MEAN WELL HDR-15-5 Ultra Slim Step Shape DIN Rail Owner’s Manual
- June 1, 2024
- MEAN WELL
Table of Contents
15W Ultra Slim Step Shape DIN Rail
HDR-15 series
UL508 UL62368 1 BS EN/EN61558 R33100 ROHS
TPTC004 AS/NZS60950-1 IEC62368-1
Features
- Ultra slim design with 17.5mm(1SU) width
- Universal input 85~264VAC(277VAC operational)
- No load power consumption<0.3W
- Isolation class II
- Pass LPS (Limited power source)
- DC output voltage adjustable
- Protections : Short circuit / Overload / Over voltage
- Cooling by free air convection (working temperature:-30~+70°C)
- DIN rail TS-35/7.5 or 15 mountable
- LED indicator for power on
- 3 years warranty
Applications
- Household control system
- Building automation
- Industrial control system
- Factory automation
- Electro-mechanical apparatus
GTIN CODE
MW Search https://www.meanwell.com/serviceGTIN.aspx
Description
HDR-15 is one economical ultra slim 15W DIN rail power supply series, adapt to
be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed
17.5mm(1SU) in width, which allows space saving inside the cabinets. The
entire series adopts the full range AC input from 85VAC to 264VAC(277VAC
operational) and conforms to BS EN/EN61000-3-2, the norm the European Union
regulates for harmonic current.
HDR-15 is designed with plastic housing that it can effectively prevent user
from electric hazards. With working efficiency up to 87%, the entire series
can operate at the ambient temperature between -30°C and 70°C under air
convection. The complete protection functions and relevant certificates for
home automations and industrial control apparatus (IEC62368-1, UL508,
UL62368-1, BS EN/EN61558-2-16) make HDR-15 a very competitive power supply
solution for household and industrial applications.
Model Encoding
- Output voltage
- Rated wattage
- Series name
SPECIFICATION
MODEL| HDR-15-5| HDR-15-12| HDR-15-15| HDR-15-24|
HDR-15-48
---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 5V| 12V| 15V| 24V| 48V
RATED CURRENT| 2.4A| 1.25A| 1A| 0.63A| 0.32A
CURRENT RANGE| 0 ~ 2.4A| 0 ~ 1.25A| 0 ~ 1A| 0 ~ 0.63A| 0 ~ 0.32A
RATED POWER| 12W| 15W| 15W| 15.2W| 15.4W
RIPPLE & NOISE (max.) Note.2| 80mVp-p| 120mVp-p | 120mVp-p| 150mVp-p|
240mVp-p
VOLTAGE ADJ. RANGE| 4.5 ~ 5.5V| 10.8 ~ 13.8V| 13.5 ~ 18V| 21.6 ~ 29V|
43.2 ~ 55.2V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 2000ms, 80ms/230VAC 2000ms, 80ms/115VAC at full
load
HOLD UP TIME (Typ.)| 30ms/230VAC 12ms/115VAC at full load
INPUT| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational ) 120 ~
370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 80%| 85%| 85.5%| 86%| 87%
AC CURRENT (Typ.)| 0.5A/115VAC 0.25A/230VAC
INRUSH CURRENT (Typ.)| COLD START 25A/115VAC 45A/230VAC
PROTECTION| OVERLOAD| 110 ~ 145% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault
condition is removed
Constant current limiting within 50% ~100% rated output voltage, recovers
automatically after fault condition is removed
OVER VOLTAGE| 5.75 ~ 6.75V| 14.2 ~ 16.2V| 18.8 ~ 22.5V| 30 ~ 36V| 56.5 ~
64.8V
Protection type : Shut off o/p voltage, clamping by zener diode
ENVIRONMENT| WORKING TEMP.| -30 ~ +70°C (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85 °C, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/°C (0 ~ 50°C) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X,
Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters
OVER VOLTAGE CATEGORY| III; According to EN61558, EN50178,EN60664-1,
EN62477-1; altitude up to 2000 meters
SAFETY & EMC (Note 4)| SAFETY STANDARDS| UL62368-1, UL508, TUV BS
EN/EN61558-2-16, BS EN/EN61558-1, IEC62368-1, EAC TP TC 004, BSMI CNS14336-1
approved; Design refer to TUV BS EN/EN62368-1
WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25°C / 70% RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32), CNS13438| Class B
Radiated| BS EN/EN55032(CISPR32), CNS13438| Class B
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| ——-
EMC IMMUNITY| BS EN/ BS EN/ BS EN/ EN55035, EN61000-6-2, EN61204-3
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, criteria A
EFT/Burest| BS EN/EN61000-4-4| Level 3, criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11| > 95% dip 0.5 periods, 30%
dip 25 periods, > 95% interruptions 250 periods
OTHERS| MTBF| 3724.3K hrs min. Telcordia SR-332 (Bellcore) ;
1166.1K hrs min. MIL-HDBK-217F (25 °C)
DIMENSION| 17.59054.5mm (WHD)
PACKING| 74g;160pcs/12.9Kg/1.09CUFT
NOTE|
- All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.
- Tolerance : includes set up tolerance, line regulation and load regulation.
- The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
- The ambient temperature derating of 3.5°C/1000m with fanless models and of 5°C/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve
Output Derating VS Input Voltage
Mechanical Specification
(Unit: mm, tolerance ± 0.5mm)
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Terminal Pin No. Assignment
Pin No.
| Assignment| Pin No.| Assignment
---|---|---|---
1| +V| 3|
AC/N
2
| -V| 4|
AC/L
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
File Name:HDR-15-SPEC 2023-12-18