Specifications

  • Remote Mounting Kit: 132B0206
  • Additional Items Required: 132B0203
  • Voltage: 3x200V, 3x400V, 3x600V
  • Power Range: Minimum waiting time – 4kW (hp) – 15 minutes, 15 kW (hp) – 15 minutes

Product Usage Instructions

Mechanical Installation

  1. Fit gasket on LCP as shown in Illustration 1.1.
  2. Cut out the panel with dimensions from Illustration 1.2.
  3. Position LCP with gasket onto the panel as shown in Illustration 1.2.

Electrical Installation

  1. Connect the LCP cable to the frequency converter as depicted in Illustration 1.4.
  2. Fasten the connector to the frequency converter using thread cutting screws provided. Torque: 1.3 Nm (11.5 in-lb).
  3. Position the bracket on the back of the LCP, then slide down as shown in Illustration 1.3.
  4. Fasten the bracket to the LCP using the thread-cutting screws supplied. Torque: 1.3 Nm (11.5 in-lb).

Items Supplied

The remote mounting kit (ordering number: 132B0206) includes:

  • Gasket.
  • Screws (3 pieces).
  • Mounting plate bracket.

Additional Items Required

  • Local control panel (LCP), ordering number 132B0200.
  • LCP 31 to RJ 45 converter kit, ordering number 132B0203.

Safety Instructions

For important information about safety precautions for installation, refer to VLT® HVAC Basic Drive FC 101 Quick Guide.

WARNING

DISCHARGE TIME

The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. Failure to wait the specified time after power has been removed before performing service or repair work, could result in death or serious injury.

  • Stop the motor.
  • Disconnect AC mains, permanent magnet-type motors, and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
  • Wait for the capacitors to discharge fully, before performing any service or repair work. The duration of waiting time is specified in Table 1.1.

Voltage [V]| Power range

[kW (hp)]

| Minimum waiting time

(minutes)

---|---|---
3×200| 0.25–3.7 (0.34–5)| 4
3×200| 5.5–11 (7.5–15)| 15
3×400| 0.37–7.5 (0.5–10)| 4
3×400| 11–90 (15–125)| 15
3×600| 2.2–7.5 (3–10)| 4
3×600| 11–90 (15–125)| 15

Mechanical Installation

  1. Fit gasket on LCP, see Illustration 1.1.
  2. Cut out the panel, with the dimensions shown in Illustration 1.2.
  3. Position LCP with gasket onto the panel, as shown in Illustration 1.2.Danfoss-FC-101-Remote-Mounting-of-LCP-fig-2
  4. Position the bracket on the back of the LCP, then slide down. See Illustration 1.3.
  5. Fasten the bracket to the LCP using the thread-cutting screws supplied. Tightening torque is 1.3 Nm (11.5 in-lb).Danfoss-FC-101-Remote-Mounting-of-LCP-fig-3

Electrical Installation

  1. Connect the LCP cable to the frequency converter, as shown in Illustration 1.4.
  2. Fasten the connector to the frequency converter using the thread-cutting screws supplied. Tightening torque is 1.3 Nm (11.5 in-lb).Danfoss-FC-101-Remote-Mounting-of-LCP-fig-4

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are the property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com

FAQ

Q: What is the waiting time required after power has been removed for performing service or repair work?

A: The waiting time is specified in Table 1.1 based on the voltage and power range of the frequency converter.

References