 Spring storage/released

OPERATION MODE

Button description

  • On and off function of the heating output relay.
  • On and off function of the exhaust output relay.
  • Control the lighting function on or off.
  • Set the menu to scroll upwards during programming or switch forward; Long press is the self-check function
  • Set the menu to scroll upwards during programming or switch next;
  • Enter the programming menu, exit the menu level by level.
  • Confirm and save the entered information or displayed settings.

4.2.-Parameter setting

In the measurement state, press the ” ” keys, the screen will display the following data in sequence:

BLUE-JAY-CBM3000-Circuit-Breaker-Manager-13

Screen No. Definition
Screen-1 Temperature and humidity values and exhaust air heating control

status
Screen-2| The working status of the relay
Screen-3| The effective value of three-phase voltage and current
Screen-4| Active power, reactive power and apparent power
Screen-5| Power factor and frequency
Screen-6| Active energy consumed and generated
Screen-7| Reactive energy consumed and generated
Screen-8| RTC
Screen-9| Event logging
Screen-10| Multi-channel wireless temperature measurement value

Press ” ” key to enter the menu programming state, enter the correct password (factory password is 0001,) to confirm the specific parameter settings. It needs to be saved after setting up and exit. The programming menu structure and description are shown in the following table:

BLUE-JAY-CBM3000-Circuit-Breaker-Manager-14

Menu layer

Level- 1 Level- 2 Level- 3 Description
Temperature and humidity 1 and 2 Status ON ” ON ” and ” OFF ” are

optional
Dehumidifying| Start>XX%;
Stop< XX%| Start 5%RH~99%RH
Stop 0%RH~94%RH
Heating| Start<XXXX°C; Stop >XXXX°C| Start -40°C ~+35°C
Stop -35°C ~+40°C
Cooling| Start >XXXX°C; Stop <XXXX°C| Start -35°C ~+125°C
Stop -40°C ~+120°C
Hysteresis| XX| left and right arrows to select, and Enter key to confirm.
Delay| XX sec
Load disconnection| ON| “ON” and “OFF” are optional
Electrical test settings| Voltage range| 100V| 100V or 380V, Default 100V
Current range| 5A| 5A or 1A, Default 1A
Voltage ratio| XXXX| Voltage magnification ratio
CT ratio| XXXX| Current magnification ratio
Wiring mode| 4P3L| 3P4L\3P3L3CT\3P3L2CT
Comm| Device address| XXX;| 001~255
Baud rate| XXXX| 2400,4800,9600,19200
Data Format| n.8.1| n.8.1 \0.8.1\e.8.1\ n.8.2
SYS| Backlight control| XXXX Min| left and right arrows to select, and Enter key to confirm.
Reset counter| ON| ” ON ” for reset to zero
Voice| ON| ” ON ” and ” OFF ” are optional
Reset password| XXXX| Enter the 4-digit new password

Notes: Part of the content is modifiable or optional.

FUNCTIONS INTRODUCTION

Status indication function

Functions Definition
VCB indicate When the handcart is in the working position (working

position contact is closed), the handcart indicator red (1A, 4A) light is on;
When the handcart is in the test position (the contact in the test position is closed), the green (1B, 4B) lights of the driving indicator are on;
When the handcart is in the working position or between the test position and the working position, close the grounding knife forcibly, and the indicator lights (1A, 1B, 4A, 4B) of the handcart will continue to flash;
When the handcart is not in the cabinet (the contacts in the working and test positions are not closed and the contacts of the circuit breaker are disconnected), the red and green (1A, 4A, 1B, 4B) lights of the handcart indicator are not on;
Circuit breaker status indicate| When the circuit breaker is closed (the contact of the circuit breaker is closed), the indicator light (2A) of the circuit breaker is on;
When the circuit breaker is open (circuit breaker sub-contact is closed), the circuit breaker indicator green (2B) light is on;
When the circuit breaker is not in the cabinet (both closed and open contacts of the circuit breaker are not closed), the red and green (2A, 2B) indicators of the circuit breaker are off;
Ground switch indicate| When the grounding switch is closed (the opening/closing contact of the grounding switch is closed), the grounding switch indicator red (3A) light is on;
When the grounding switch is not closed (the opening/closing contact of the grounding switch is not closed), the green (3B) light of the grounding switch is on
Spring status indicate| When the contact is closed, the energy storage indicator red light (6) is on;

Intelligent voice warning function

Warning 1:
When the circuit breaker is closed and the handcart is between the test position and the working position (the contacts of the test position and the working position are both disconnected), the 1A, 4A, 1B, 4B, 2B indicator lights flash, and the 2A indicator light is always on. Lights up and there is a voice prompt “Please turn off the circuit breaker”

Warning 2:
When the handcart is in the working position or between the test position and the working position, close the grounding knife forcibly, the 1A, 4A, 1B, 4B, 3B indicator lights will flash, the 3A indicator light will always be on and there will be a voice prompt “Please open the grounding switch ”

Warning 3:
When both the grounding knife and the circuit breaker are closed, when the trolley is accidentally pushed to switch from the test position to the working position, the 2B and 3B indicator lights will flash at the same time, accompanied by language prompts “Please switch off the circuit breaker” and “Please switch off the grounding switch”

Warning 4:
When the circuit is electrified and the human body senses a signal, there will be a voice prompt of “This circuit is electrified”

High voltage indicate and lock function

Functions Definition
High voltage live display When the three phases A, B, and C are charged

(voltage ≥ 15% of the rated voltage), the corresponding three- phase indicators (7) of A, B, and C will start to glow;
High voltage live lock| When any one of the three phases A, B, and C is electrified (voltage ≥ 65% of the rated voltage), the high- voltage lock indicator red light (9) is on, the high-voltage unlock indicator green light (10) is off, and the corresponding high-voltage lock contact output pops open;

When the three phases are not charged, the green light (10) of the high- voltage unlocking indicator is on, the red light (9) of the high-voltage locking indicator is off, and the output of the corresponding high-voltage locking contact is closed;

High voltage phase loss alarm| When any one or two of the three phases A, B, and C are charged (voltage ≥ 65% of the rated voltage), the phase loss alarm contact output is closed;

When all three phases are not charged or all three phases are charged, the phase loss alarm contact The output is turned on.

Note: A, B, C three-phase matching sensor, its output short-circuit current must reach 220uA ± 10%.

Operation function

Functions Definition
Switch off/on storage
Opening/closing operation
Remote/local conversion
Test In the measurement state, long press ”   ” button for ≥ 3 seconds

to enter the test mode, all indicator lights are on for 3 seconds, the relay is closed for 3 seconds, and the voice repeats “This circuit is electrified” (The test content does not include high voltage electrification Indicator light and lock indicator light)
Cabinet lighting| In the measurement state, press the button  to start the cabinet lighting with corresponding instructions: the second LCD screen displays that the lighting relay is closed

Working mode

Functions Definition
Measurement In the measurement state, the area 20 displays the current

channel, temperature, humidity value, electrical parameter value, switch status, etc., and can choose to cycle display. For the specific interface, please refer to the “Instructions for Use” below.
Control| When the temperature or humidity of the environment meets the pre-set working conditions, the heater or fan is started, and the corresponding indicator light is on. When the load fails and does not work according to the conditions, the corresponding load disconnection relay is closed, and the Appears on the display.
Control test| Under normal working conditions, press button to force heat;

press    button to force cooling.

Setting mode

Enter/exit system setting mode
Enter the system: Under normal condition, press button to enter the system setting mode. Press the left and right keys to enter the password. refer to the following “Instructions” for each setting interface.
Note: The default password is 0001.

Wireless temperature measurement function
Wireless Temperature Receiver:
Each device can be equipped with 1 wireless temperature receiver and 9 (according to customer needs can be expanded to 12) wireless temperature collector, each 3 serial number connected wireless temperature collector is a group.
Dimension: unit(mm)

BLUE-JAY-CBM3000-Circuit-Breaker-Manager-15

Installation: 35mm Din rail

BLUE-JAY-CBM3000-Circuit-Breaker-Manager-16

Wireless temperature collector:
The specific installation method of the wireless temperature collector is shown in the figure below. Each collector has a temperature-sensing point, and the temperature measured by the collector is the temperature of the temperature-sensing point.
If the collector is placed in the air, the measured temperature is ambient temperature. In order to accurately measure the temperature of the surface of the object, it should be ensured that the temperature-sensing surface of the collector is in close contact with the surface of the object to be measured.

BLUE-JAY-CBM3000-Circuit-Breaker-Manager-17

Watch strap wireless temperature collector

Each control device can be equipped with 1 wireless temperature receiver and 9 (can be expanded to 12 according to customer needs) wireless temperature collectors, and every 3 serial numbers connected wireless temperature collectors form a group.
Note: When installing, follow the position marked on the label on the wireless temperature collector. If the installation location is not corresponding, the temperature displayed on the control device from T1 to T12 is not the temperature of the actual location.
The supporting wireless receiving box (rail-mounted installation) must be installed in the handcart room of the circuit breaker, and connected to the control device through a 4-core connecting line (preferably shielded cable). The corresponding connection relationship is as follows:
Wiring method of wireless temperature receiver:

8 7 6 5 4 3 2 1
+5V 485B 485A power

light

| | N| L

The connection method between the wireless temperature receiver and the control terminal

Wireless routing adapter terminal number| Temperature measurement terminal number
---|---
8| +5V| 64
7| ┻| 63
6| 485B| 62
5| 485A| 61
4| power light|

When a wireless temperature sensor detects that the surface temperature of the target point exceeds the upper alarm limit, the red alarm light on the front of the device flashes, the corresponding serial number of the wireless temperature measurement display interface changes to “!” Flashes, and the information is saved in the event record; When the surface temperature of the target point exceeds the upper limit of the alarm, the alarm output relay draws in; when the surface temperature of the target point drops to the exit alarm temperature point (Th-5°C), the device automatically exits the alarm state of this aspect.

Technical Parameters

Resolution 0.1°C
Measurement accuracy < ± 1°C
Measurement range -40°C-150°C
Measurement interval 0.5s
Sending interval 1-60s (Adjustable)
Battery life >= 5 years
Working temperature -20°C ~80°C
Working environment humidity ≤95%RH
Collection point and receiver distance ≤80 meters (open viewing distance)
Receiver size 604526mm
Positioning hole diameter 3mm
Positioning hole center distance 69.6mm

COMMUNICATION INTERFACE

MODBUS © protocol
CBM3000 can choose RS485 communication interface and support standard Modbus- RTU communication protocol.

Modbus RTU Frame Format:

Address 1-247
Baud 2400bps,4800bps, 9600bps,192000 bps
Data format N. 8. 1

0. 8. 1
E. 8. 1
N. 8. 2

Note:
For detailed Modbus-RTU communication protocol description, please visit http://www.modbus.org, can refer to document Modbus_Application_Protocol_V1_1a.pdf.

Register Map

Addr. Data Description Byte

Secondary side parameters (integer data)
0x00| Ua| Phase-line voltage data, unit 0.1V| 1
0x01| Ub| 1
0x02| Uc| 1
0x03| Uab| Phase-phase voltage data, unit 0.1V| 1
0x04| Ubc| 1
0x05| Uca| 1
0x06| Ia| Current data, unit 0.001A| 1
0x07| Ib| 1
0x08| Ic| 1
0x09| Pa| Split phase active power, unit 0.1W| 1
0x0a| Pb| 1
0x0b| Pc| 1
0x0c| P∑| Total active power, unit 1W| 1
0x0d| Qa| Split phase reactive power, unit 0.1var| 1
0x0e| Qb| 1
0x0f| Qc| 1
0x10| Q∑| Total reactive power, unit 1var| 1
Reserved| 1
0x14| S∑| Total apparent power, unit 1VA| 1
Reserved| 1
0x18| cosQ| Power factor 0~1.000| 1
0x19| FR| Frequency 0.01Hz| 1
0x1a| Ep+| Positive active energy, unit Wh| 2
0x1c| Ep-| Reverse active energy (generated)| 2
0x1e| Eq+| Inductive reactive energy, unit Varh| 2
0x20| Eq-| Capacitive reactive energy, unit Varh| 2
Reserved| 1
0x28| T1| Temperature sensor 1,Unit 0.1°C| 1
0x29| RH1| Humidity sensor 1,Unit 0.1%RH| 1
0x2A| T2| Temperature sensor 2,Unit 0.1°C| 1
0x2B| RH2| Humidity sensor 2,Unit 0.1%RH| 1
---|---|---|---
Reserved| 1
0x44| DI| Input signal status:

0 for opened, 1 for closed
[Bit 0] VCB working [Bit 1] VCB test
[Bit 2] VCB opened [Bit 3] VCB closed [Bit 4] Spring storage
[Bit 5] Ground switch

| ****




1

0x45| DO| Output signal status:
0 for opened, 1 for closed
[Bit 0] Heater_1
[Bit 1] Heater_2
[Bit 2] Fan_1
[Bit 3] Fan_2 [Bit 4] Door locker [Bit 5] Phase loose [Bit 6] Light lamp
[Bit 7] Load disconnect| ****






1

Primary side parameters (floating point data)
0x100| Ua| ****

Phase-line voltage data, unit V

| 2
0x102| Ub| 2
0x104| Uc| 2
0x106| Uab| Phase-phase voltage data, unit V| 2
0x108| Ubc| 2
0x10a| Uca| 2
0x10c| Ia| Current data, unit A| 2
0x10e| Ib| 2
0x110| Ic| 2
0x112| Pa| Split phase and total active power, unit kW| 2
0x114| Pb| 2
0x116| Pc| 2
0x118| P∑| 2
0x11a| Qa| Split phase and total reactive power, unit kvar| 2
0x11c| Qb| 2
0x11e| Qc| 2
0x120| Q∑| 2
Reserved| 2
0x128| S∑| Total apparent power KVA| 2
Reserved| 2
0x130| COSQ| Power factor 0~1.000| 2
0x132| FR| Frequency 0.01Hz| 2
0x134| Ep+| Positive active energy, Unit kWh| 2
0x136| Ep-| Reverse active energy (generated)| 2
0x138| Eq+| Inductive reactive energy, unit kVarh| 2
0x13a| Eq-| Capacitive reactive energy, unit kVarh| 2


Wireless temperature measurement (integer data)

0x300| WX_T1| Wireless probe-1(0.1°C)| 1
0x301| WX_T2| Wireless probe-2| 1
0x302| WX_T3| Wireless probe-3| 1
0x303| WX_T4| Wireless probe-4| 1
0x304| WX_T5| Wireless probe-5| 1
0x305| WX_T6| Wireless probe-6| 1
0x306| WX_T7| Wireless probe-7| 1
0x307| WX_T8| Wireless probe-8| 1
0x308| WX_T9| Wireless probe-9| 1
0x309| WX_T10| Wireless probe-10| 1
0x30A| WX_T11| Wireless probe-11| 1
0x30B| WX_T12| Wireless probe-12| 1
0x30C| WX_T13| Wireless probe-13| 1
0x30D| WX_T14| Wireless probe-14| 1
0x30E| WX_T15| Wireless probe-15| 1

TECHNICAL SERVICE

For any inquiry about the instrument performance or whether any failure happens, contact to Blue Jay’s technical service.

  1. If there is any not understand in the description when user installation instructions, please contact technical directly.
  2. Company technology will answer any questions at any time.
  3. Issues arising from the use of the product within one working day to respond.
  4.  These products is 1-year warranty, free of charge maintenance for life.

Blue Jay – After-sales service
1802,Building 2,No.88,Jianxin East Road, Chongqing,400020,China
Tel – + 0086 023 67628702
E-mail: tech@cqbluejay.com