**EKF RT Series Time Relay Instruction Manual
**
DESCRIPTION
Time relay RT-SBA EKF is an electronic switching device with an adjustable time setting. The time relay is designed to switch on load with time delay. Time delay can be adjusted using the dials on the front panel of the relay.
The time relay complies with IEC 61000-4-4:2004.
The relay can be used in industrial and household automation, e.g. in HVAC and lighting systems.
TECHNICAL DATA
Table 1
Characteristics | Values |
---|---|
Item code | RT- SBA |
240 | RT-SBA- 12-240- 2 |
Rated voltage, V | 24-240 В AC/DC |
Rated pulse voltage, V AC | 400 |
Power consumption | AC: ≤1,5 VA; DC: ≤1 W |
Time delay range | 0,1 s … 10 days |
Set-point accuracy, % | ≤5 |
Repeatability, % | ≤0,2 |
Power interruption, ms | min 200 |
Electrical life, cycles | 100 000 |
Mechanical life, cycles | 1 000 000 |
Characteristics | Values |
--- | --- |
Item code | RT- SBA |
240 | RT-SBA- 12-240- 2 |
Number
of switching contacts
| 1| 2| 1| 2
Rated load current| 8A at 230 V AC1
Interference immunity| 3 in accordance with IEC 61000-4-4:2004
Max. altitude above sea level, m| 2000
Degree of
protection
| IP20
Pollution degree| 3
Operating
temperature, °С
| -5 … 40
Storage temperature, °С| -25 … 75
Connection| Screw terminals, max. conductor cross-section 2,5 mm2
Tightening torque, N*m| 0,5
Mounting| 35 mm DIN rail
Indication
- Green «U» LED: constantly lit when the relay is powered.
- Red « » LED: flashes red during timer countdown.
- The relay is on, contacts 15-18 (25-28) are closed – lit.
- The relay is off, contacts 15-18 (25-28) are open – not lit.
Control panel
Function diagram
On-delay. After the relay is energized, a countdown (T) is started. During the countdown, relay contacts 15-16 (25-26) remain closed and contacts 15-18 (25-28) remain open (relay coil is off). Once the countdown is finished, contacts 15-16 (25-26) open, and contacts 15- 18 (25-28) close (relay coil is on), remaining in this state until the relay is de-energized.
Setup:
- Install and secure the relay in the intended location.
- Connect the relay as per wiring diagram.
- Energize the relay, the «U» LED will light up green.
- Set up the required time ranges.
Wiring diagram
OVERALL AND INSTALLATION DIMENSIONS
Fig. 1
OPERATING CONDITIONS
- Operating temperature: -5°C to +40°C
- Max. altitude above sea level: 2000 m.
DELIVERY SCOPE
- Time relay RT-SBA EKF – 1 pc.
- Technical manual – 1 pc.
SAFETY REQUIREMENTS
Do not operate relays with visible mechanical damage.
The relays conform to IEC 61140 Class 0 for protection against electrical shock and must be installed in Class 1 enclosures or higher.
MAINTENANCE
For maintenance, follow national safety rules for operation of electrical Installations.
Under normal operating conditions, visually inspect the relay and check the set modes and trigger time every 6 months.
Tighten the screw terminals, as they may become loose due to cyclical changes in the ambient temperature and material flow.
The relay must be installed and maintained by qualified personnel. Follow the wiring diagram when installing the relay. Do not install the relay without protective cover in any area exposed to water or direct sunlight.
TRANSPORTATION AND STORAGE
Relays can be transported by any means of enclosed transport that protects the packaged goods from mechanical impact and weather exposure.
Relays shall be stored indoors, in their original packaging, at the ambient temperatures from -25°С to +75°С and max. relative humidity of 80% at +25°С.
MANUFACTURER’S WARRANTY
The manufacturer guarantees the relays comply with the declared characteristics, provided that the consumer observes the operation, transportation and storage conditions and requirements.
- Warranty period: 7 years.
- Shelf life: 7 years.
- Service life: 10 years
Manufacturer: for information, refer to the product packaging. Importer and EKF trademark service representative:
EKF ELECTRICAL SOLUTION – FZCO, Dubai Silicon Oasis, DDP, Building A2, Dubai, United Arab Emirates.
Importer and EKF trademark service representative on the territory of the Russian Federation: OOO «Electroresheniya», Otradnaya st., 2b bld. 9, 5th floor, 127273, Moscow, Russia. Теl.: +7 (495) 788-88-15.
Importer and EKF trademark service representative оn the territory of the Republic of Kazakhstan: TOO «Energoresheniya Kazakhstan», Kazakhstan, Almaty, Bostandyk district, Turgut Ozal st., 247, apt 4.
CERTIFICATE OF ACCEPTANCE
The time relay has been manufactured in compliance with the effective laws and regulations and has been approved for operation.
Date of manufacture: for information, refer to the product packaging.
Quality control stamp
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>