MEAN WELL DDR-240 Series 240W DIN Rail Type DC Converter Owner’s Manual

June 1, 2024
MEAN WELL

MEAN WELL DDR-240 Series 240W DIN Rail Type DC Converter

Specifications

  • Model: DDR-240B-24 / DDR-240B-48 / DDR-240C-24 / DDR-240C-48 / DDR-240D-24 / DDR-240D-48
  • DC Voltage: 24V / 48V
  • Rated Current: 10A (24V) / 5A (48V)
  • Rated Power: 240W
  • Peak Current: 15A (3 sec.)
  • Input Voltage Range: 16.8V – 154V
  • Efficiency: 90% – 92.5%
  • Operating Temperature: -40°C to +70°C
  • Working Humidity: 5% – 95% RH non-condensing
  • Dimensions: width 40mm, DIN rail mountable
  • Protections: Short circuit, Overload, Over voltage, Over temperature, Input reverse polarity, Input under voltage
  • Isolation: 4KVdc I/O isolation (Reinforced isolation)
  • Features: Current sharing up to 960W(3+1), DC output adjustable, Cooling by free air convection, Remote ON-OFF control, DC OK relay contact
  • Warranty: 3 years

Installation

  1. Ensure that the input voltage matches the specifications of  the DC-DC converter.
  2. Mount the converter on a DIN rail TS-35/7.5 or TS-35/15 securely.

Operation

  1. Connect the input power source within the specified voltage range.
  2.  Use the DC output adjustment feature if necessary.

Maintenance

  1. Regularly check for any signs of damage or overheating.
  2. Keep the cooling vents clear of obstructions for optimal performance.

Troubleshooting
If the DC-DC converter experiences frequent shutdowns or malfunctions, refer to the user manual for specific troubleshooting steps.

Frequently Asked Questions (FAQ)
Q: What is the warranty period for the DDR-240 series DC-DC converter?
A: The product comes with a 3-year warranty from the date of purchase.

Features

  • Compliance to BS EN/EN50155 and BS EN/EN45545-2 railway standard
  • Width only 40mm
  • 2:1 wide input range
  • -40~+70°C wide working temperature
  • 150% peak load capability
  • Current sharing up to 960W(3+1)
  • DC output adjustable
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Protections: Short circuit / Overload / Over voltage / Over temperature / Input reverse polarity/ Input under voltage protection
  • 4KVdc 1/0 isolation(Reinforced isolation)
  • DC OK relay contact
  • Remote ON-OFF control
  • 3 vears warranty

Applications

  • Bus,tram, metro or railway system
  • Industrial control system
  • Semi-conductor fabrication equipment
  • Factory automation
  • Electro-mechanical
  • Wireless network
  • Telecom or datacom system

GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

DDR-240 series is a 240W DIN Rail type DC-DC converter with main features including DIN rail-type easy installation, ultra slim width (40mm), 2:1 wide input voltage, fanless design, -40 ~+70°C wide operating temperature, 4KVdc 1/0 isolation, 150% peak load, current sharing, DC OK, adjustable output voltage and full protective functions. This series of models has various input options: 16.8~33.6V / 33.6~67.2V / 67.2~154V and two output options: 24V / 48V and can be used for industrial & railway control, security control, communication system and other fields. Suitable applications include to DC buck/boost regulator, increasing system insulation level and voltage drop compensation along cable…etc.

Model Encoding

MEAN WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-Converter-
\(3\)

SPECIFICATION

MODEL| DDR-240B-24| DDR-240B-48| DDR-240C-24| DDR- 240C-48| DDR-240D-24| DDR-240D-48
---|---|---|---|---|---|---









OUTPUT

| DC VOLTAGE| 24V| 48V| 24V| 48V| 24V| 48v
RATED CURRENT| 10A| 5A| 10A| 5A| 10A| 5A
CURRENT RANGE| 0 ~ 10A| 0 ~ 5A| 0 ~ 10A| 0 ~ 5A| 0 ~ 10A| 0 ~ 5A
RATED POWER| 240W| 240W| 240W| 240W| 240W| 240W
PEAK| CURRENT| 15A| 7.5A| 15A| 7.5A| 15A| 7.5A
POWER Note.5| 360W (3sec.)
RIPPLE & NOISE (max.) **Note.2| 80mVp-p| 100mVp-p| 80mVp-p| 100mVp-p| 80mVp-p| 100mVp-p
VOLTAGE ADJ. RANGE| 24 ~ 28V| 48 ~ 56V| 24 ~ 28V| 48 ~ 56V| 24 ~ 28V| 48~ 56V
VOLTAGE TOLERANCE Note.3| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 60ms
HOLD UP TIME (Typ.)**| Please refer to page 6 Hold up Time( Load de-rating curve )




INPUT

| VOLTAGE RANGE Note.4| CONTINUOUS| 16.8 ~ 33.6Vdc| 33.6 ~ 67.2Vdc| 67.2 ~ 154Vdc
100ms| 14.4 ~ 16.8Vdc| 28.8 ~33.6Vdc| 66 ~ 67.2Vdc
EFFICIENCY (Typ.)| 90%| 90%| 91%| 92%| 92%| 92.5%
DC CURRENT (Typ.)| 11.2A @24Vdc| 5.6A @48Vdc| 2.5A @110Vdc
INRUSH CURRENT (Typ.)| 30A


INTERRUPTION OF VOLTAGE SUPPLY

| EN50155:2007-B/C- type comply with S2 level (10ms)@ 70% load ; D-type comply with S2 level (10ms)@ full load
EN50155:2017-Comply with S1 level





PROTECTION

| ****

OVERLOAD Note.5

| Normally works within 150% rated output power for more than 3 seconds and then constant current protection 105~135% rated output power with auto- recovery


OVER VOLTAGE

| 28.8 ~ 35V| 57.6 ~ 65.0V| 28.8 ~ 35V| 57.6 ~ 65V| 28.8 ~ 35V| 57.6 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, re-power on to recover


UNDER VOLTAGE LOCKOUT

| 24Vin (B – type) :Power  ON≥16.8V ,

OFF≤16.5V

| 48Vin (C – type) :Power ON≥33.6V ,

OFF≤33V

| 110Vin (D – type):Power ON≥67.2V ,

OFF≤65V


FUNCTION

| DC OK REALY CONTACT RATINGS (max.)| 30Vdc/1A resistive load
CURRENT SHARING| Up to 960W (3+1 units). Please refer to the Function Manual
REMOTE ON-OFF CONTROL| Please refer to the Function Manual




ENVIRONMENT

| WORKING TEMP.| -40 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 5 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85, 5 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 55℃)
VIBRATION| Component:10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC61373
OPERATING ALTITUDE Note.7| 5000 meters









SAFETY & EMC

(Note 6)

| SAFETY STANDARDS| IEC 62368-1, UL 62368-1, EAC TP TC 004, AS/NZS 62368.1 approved
WITHSTAND VOLTAGE| I/P-O/P:4KVdc I/P-FG:2.5KVdc O/P-FG:0.71KVdc
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500Vdc / 25℃/ 70% RH




EMC EMISSION

| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032| Class B
Radiated| BS EN/EN55032| Class B
Voltage Flicker| BS EN/EN61000-3-3| —–
Harmonic Current| —–| —–







EMC IMMUNITY

| BS EN/EN55035 , BS EN/EN61000-6-2(BS EN/EN50082-2)
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 3, 6KV contact; criteria A
Radiated| BS EN/EN61000-4-3| Level 3, 10V/m ; criteria A
EFT / Burst| BS EN/EN61000-4-4| Level 3, 2KV ; criteria A
Surge| BS EN/EN61000-4-5| Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-FG ;criteria A
Conducted| BS EN/EN61000-4-6| Level 3, 10V ; criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m ; criteria A
RAILWAY STANDARD| Compliance to BS EN/EN45545-2 for fire protection ; Meet BS EN/EN50155 / IEC60571 including IEC61373 for shock & vibration, BS EN/EN50121-3-2 for EMC


OTHERS

| MTBF| 1415.6K hrs min.       Telcordia SR-332 (Bellcore) ; 189.9K hrs min.         MIL-HDBK-217F (25℃)
DIMENSION| 40125.2113.5mm (WHD)
PACKING| 0.76Kg;20psc/16.2Kg/1.16CUFT





NOTE

|

  1. All parameters NOT specially mentioned are measured at normal input (B:24Vdc , C:48Vdc , D:110Vdc ) , rated load and 25℃ of ambient temperature.
  2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
  3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. Derating may be needed under low input voltage. Please check the derating curve for more details.
  5. 3 seconds max., please refer to peak loading curves.
  6. The power supply is considered as an independent unit, but the final equipment still need to confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
  7. (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
  8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

MEAN WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-Converter-
\(4\)

Derating Curve
Output derating VS input voltage

MEAN WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-Converter-
\(5\)

Peak Loading

MEAN WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-Converter-
\(6\)

DC OK Relay Contact

Contact Close PSU turns on / DC OK.
Contact Open PSU turns off / DC Fail.
Contact Ratings (max.) 30V/1A resistive load.

Function Manual

  1. Current sharing

  2. Parallel operation is available by connecting the units shown as below (P+,P- are connected mutually in parallel) :

  3. The voltage difference among each output should be minimized that less than 0.2V is required.

  4.  The total output current must not exceed the value determined by the following equation (Output current at parallel operation) =(The rated current per unit) x (Number of unit) x 0.9.

  5. In parallel operation 4 units is the maximum, please consult the manufacture for other applications.

  6.  When in parallel operation, the minimum output load should be greater than 3% of total output load.
    (Min. load > 3% rated current per unit x number of unit)
    MEAN WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-Converter-
\(7\)

  7. Remote ON-OFF Control
    ※ The power supply can be turned ON-OFF by using the “Remote ON-OFF” function.

Remote ON-OFF (TB1 PIN2,4)|

Output Status

---|---
Open or 4 ~ 10VDC| power supply ON
Short or 0 ~ 0.8VDC| power supply OFF

Input Fuse
There is one fuse connected in series to the positive input line, which is used to protect against abnormal surge. Fuse specifications of each model are shown as below.

Type Fuse Type Reference and Rating
B Time-Lag Conquer MST, 10A, 250V *2
C Time-Lag Conquer MST, 6.3A, 250V *2
D Time-Lag Conquer MST, 6.3A, 250V *1

Input Under-Voltage Protection

If input voltage drops below Vimin, the internal control IC shuts down and there is no output voltage. It recovers automatically when input voltage reaches above Vimin,please refer to the cruve below.

MEAN WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-Converter-
\(8\)

Input Reverse Polarity Protection

There is a MOSFET connected in series to the negative input line. If the input polarity is connected reversely, the MOSFET opens and there will be no output to protect the unit.

Inrush Current
Inrush current is suppressed by a resistor during the initial start-up, and then the resistor is bypassed by a MOSFET to reduce power consumption after accomplishing the start-up.

Hold-up Time
EN50155: 2007 version – B/C- type comply with S2 level (10ms)@ 70% load ; D-type comply with S2 level (10ms)@ full load, P easelrefer to thetable and cu vesr show below for the holdu time specification.

Load

Model

| 100% load| 70% load| other load
---|---|---|---
B type (24Vin)| 6ms min.| 10ms min.| figure 1,2
C type (48Vin)| 8ms min.| 11ms min.| figure 3,4
D type (110Vin)| 11ms min.| 15ms min.| figure 5,6

MEAN WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-Converter-
\(9\)

MEAN WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-Converter-
\(10\)

EN50155: 2017 version – Comply with S1 level

Efficiency vs Load & Vin Curve

The efficiency vs load & Vin curves of each model are shown as below.

MEAN WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-Converter-
\(11\) MEAN WELL-DDR-240-Series-
240W-DIN-Rail-Type-DC-Converter- \(12\)

Immunity to Environmental Conditions

Test method Standard Test conditions Status
Cooling Test EN 50155 section 12.2.3 (Column 2, Class TX)

EN 60068-2-1

| Temperature: -40℃

Dwell Time: 2 hrs/cycle

| No damage


Dry Heat Test

| EN 50155 section 12.2.4 (Column 2, Class TX)

EN 50155 section 12.2.4 (Column 3, Class TX & Column 4, Class TX) EN 60068-2-2

| ****

Temperature: 70℃ / 85℃ Duration: 6 hrs / 10min

| ****

PASS


Damp Heat Test, Cyclic

| ****

EN 50155 section 12.2.5

EN 60068-2-30

| Temperature: 25℃~55℃ Humidity: 90%~100% RH Duration: 48 hrs| ****

PASS


Vibration Test

| EN 50155 section 12.2.11

EN 61373

| Temperature: 19℃ Humidity: 65%

Duration: 10 mins

| ****

PASS


Increased Vibration Test

| ****

EN 50155 section 12.2.11

EN 61373

| Temperature: 19℃ Humidity: 65%

Duration: 5 hrs

| ****

PASS


Shock Test

| ****

EN 50155 section 12.2.11

EN 61373

| Temperature: 21± 3℃ Humidity: 65 ± 5%

Duration: 30ms*18

| ****

PASS


Low Temperature Storage Test

| ****

EN 50155 section 12.2.3 (Column 2, Class TX)

EN 60068-2-1

| ****

Temperature: -40℃ Dwell Time: 16 hrs

| ****

PASS


Salt Mist Test

| ****

EN 50155 section 12.2.10 (Class ST4)

| ****

Temperature: 35℃±2℃ Duration: 96 hrs

| ****

PASS

EN45545-2 Fire Test Conditions

Test Items Hazard Level

| Items| Standard| ****

HL1

| ****

HL2

| ****

HL3





R22

| ****

Oxygen index test

| EN 45545-2:2013

EN ISO 4589-2:1996

| ****

PASS

| ****

PASS

| ****

PASS


Smoke density test

| EN 45545-2:2013

EN ISO 5659-2:2006

| ****

PASS

| ****

PASS

| ****

PASS


Smoke toxicity test

| EN 45545-2:2013 NF X70-100:2006| ****

PASS

| ****

PASS

| ****

PASS


R24

| ****

Oxygen index test

| EN 45545-2:2013

EN ISO 4589-2:1996

| ****

PASS

| ****

PASS

| ****

PASS


R25

| ****

Glow-wire test

| EN 45545-2:2013

EN 60695-2-11:2000

| ****

PASS

| ****

PASS

| ****

PASS


R26

| ****

Vertical flame test

| EN 45545-2:2013

EN 60695-11:2003

| ****

PASS

| ****

PASS

| ****

PASS

Mechanical Specification

MEAN WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-Converter-
\(13\)

Installation Instruction

MEAN WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-Converter-
\(1\)

This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the Instruction manual.

Installation Manual

Please refer to : http://www.meanwell.com/manual.html

Downloaded from Arrow.com.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals