MEAN WELL LPV-100 Series 100W Single Output Switching Power Supply Owner’s Manual

June 1, 2024
MEAN WELL

MEAN WELL LPV-100 Series 100W Single Output Switching Power Supply Owner’s Manual
MEAN WELL LPV-100 Series 100W Single Output Switching Power Supply
Owner's

Features:

  • Constant voltage design
  • Universal AC input/ Full range
  • Fully encapsulated with IP67 level (Note.7)
  • Withstand 300VAC surge input for 5 seconds
  • Protections: Short circuit/Overload/Over voltage
  • Fully isolated plastic case
  • Cooling by free air convection
  • 100% full load burn-in test
  • Low cost, high reliability
  • Suitable for LED related fixture or appliance (such as LED Decoration or Advertisement devices) (Note.11)
  • 2 years warranty

User’s Manual
QR Code

SPECIFICATION

Symbols

MODEL LPV-100-5 LPV-100-12 LPV-100-15 LPV-100-24 LPV-100-36 LPV-100-48
OUTPUT DC VOLTAGE 5V 12V 15V 24V 36V
RATED CURRENT 12A 8.5A 6.7A 4.2A 2.8A 2.1A
CURRENT RANGE 0 ~ 12A 0 ~ 8.5A 0 ~ 6.7A 0 ~ 4.2A 0 ~ 2.8A 0 ~ 2.1A
RATED POWER 60W 102W 100.5W 100.8W 100.8W 100.8W
RIPPLE & NOISE (max.) Note.2 80mVp-p 120mVp-p 120mVp-p 150mVp-p 150mVp-p

150mVp-p
VOLTAGE TOLERANCE Note.3| ±8.0%| ±5.0%
LINE REGULATION| ±1.0%
LOAD REGULATION| ±6.0%| ±2.0%
SETUP, RISE TIME| Note.6| 2000ms, 25ms / 230VAC  2000ms, 25ms / 115VAC
HOLD UP TIME (Typ.)| 50ms/230VAC        14ms/115VAC at full load
INPUT| VOLTAGE RANGE| Note.4| 90 ~ 264VAC      127 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 80%| 85%| 87%| 88%| 88%| 89%
AC CURRENT| 2.2A/115VAC  1.2A/230VAC
INRUSH CURRENT(Typ.)| COLD START 75A(twidth=700μs measured at 50% Ipeak) at 230VAC
MAX. No. of PSUs on 16A CIRCUIT BREAKER| 2 units (circuit breaker of type B) / 3 units (circuit breaker of type C) at 230VAC
LEAKAGE CURRENT| 0.25mA / 240VAC
PROTECTION| OVERLOAD| 110 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
OVER VOLTAGE| 5.75 ~ 6.75V| 13.8 ~ 16.2V| 17.25 ~ 20.25V| 27.6 ~ 32.4V| 41.4 ~ 48.6V| 55.2 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
ENVIRONMENT| WORKING TEMP.| -25 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +80℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
SAFETY & EMC| SAFETY STANDARDS| UL8750,CSA C22.2 No 250.13-12,UL879,CSA C22.2 No.207-M89,BIS IS15885(Note12),EAC TP TC 004,IP67, IEC62368-1 , BS EN/EN62368-1 approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC
ISOLATION RESISTANCE| I/P-O/P:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2 Class A(≤80% load), BS EN/EN61000-3-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11; BS EN/EN55035, light industry level, EAC TP TC 020
OTHERS| MTBF| 4497.1K hrs min.    Telcordia SR-332 (Bellcore) ;| 681.6Khrs min.| MIL-HDBK-217F (25℃)|
DIMENSION| 1905237mm (LWH)
PACKING| 0.63Kg;20pcs/13.6Kg/0.55CUFT
NOTE|

  1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
  3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. Derating may be needed under low input voltage. Please check the static characteristics for more details.
  5. The power supply is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected by the complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again.(as available on https://[www.meanwell.com//Upload/PDF/EMI_statement_en.pdf)](http://www.meanwell.com/Upload/PDF/EMI_statement_en.pdf))
  6. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time
  7. Suitable for indoor use or outdoor use without direct sunlight exposure
  8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
  9. Products sourced from the Americas regions may not have the TUV/BIS/CCC logo. Please contact your MEAN WELL sales for more information.
  10. For any application note and IP water proof function installation caution, please refer our user manual before using. https://[www.meanwell.com/Upload/PDF/LED_EN.pdf](http://www.meanwell.com/Upload/PDF/LED_EN.pdf)
  11. This product is not intended for LED lighting luminaire applications in the EU.(In the EU the LPF/NPF/XLG series are recommended.)
  12. R-41027766 (GZ factory) only for 12V,24V / R-62002178 (ID factory) for 5V~48V

※ Product Liability Disclaimer:For detailed information, please refer to https://[www.meanwell.com/serviceDisclaimer.aspx](http://www.meanwell.com/serviceDisclaimer.aspx)

| Arrow.com.| File Name: LPV-100-SPEC __2024-02-19

Mechanical Specification

Mechanical Specification

Recommend Mounting Direction

Recommend Mounting Direction

Block Diagram

Block Diagram

Aerating Curve

Aerating Curve

Static Characteristics

Static Characteristics

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals