EG4 Wallmount Indoor 280Ah Lithium Battery User Guide
- June 1, 2024
- Eg4
Table of Contents
EG4 Wallmount Indoor 280Ah Lithium Battery
Specifications
-
Product: EG4 Wallmount Indoor 280Ah Lithium Battery
Voltage: 51.2V -
Capacity: 280Ah
-
Charging Voltage (Bulk/Absorb): 56.0V (+/-0.8V) to 56.2V (+/-0.2V)
-
Float Voltage: 54V (+/-0.2V)
-
Low DC Cutoff: 44.8V to 47-45.6V
-
Charging Current: 60A to 200A (Max. continuous)
-
Discharging Current: 160A to 200A (Max. continuous)
-
Ingress Protection: IP20
-
Cell Voltage Protection: 3.8V
-
Module Voltage Protection: 60.0V to 55.2V
-
Over Charging Current 1: >205A for 10 sec
-
Over Charging Current 2: >225A for 3 sec
-
Temperature Protection: Various levels of protection
Installation
- Ensure the battery is placed in a well-ventilated area with proper clearance.
- Connect the battery to the appropriate power source using the recommended voltage settings.
- Securely mount the battery on a stable surface following the
manufacturer’s guidelines.
Charging
- Set the charging voltage within the specified range of 56.0V to 56.2V.
- Monitor the charging current and adjust as needed, keeping it between 60A to 200A.
- Ensure proper float voltage maintenance during charging to prevent overcharging.
Discharging
- Maintain discharging current within the recommended range of 160A to 200A for optimal performance.
- Avoid discharging below the low DC cutoff voltage to prevent damage to the battery.
Frequently Asked Questions (FAQ)
- Q: What should I do if the battery overheats during charging?
A: Immediately disconnect the battery from the power source andallow it to cool down before attempting to charge again.
EG4 WALLMO UNT IN DO O R
280Ah LIT HIUM B ATT ERY
QUICK- START GUIDE
This guide has been created to give the end-user a quick and easy process to
install and commission the WallMount Indoor 280Ah Lithium battery in a variety
of configurations.
TECHNICAL SPECIFICATIONS
MODULE OPERATING PARAMETERS
PARAMETER| BMS| Recommended Setting
VOLTAGE| 51.2V| | –
CAPACITY| 280Ah| | –
CHARGING VOLTAGE (BULK/ABSORB)| 56.0V (+/-0.8V)| | 56.2V (+/-0.2V)
FLOAT| –| | 54V (+/-0.2V)
LOW DC CUTOFF| 44.8V| 47-45.6V (start high, lower as needed)
CHARGING CURRENT| 200A (Max. continuous)| | 60A – 160A
DISCHARGING CURRENT| 200A (Max. continuous)| | 160A
ENVIRONMENTAL PARAMETERS| | |
CHARGING RANGE| | 32° to ≈113°F (0°C to ≈45°C)
DISCHARGING RANGE| | -4°F to ≈122°F (-20°C to ≈50°C)
STORAGE RANGE| | -4°F to ≈122°F (-20°C to ≈50°C)
INGRESS PROTECTION| | IP20|
C H AR G I N G / D I S C
H AR G IN G P ARA M E T E R
S
CHARGE| Spec| Delay| Recovery
CELL VOLTAGE PROTECTION| 3.8V| 1 sec| 3.45V
MODULE VOLTAGE PROTECTION| 60.0V| 1 sec| 55.2V
OVER CHARGING CURRENT 1| >205A| 10 sec| –
OVER CHARGING CURRENT 2| >225A| 3 sec| –
TEMPERATURE PROTECTION| <23°F or >158°F
<-5°C or >70°C
| 1 sec| >32°F or <140°F
0°C or <60°C
DISCHARGE| Spec| Delay| Recovery
CELL VOLTAGE PROTECTION| 2.3V| 1 sec| 3.1V
MODULE VOLTAGE PROTECTION| 44.8V| 1 sec| 48V
OVER-CHARGING CURRENT 1| >205A| 10 sec| 60 sec
OVER-CHARGING CURRENT 2| >300A| 3 sec| 60 sec
SHORT CIRCUIT| >600A| <0.1 mS| –
TEMPERATURE PROTECTION| <-4°F or >167°F
<-20°C or >75°C
| 1 sec| >14°F or <149°F
-10°C or <65°C
PCB TEMP PROTECTION| >230°F (>110°C)| 1 sec| @ <176°F (<80°C)
GENERAL SPECIFICATIONS| | |
PARAMETER| Spec| | Condition
CELL BALANCE| 120mA| Passive Balance| Cell Voltage Difference >40mV
TEMPERATURE ACCURACY| 3%| Cycle Measurement| Measuring Range -40°F to ≈212°F
(-40°C to ≈100°C)
VOLTAGE ACCURACY| 0.5%| Cycle Measurement| For Cells & Module
CURRENT ACCURACY| 3%| Cycle Measurement| Measuring Range -200A – 200A
SOC| 5%| –| Integral Calculation
POWER CONSUMPTION| Sleep & Off Mode| <300uA| Storage/Transport/Standby
POWER CONSUMPTION| Operating Mode| <25mA| Charging/Discharging
COMMUNICATION PORTS| RS485/CAN| Can be customized
BATTERY HEATER
SPECIFICATIONS
| | |
PARAMETER| Spec| | Condition
VOLTAGE| 56V| | –
POWER CONSUMPTION| 224W| | –
INTERNAL BATTERY TEMPERATURE| ≤32°F (0°C)/≥41°F (5°C)| Heat On/Heat Off
PHYSICAL SPECIFICATIONS|
---|---
DIMENSIONS (H×W×D)| 36.4 in.×18.1 in.×9.6 in. (925 mm×460 mm×245 mm)
WEIGHT| 282.2 lbs. (128 kg)
DESIGN LIFE| >15 Years
CYCLE LIFE| >8000 Cycles, 0.5C 80% DOD
LIFETIME PRODUCTION| 82.6MWh*
SAFETY CERTIFICATIONS|
CERTIFICATIONS| UL1973, UL 9540A (Testing)
*(51.2V×280Ah/1000×80%×8000 cycles/1000)90%=MWh
ABBREVIATIONS
- AWG – American Wire Gauge
- A – Amp(s)
- Ah – Amp hour(s)
- AC – Alternating Current
- AFCI-Arc-Fault Circuit Interrupter
- AHJ – Authority Having Jurisdiction
- ANSI – American National Standards Institute
- BAT-Battery
- BMS – Battery Management System
- COM-Communication
- CT-Current Transformer
- DC – Direct Current
- DIP – Dual In-line Package
- DOD – Depth of Discharge
- EG – Equipment Ground
- EGS – Equipment Grounding System
- EMC-Electromagnetic Compatibility
- EPS – Emergency Power System
- ESS – Energy Storage System
- E-Stop-Emergency Stop
- E-Stop NO – Emergency Stop Normally Open
- FCC-Federal Communication Commission
- GE – Grounding Electrode
- GEC – Grounding Electrode Conductor
- GEN-Generator
- GES – Grounding Electrode System
- GFCI-Ground Fault Circuit Interrupter
- GFDI-Ground Fault Detector/Interrupter
- Imp – Maximum Power Point Current
- IEEE-Institute of Electrical and Electronic Engineers
- IP-Ingress Protection
- Isc – Short-Circuit Current
- In. lbs. – Inch Pounds
- kW – Kilowatt
- kWh – Kilowatt-hour
- LCD-Liquid Crystal Display
- LFP – Lithium Iron Phosphate or LiFePO4
- L1-Line 1; Typically, a black wire
- L2-Line 2; Typically, a red wire
- mm – Millimeter(s)
- MPPT-Maximum Power Point Tracking
- mV – Millivolt(s)
- N-Neutral; Typically, a white wire
- NEC – National Electrical Code
- NEMA- National Electrical Manufacturers Association
- NFPA – National Fire Prevention Association
- Nm – Newton Meters
- NOCT-Normal Operating Cell Temperature
- PC – Personal Computer
- PCB – Printed Circuit Board
- PE – Protective Earth (G or Ground);
- Pnum-Parallel Number
- PPE – Personal Protective Equipment
- PV – Photovoltaic
- RSD – Rapid Shut Down
- SCC- Standards Council of Canada
- SOC – State of Charge
- STC – Standard Testing Conditions
- UL-Underwriters Laboratories
- UPS-Uninterrupted Power Supply
- V – Volt(s)
- VOC – Open-Circuit Voltage
- VMP – Voltage Maximum Power
SAFETY
SAFETY INSTRUCTIONS
International safety regulations have been strictly observed in the design and
testing of the inverter. Before beginning any work, carefully read all safety
instructions, and always observe them when working on or with the inverter.
The installation must follow all applicable national or local standards and
regulations.
Incorrect installation may cause:
- Injury or death to the installer, operator or third party
- Damage to the inverter or other attached equipment
IMPORTANT SAFETY NOTIFICATIONS
There are various safety concerns that must be carefully observed before,
during, and after the installation, as well as during future operation and
maintenance. The following are important safety notifications for the
installer and any end users of this product under normal operating conditions.
- Do not disassemble the battery. Contact the distributor for any issues that need repair for more information and proper handling instructions. Incorrect servicing or re-assembly may result in a risk of electric shock or fire and void the warranty.
- Never short-circuit DC inputs. Short-circuiting the battery may result in a risk of electric shock or fire and can lead to severe injury or death and/or permanent damage to the unit and/or any connected equipment.
- Use caution when working with metal tools on or around batteries and systems. Risk of electrical arcs and/or short circuiting of equipment can lead to severe injury or death and equipment damage.
- Beware of high battery current. Please ensure that the battery module breakers and/or on/off switches are in the “open” or “off” position before installing or working on the battery. Use a voltmeter to confirm there is no voltage present to avoid electric shock.
- Do not make any connections or disconnections to the system while the batteries are operating. Damage to system components or risk of electrical shock may occur if working with energized batteries.
- Make sure the battery and rack are properly grounded.
- An installer should make sure to be well protected by reasonable and professional insulative equipment [e.g., personal protective equipment (PPE)].
- Before installing, operating, or maintaining the system, it is important to inspect all existing wiring to ensure it meets the appropriate specifications and conditions for use.
- Ensure that the battery and system component connections are secure and proper to prevent damage or injuries caused by improper installation.
WARNING: To reduce the risk of injury, read all instructions!
All work on this product (system design, installation, operation, setting, configuration, and maintenance) must be carried out by qualified personnel. To reduce the risk of electric shock, do not perform any servicing other than those specified in the operating instructions unless qualified to do so.
- Read all instructions before installing. For electrical work, follow all local and national wiring standards, regulations, and these installation instructions.
- Make sure the inverter is properly grounded. All wiring should be in accordance with the National Electrical Code (NEC), ANSI/NFPA 70.
- The inverter and system can interconnect with the utility grid only if the utility provider permits. Consult with the local AHJ (Authority Having Jurisdiction) before installing this product for any additional regulations and requirements for the area.
- All warning labels and nameplates on this inverter should be clearly visible and must not be removed or covered.
- The installer should consider the safety of future users when choosing the inverter’s correct position and location as specified in this manual.
- Please keep children away from touching or misusing the battery and relevant systems.
DISCLAIMER
EG4 reserves the right to make changes to the material herein at any time
without notice.
Please refer to www.eg4electronics.com for
the most updated version of our manuals/spec sheets.
PACKING LIST
The items listed below will arrive with the product shipment:
EG4 WallMount Indoor 280Ah
LOCATION SELECTION AND INSTALLATION
Requirements for installation location:
- The WallMount Indoor battery is heavy. Use a lift or other equipment to lift and carry the unit.
- The battery can be installed against a flat wall, but the weight of the battery should not be fully supported by the wall. To help with this requirement, the battery comes with pre-installed feet that should be used to carry the weight of the battery.
- If the battery is installed against a wall, the wall should be made of non-combustible material. If this is not possible, then the unit MUST have a minimum of 2 in. (50.8mm) clearance from the wall. Also note that whatever mounting solution that is used to grant the 2 in. clearance from the wall MUST be made of a non-combustible material.
- If installing on flat ground as a standalone unit, ensure there is proper drainage on the ground surrounding the battery to maintain integrity of the module over time and prevent damage from flooding. If installing against a wall, ensure at least a 12 in. (305mm) gap on each side of the unit for adequate airflow and operations.
- Ensure the battery is mounted upright.
NOTE: The battery will be shipped with temporary lifting handles for removing the battery from its packaging. The battery is very heavy. Use the team-lift technique during installation and remove the temporary lifting handles before making any connections within the system.
PARALLEL EXAMPLES
The diagrams below show different parallel orientations. These diagrams are for reference only!
BATTERY CABLE CONNECTIONS
The following battery cable connection diagrams are examples using the
internal busbars to parallel the batteries together and attach the inverter(s)
to the batteries. When relying on the internal busbars, up to 3 batteries are
supported in parallel when connected to a single inverter, 4 batteries in
parallel when connected to 2 inverters, or up to 5 batteries in parallel when
connected to 3 inverters.
Systems with more batteries than these configurations require the use of an
external fused positive busbar and an unfused negative busbar rated at a
minimum of 200A per battery. Each fuse should be a maximum of 250A.
Alternatively, larger systems could rely on the 18kPV’s ability to draw from
different battery packs while still paralleling inverters rather than
utilizing external busbars.
The maximum recommended number of paralleled 18kPV inverters is 6. If this approach is used, we recommend a ratio of 2 batteries per pack controlled by each 18kPV inverter. Separating packs is only recommended if each pack’s average SOC is monitored over time and does not diverge by more than 10%. Common busbars are superior to separating battery packs but it may be difficult to source fused positive busbars rated to greater than 1800 Amps. This translates into separating packs larger than 9 batteries. Refer to NEC code and the local AHJ for exact requirements.
NOTE: In the following diagrams, units are spaced 12 in. apart. Local regulations may require a larger minimum battery spacing. Check with the local AHJ for these requirements. If longer parallel cables than are available in the optional paralleling kit are necessary, please check with the distributor for availability.
Note: To comply with the UL9540 listing for this integrated battery, conduit
box, and inverter system, the batteries must be wired as shown using the
supplied inverter to battery cables. An additional paralleling kit is required
for each additional paralleled battery (sold separately).
Caution: To minimize voltage drop in the wire, the battery cables should
maintain optimum length. The 53.1 in. cables from the “parallel kit” are
sufficient to daisy chain the batteries.
Figure 1 – (1) 18kPV Inverter with (1) WallMount
ADDITIONAL CONFIGURATIONS
Note: Some configurations require additional
wiring/connectors to achieve the example layouts. Inverter to inverter
paralleling cables are not shown in the following diagrams.
Other configurations can be achieved by using external busbars. Please seek
the guidance of an electrician or qualified personnel for optional system
layout.
Figure 2 – (1) 18kPV Inverter with (2) WallMount
Pro Tip: One EG4-18kPV and a minimum of 2 WallMount units is the recommended configuration to maximize the system’s functionality.
Color Code
Reminder!
The separation between batteries should be ≥ 12 in.
Figure 3 – (1) 18kPV Inverter with (3) WallMount
Figure 4 – (2) 18kPV Inverter with (2) WallMount
Figure 5 – (2) 18kPV Inverter with (3) WallMount
Figure 6 – (2) 18kPV Inverter with (4) WallMount
Figure 7 – (3) 18kPV Inverter with (3) WallMount
Figure 8 – (3) 18kPV Inverter with (4) WallMount
ORIENTATION EXAMPLES
INSTALLING THE BATTERY
Follow the steps listed below to ensure the WallMount Indoor battery is mounted correctly.
WARNING: Do not put EG4 WallMount batteries in series!
The BMS and internal components are not designed to handle this setup, which
could cause the modules to fail, leading to damage.
NOTE: The battery will be shipped with temporary lifting handles for removing
the battery from its packaging. EG4 recommends these handles be removed before
making any connections.
STANDALONE BATTERY INSTALL
- Remove the 4 set screws holding the mounting bracket to the back of the battery pack and set them to the side.
- Remove the mounting bracket from the battery.
- Position the bottom of the mounting bracket on the wall at desired mounting height, with a minimum clearance of 29.2 in. (74.2mm) from the ground.
- Using a level, ensure the bracket is level and drill 6 holes to accommodate the mounting hardware used.
- Secure the mounting bracket to the wall using the included expansion bolts or appropriate hardware required for the mounting surface.
- Attach the battery pack to the mounting bracket. Using the team-lift technique, lift the battery and hook the back flange onto the front flange of the mounting bracket.
- Secure the battery to the mounting bracket using the 4 included side screws.
- Finally, properly ground the battery, attaching a grounding conductor to the M6 grounding screw on top of the battery to the Equipment Grounding System. DO NOT GROUND THE NEGATIVE BATTERY CABLE!
Rear View
BATTERY INSTALL WITH CONDUIT BOX
- Remove the 4 set screws holding the mounting bracket to the back of the battery pack and set them to the side.
- Remove the mounting bracket from the battery.
- Position the mounting bracket on the wall at desired mounting height, with a minimum clearance of 29.2 in. (74.2mm).
- Using a level, ensure the bracket is level and drill 6 holes to accommodate the mounting hardware used.
- Secure the mounting bracket to the wall using the included expansion bolts (concrete or brick walls) or appropriate hardware for the mounting surface.
- Attach the battery to the mounting bracket. Using the team-lift technique, lift the battery and hook its back flange onto the front flange of the mounting bracket.
- Secure the battery to the mounting bracket using the 4 included side screws.
- Attach the optional conduit box to the top of the battery using the included hardware.
- Finally, properly ground the battery, attaching a grounding conductor to the M6 grounding screw on top of the battery to the equipment grounding system. DO NOT GROUND THE NEGATIVE BATTERY CABLE!
NOTE: If mounting the bracket at 29.2 in. (74.2mm) from the ground, the battery will rest on the ground.
BATTERY INSTALL WITH CONDUIT BOX & EG4 INVERTER
The WallMount Indoor battery is designed to integrate with the EG4 18kPV hybrid inverter, as well as the 6000XP off-grid inverter.
Follow the steps listed below to ensure proper connections are made in the system:
- Remove the 4 set screws holding the mounting bracket to the back of the battery pack and set them to the side.
- Remove the mounting bracket from the battery.
- Position the mounting bracket on the wall at desired mounting height, with a minimum clearance of 29.2 in. (74.2mm).
- Using a level, ensure the bracket is level and drill 6 holes to accommodate the mounting hardware used.
- Align the provided X-bracket with the holes on the mounting bracket and secure both to the wall, using the included expansion bolts (concrete/brick walls) or appropriate hardware required for the mounting surface. The X-bracket will be behind the mounting plate, against the wall.
- Attach the optional conduit box to the top of the battery using the included hardware.
- Attach the inverter to the mounting bracket and ensure the inverter’s bottom knockouts align with the conduit box.
- Finally, properly ground the battery, attaching a grounding conductor to the M6 grounding screw on top of the battery to the equipment grounding system. DO NOT GROUND THE NEGATIVE BATTERY CABLE!
The image to the right represents a completed install showing a rear view.
PRE-WIRE STEPS AND WIRING
Refer to the table below for wire size and torque recommendations for the
battery cables.
# OF CABLES | CABLE SIZE | MAX. DISTANCE | TORQUE VALUES |
---|---|---|---|
2 sets (18kPV) | 1/0 AWG (53.5 mm2) | 10 ft. | Max. 165 in-lbs. (18.6 Nm) |
2 sets (18kPV) | 2/0 AWG (67.4 mm2) | 20 ft. | Max. 165 in-lbs. (18.6 Nm) |
1 set (6000XP) | 1 AWG (38 mm2) | 10 ft. | Max. 106 in-lbs. (12 Nm) |
IMPORTANT
The battery can charge/discharge up to 200A before the BMS shuts off the pack.
Ensure the inverter is configured to handle this high of a current and size
all wires accordingly! Refer to an NEC approved ampacity chart or consult with
the installer or a solar electrician for more information.
MULTIPLE BATTERY PARALLEL INSTALL
When paralleling multiple WallMount Indoor batteries, a paralleling kit must
be purchased through the distributor.
Follow the steps outlined below to ensure proper installation of multiple
batteries in parallel.
-
Ensure all circuit breakers are open (off). Using a multimeter, check for voltage at all available disconnects and lines. Once no voltage is confirmed, proceed to the next step.
-
Set the DIP switch address on the master battery to address 1, and all other batteries in parallel to differing addresses going in ascending order. (See image)
-
Reset the battery BMS via the power button to register the address change.
-
Set up communication between the batteries via the “Battery-Comm” ports by using a CAT 5, 5e, or 6 cable.
-
The battery set to address 1 will connect directly to the inverter BMS communication port via CAT 5, 5e or CAT 6 cable.
-
Install battery paralleling cables between the batteries included in the optional paralleling kit ensuring the connectors are seated properly.
MULTIMETER TESTING AND WIRING
Follow the steps outlined below to both test the inputs and wire the battery
pack to the inverter.
-
Ensure all circuit breakers are open (off). Using a multimeter, check for voltage at all available disconnects and lines. Once no voltage is confirmed, proceed to the next step.
-
Connect the included sets of 2/0 AWG (70mm2) connectors to the battery’s positive and negative terminals. The connectors will “click” when seated properly.
NOTE: If installing the battery pack with the optional conduit box, secure the conduit fittings to the enclosure using the counter nuts after step 2. -
If applicable, route the battery power cables through the conduit box to the inverter without making any connections!
DANGER! No connections should be made until proper polarity of cables has been confirmed! -
Ensure proper polarity of cables. Once confirmed, proceed to the next step.
-
Install the 2 positive battery cables (1 positive cable for the 6000XP) to the inverter’s positive battery terminals following proper torque values.
-
Install the 2 negative battery cables (1 negative cable for the 6000XP) to the inverter’s negative battery terminals following proper torque values.
BMS COMMUNICATIONS
EG4 batteries interface with compatible inverters by designating a “Master”
battery (DIP switch ID No. 1).
The battery will connect directly to the inverter via an RS485 battery
communications cable or a standard CAT 5, 5e, or 6 cable for closed loop
communications with supported EG4 and non-EG4 inverters using CAN bus
protocol.
The PC software “BMS TOOLS” provides real-time battery analysis and
diagnostics. The battery cannot communicate with the software and a closed
loop inverter simultaneously.
Scan the QR code for a white sheet walking through the BMS Tools setup
process.
CLOSED LOOP COMMUNICATIONS
- Power off all battery DC breakers and BMS power buttons.
- The inverter protocol can only be changed with the master battery temporarily set to address 64 (all switches ON). After the DIP switch is changed, restart the BMS using the BMS power button for the settings to take effect. (See image)
- On the master battery, press and hold the “Return” key for 5 seconds and release to enter the “Protocol Setting” menu.
- Select the corresponding CAN protocol (P01-EG4/LUX) for the system if using EG4 inverters,(See table below).
- Change the master DIP switch address back to address 1 for inverter communications & power cycle the BMS. (See image)
CLOSED LOOP COMMS. WITH EG4 INVERTERS
MODEL| PROTOCOL SELECTION
18kPV/6000XP| CAN – P01
CAN PROTOCOL LIST
PROTOCOL #| MANUFACTURER
P01-EG4/LUX| EG4/LUX
P02-GRW| Growatt
P03-SLK| Sol-Ark
P04-DY| Deye
P05-MGR| Megarevo
P06-VCT| Victron
P07-LUX| Luxpower
P08-SMA| SMA
RS485 PROTOCOL LIST
PROTOCOL #| MANUFACTURER
P01-EG4| EG4
P02-GRW| Growatt
P03-SLK| Sol-Ark
P04-SCH| Schneider
*NOTE: Both the CAN Protocol and RS485 Protocol menus are password protected. The default password for both CAN and RS485 menus is “123456”.
*NOTE: Closed loop communications using RS485 protocols require a specific pinout on the comms cable from battery to inverter. Refer to the table below for EG4 specifics.
EG4 INVERTER MODEL | PROTOCOL | COMMUNICATION CABLE PINOUT |
---|
__
18kPV
| CAN| To inverter – RJ 45 Pin 4-H & Pin 5-L To battery – RJ 45 Pin 4-H & Pin
5-L
RS485| To inverter – RJ45 Pins 7-A & 8-B
To battery – RJ45 Pins 1-B & 2-A
__
6000XP
| CAN| To inverter – RJ 45 Pin 4-H & Pin 5-L To battery – RJ 45 Pin 4-H & Pin
5-L
RS485| To inverter – RJ45 Pins 1-B & 2-A
To battery – RJ45 Pins 1-B & 2-A
3000EHV (Legacy Product)| RS485| To inverter – USB Type B
To battery – RJ45 Pins 1-B & 2-A
__
8KEXP (Legacy Product)
| CAN| To inverter – RJ 45 Pin 4-H & Pin 5-L To battery – RJ 45 Pin 4-H & Pin
5-L
RS485| To inverter – RJ45 Pins 7-B & 8-A
To battery – RJ45 Pins 1-B & 2-A
6000EX (Legacy Product)| RS485| To inverter – RJ45 Pins 3 & 5 To battery –
RJ45 Pins 1-B & 2-A
6500EX (Legacy Product)| RS485| To inverter – RJ45 Pins 3 & 5
To battery – RJ45 Pins 1-B & 2-A
FIRMWARE UPDATES
Always ensure all system components are fully up to date before commissioning the system. Navigate to the EG4 WallMount Indoor battery product page by using the QR code below to find the latest downloads for the battery. A PDF walkthrough will be included in the downloaded .zip file.
If encountering difficulties during the updating process, contact the distributor for more information.
CONTACT US
support@eg4electronics.com
903-609-1988
www.eg4electronics.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>