MEAN WELL MDR-40 Series Industrial DIN Rail Power Supply Owner’s Manual
- June 1, 2024
- MEAN WELL
Table of Contents
MEAN WELL MDR-40 Series Industrial DIN Rail Power Supply
Features
- Universal AC input/Full range
- Protections: Short circuit / Overload / Over voltage
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- Class I, Div 2 Hazardous Locations T4
- LED indicator for power on
- DC OK relay contact
- No load power consumption<0.75W
- 100% full load burn-in test
- 3 years warranty
GTIN CODE
- MW Search: https://www.meanwell.com/serviceGTIN.aspx
SPECIFICATION
MODEL | MDR-40-5 | MDR-40-12 | MDR-40-24 | MDR-40-48 |
---|
OUTPUT
| DC VOLTAGE| 5V| 12V| 24V| 48V
RATED CURRENT| 6A| 3.33A| 1.7A| 0.83A
CURRENT RANGE| 0 ~ 6A| 0 ~ 3.33A| 0 ~ 1.7A| 0 ~ 0.83A
RATED POWER| 30W| 40W| 40.8W| 39.8W
RIPPLE & NOISE (max.) **Note.2| 80mVp-p| 120mVp-p| 150mVp-p| 200mVp-p
VOLTAGE ADJ. RANGE| 5 ~ 6V| 12 ~ 15V| 24 ~ 30V| 48 ~ 56V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME Note.5| 500ms, 30ms/230VAC 500ms,
30ms/115VAC at full load
HOLD UP TIME (Typ.)**| 50ms/230VAC 20ms/115VAC at full load
INPUT
| VOLTAGE RANGE| 85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 78%| 85%| 88%| 88%
AC CURRENT (Typ.)| 1.1A/115VAC 0.7A/230VAC
INRUSH CURRENT (Typ.)| COLD START 30A/115VAC 60A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC
PROTECTION
| ****
OVERLOAD
| 105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after
fault condition is removed
OVER VOLTAGE
| 6.25 ~ 7.25V| 15.6 ~ 18V| 31.2 ~ 36V| 57.6 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
FUNCTION| DC OK SIGNAL| Relay contact rating(max.): 30V/1A
resistive
ENVIRONMENT
| WORKING TEMP.| -20 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min.
each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6
SAFETY & EMC
(Note 4)
| SAFETY STANDARDS| UL508, UL62368-1, TUV BS EN/EN62368-1,Class I, Div.
2 Group A, B, C, D Hazardous Locations T4, EAC TP TC 004, BSMI CNS14336-1,
AS/NZS 60950.1 ,IS13252(Part1)/IEC60950-1(except 48V)approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3
Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class B
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2, 3, 4, 5, 6, 8, 11, BS
EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3, heavy industry level, EAC TP
TC 020
OTHERS
| MTBF| 2418.5K hrs min. Telcordia SR-332 (Bellcore) ; 301.7K hrs
min. MIL-HDBK-217F (25℃)
DIMENSION| 4090100mm (WHD)
PACKING| 0.3Kg; 42pcs/13.6Kg/0.82CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC
input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted
pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation, and load
regulation.
4. The power supply is considered a component that will be installed into the
final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer
to “EMI testing of component power supplies.”(as available on
https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf
)
5. Length of set up time is measured at first cold start. Turning ON/OFF the
power supply may lead to an increase of the set-up time.
6. The ambient temperature derating of 3.5℃/1000m with fanless models and of
5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Mechanical Specification
Block Diagram
DC OK Relay Contact
- Contact Close
- PSU turns on / DC OK.
- Contact Open
- PSU turns off / DC Fail.
- Contact Ratings (max.)
- 30V/1A resistive load.
Derating Curve
Output Derating VS Input Voltage
- Downloaded from Arrow.com.