FRIGIDAIRE FFAD2234W1 Low Humidity 22 Pint Energy Star Dehumidifier User Manual
- June 1, 2024
- Frigidaire
Table of Contents
FFAD2234W1 Low Humidity 22 Pint Energy Star Dehumidifier
“`html
Specifications
- Model Numbers: FFAD2234W1, FFAD3534W1
- Manufacturer: Frigidaire
- Country of Origin: USA/Canada
Product Information
Welcome to our family! This manual serves as your guide for the
proper use and maintenance of your dehumidifier. Please read
through it thoroughly before operating the appliance. Refer back to
it as needed for quick assistance with troubleshooting and care
instructions.
For additional resources, FAQs, tips, and support, visit our
website at www.frigidaire.com. Our
customer service team is also available via chat or phone to assist
you with any queries or issues you may encounter.
Product Usage Instructions
Important Safety Instructions
Before using the dehumidifier, ensure to read and understand all
safety precautions outlined in the manual. Failure to follow these
instructions may result in serious injury or damage to the
appliance.
Location
Place the dehumidifier in a well-ventilated area with access to
a grounded electrical outlet. Avoid using extension cords or
adapter plugs to prevent fire hazards or electric shock.
How It Works
The dehumidifier operates by removing excess moisture from the
air, helping to maintain a comfortable humidity level in your
space. It works by drawing in humid air, passing it over a cold
coil to condense the moisture, and then releasing dry air back into
the room.
Dehumidifier Features
Features of the dehumidifier include adjustable humidity
settings, a water tank for collected moisture, auto-shutoff when
the tank is full, and indicator lights for filter replacement.
Operating Instructions
To start using the dehumidifier, plug it into a power source,
set your desired humidity level, and turn the unit on. Empty the
water tank regularly to ensure efficient operation. Clean the
filter as recommended in the care instructions.
Care And Cleaning
Regularly clean the water tank, filter, and exterior surfaces of
the dehumidifier to maintain optimal performance. Refer to the care
section of the manual for detailed cleaning instructions.
FAQs
-
1. **Q:** How often should I clean the filter?
A: The filter should be cleaned every two weeks
under normal operating conditions. If used in a dusty environment,
more frequent cleaning may be required.
-
1. **Q:** What should I do if the dehumidifier stops
working?
A: Check the power source, ensure the water
tank is properly seated, and that the filter is clean. If issues
persist, refer to the troubleshooting section of the manual or
contact customer support.
“`
use care Dehumidifier &
Introduction ……………………………………………..2 Important Safety Instructions ……………….3
Location…………………………………………………… 11 How It Works………………………………………….. 11 Dehumidifier
Features………………………….. 12 Operating Instructions …………………………. 12
Frigidaire.com USA 1-800-944-9044
Care And Cleaning ……………………………….. 16 Storage …………………………………………………… 17 Normal
Sounds ……………………………………… 17 Before You Call……………………………………… 18 Major Appliance
Limited Warranty……. 19
Model: FFAD2234W1 FFAD3534W1
Frigidaire.ca Canada 1-800-265-8352
2
INTRODUCTION
family Welcome to our
Thank you for bringing Frigidaire® into your home! We see your purchase as the
beginning of a long relationship together.
This manual is your resource for the use and care of your product. Please read
it before using your appliance. Keep it handy for quick reference. If
something doesn’t seem right, the troubleshooting section will help you with
common issues.
FAQs, helpful tips and videos, cleaning products, and kitchen and home
accessories are available at www.frigidaire.com.
We are here for you! Visit our website, chat with an agent, or call us if you
need help. We may be able to help you avoid a service visit. If you do need
service, we can get that started for you.
Let’s make it official! Be sure to register your product.
Keep your product info here so it’s easy to find.
Model Number
Serial Number
Purchase Date
IMPORTANT SAFETY INSTRUCTIONS
3
WARNING
For Your Safety · Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
Read product labels for flammability and other warnings. · Discard water from
bucket. Water is not potable and cannot be used for drinking.
WARNING
· Do not leave children unattended in an area where the appliance is
operating. Do not allow them to sit or stand on the appliance.
· This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
· Children should be supervised to ensure that they do not play with the
appliance.
Electrical Information · For your safety and protection, this
dehumidifier is equipped with a three-prong grounding plug on the power cord.
Do not, under any circumstances, cut or remove the round ground prong from the
plug. · Your dehumidifier must be plugged directly into a properly grounded
and polarized three-prong receptacle. lf the wall receptacle you intend to use
will not accept a three-prong plug, or if you are not sure the outlet is
adequately grounded or protected by a time delay fuse or circuit breaker, have
a qualified electrician install the proper outlet according to the National
Electrical Code and applicable local codes and ordinances. Do not use an
extension cord or an adapter plug. · Never unplug the dehumidifier by pulling
on the power cord. Always grip the plug firmly and pull straight out from the
receptacle. · Do not pinch, bend, or knot the power cord.
WARNING
Child Safety Precautions
· Destroy the carton, plastic bags, and any packing materials immediately
after the dehumidifier is unpacked. Children should never use these items for
play.
SAFETY PRECAUTIONS
DANGER! Avoid Serious Injury or Death
· This dehumidifier contains no user-serviceable parts. Always call an
authorized Electrolux servicer for repairs.
· Do not insert or place fingers or objects into the air discharge area or
back grille of the unit.
· Do not start or stop the dehumidifier by unplugging the power cord or
turning off the power at the electrical box.
· Do not cut or damage the power cord. Do not pull on the power cord.
· If the power cord is damaged, it should only be replaced by an authorized
Electrolux servicer.
· In the event of a malfunction (sparks, burning smell, etc.), immediately
stop the operation, disconnect the power cord, and call an authorized
Electrolux servicer.
· Do not operate the dehumidifier with wet hands. Do not drink any water from
the dehumidifier.
· If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
· The appliance shall be installed in accordance with national wiring
regulations.
4
IMPORTANT SAFETY INSTRUCTIONS
SAFETY PRECAUTIONS
WARNING
CAUTION! Avoid Injury or damage to the unit or other property · Do not direct
airflow at fireplaces or other
heat related sources as this could cause flare ups. · Do not climb on or place
objects on the unit. Do not hang objects off the unit. · Do not place
containers with liquids on the unit. · Turn off the dehumidifier at the power
source when it will not be used for an extended period of time. · Operate the
unit with air filter in place. · Do not block or cover the intake grille,
discharge area and outlet ports. · Ensure that any electrical/electronic
equipment is one yard away from the unit. · Do not use or store flammable
gases near the unit.
WARNING
Avoid fire hazard or electric shock. Do not use an extension cord or an
adaptor plug. Do not remove any prong from the power cord.
Grounding type wall receptacle
Do not, under any circumstances, cut, remove, or bypass the grounding prong.
Power supply cord with 3-prong grounding plug
FOR FLAMMABLE REFRIGERANT · Servicing shall only be performed as
recommended by the equipment manufacturer. Maintenance and repair requiring
the assistance of other skilled personnel shall be carried out under the
supervision of the person competent in the use of flammable refrigerants. · DO
NOT modify the length of the power cord or use an extension cord to power the
unit. · DO NOT share a single outlet with other electrical appliances.
Improper power supply can cause fire or electrical shock. · Please follow the
instruction carefully to handle, install, clear, service the air conditioner
to avoid any damage or hazard. · Flammable Refrigerant R32 is used within air
conditioner. When maintaining or disposing the air conditioner, the
refrigerant (R32) shall be recovered properly, shall not discharge to air
directly. · Compliance with national gas regulations shall be observed. · Keep
ventilation openings clear of obstruction. · The appliance shall be stored so
as to prevent mechanical damage from occurring. · A warning that the appliance
shall be stored in a well-ventilated area where the room size corresponds to
the room area as specified for operation. · Any person who is involved with
working on or breaking into a refrigerant circuit should hold a current valid
certificate from an industry-accredited assessment authority, which authorises
their competence to handle refrigerants safely in accordance with an industry
recognised assessment specification.
Examples for such working procedures are: · breaking into the refrigerating
circuit; · opening of sealed components; · opening of ventilated enclosures.
IMPORTANT SAFETY INSTRUCTIONS
5
· No any open fire or device like switch which may generate spark/arcing shall
be around air conditioner to avoid causing ignition of the flammable
refrigerant used. Please follow the instruction carefully to store or maintain
the air conditioner to prevent mechanical damage from occurring.
· Do not use means to accelerate the defrosting process or to clean, other
than those recommended by the manufacturer.
· The appliance shall be stored in a room without continuously operating
ignition sources (for example: open flames, an operating gas appliance) and
ignition sources or (for example: an operating electric heater) close to the
appliance.
· Do not pierce or burn. · Be aware that the refrigerants may not
contain an odour.
1. Transport of equipment containing flammable refrigerants.
See transport regulations.
2. Marking of equipment using signs
See local regulations.
3. Disposal of equipment using flammable refrigerants
See national regulations.
4. Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer’s
instructions.
5. Storage of packed (unsold) equipment
Storage package protection should be constructed such that mechanical damage
to the equipment inside the package will not cause a leak of the refrigerant
charge. The maximum number of pieces of equipment permitted to be stored
together will be determined by local regulations.
6. Information on servicing
a)Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimised. For
repair to the refrigerating system, the following precautions shall be
complied with prior
to conducting work on the system.
b)Work procedure
Work shall be undertaken under a
controlled procedure so as to minimise
the risk of a flammable gas or vapour
being present while the work is being
performed.
c) General work area
All maintenance staff and others working
in the local area shall be instructed on
the nature of work being carried out.
Work in confined spaces shall be
avoided. The area around the workspace
shall be sectioned off. Ensure that the
conditions within the area have been
made safe by control of flammable
material.
d)Checking for presence of refrigerant
The area shall be checked with an
appropriate refrigerating detector prior
to and during work, to ensure the
technician is aware of potentially
flammable atmospheres. Ensure that the
leak detection equipment being used is
suitable for use with flammable
refrigerants,
i.e.
non-sparking,
adequately sealed or intrinsically safe.
e) Presence of fire extinguisher
If any hot work is to be conducted on the
refrigeration equipment or any
associated parts, appropriate fire
extinguishing equipment shall be
available to hand. Have a dry powder or
CO2 fire extinguisher adjacent to the
charging area.
f) No ignition sources
No person carrying out work in relation
to a refrigerating system which involves
exposing any pipe work that contains or
has contained flammable refrigerant
shall use any sources of ignition in such a
manner that it may lead to the risk of fire
or explosion. All possible ignition
sources, including cigarette smoking,
should be kept sufficiently far away from
the site of installation, repairing,
removing and disposal, during which
flammable refrigerant can possibly be
released to the surrounding space. Prior
to work taking place, the area around the
6
IMPORTANT SAFETY INSTRUCTIONS
equipment is to be surveyed to make sure that there are no flammable hazards
or ignition risks. No Smoking signs shall be displayed.
g)Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work. A degree of ventilation
shall continue during the period that the work is carried out. The ventilation
should safely disperse any released refrigerant and preferably expel it
externally into the atmosphere.
h) Checks to the refrigerating equipment
Where electrical components are being changed, they shall be fit for the
purpose and to the correct specification. At all times the manufacturer’s
maintenance and service guidelines shall be followed. If in doubt consult the
manufacturer’s technical department for assistance. The following checks shall
be applied to installations using flammable refrigerants: The actual
refrigerant charge is in accordance with the room size within which the
refrigerant containing parts are installed; The ventilation machinery and
outlets are operating adequately and are not obstructed; If an indirect
refrigerating circuit is being used, the secondary circuit shall be checked
for the presence of refrigerant; Marking to the equipment continues to be
visible and legible. Markings and signs that are illegible shall be corrected;
Refrigerating pipe or components are installed in a position where they are
unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
i) Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures. If a fault exists that could
compromise safety, then no electrical
supply shall be connected to the circuit until it is satisfactorily dealt
with. If the fault cannot be corrected immediately but it is necessary to
continue operation, an adequate temporary solution shall be used. This shall
be reported to the owner of the equipment so all parties are advised. Initial
safety checks shall include: That capacitors are discharged: this shall be
done in a safe manner to avoid possibility of sparking; That there no live
electrical components and wiring are exposed while charging, recovering or
purging the system; That there is continuity of earth bonding.
7. Repairs to sealed components
a) During repairs to sealed components, all electrical supplies shall be
disconnected from the equipment being worked upon prior to any removal of
sealed covers, etc. If it is absolutely necessary to have an electrical supply
to equipment during servicing, then a permanently operating form of leak
detection shall be located at the most critical point to warn of a potentially
hazardous situation.
b)Particular attention shall be paid to the following to ensure that by
working on electrical components, the casing is not altered in such a way that
the level of protection is affected. This shall include damage to cables,
excessive number of connections, terminals not made to original specification,
damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is
mounted securely.
Ensure that seals or sealing materials have not degraded such that they no
longer serve the purpose of preventing the ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer’s
specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types
of leak detection equipment. Intrinsically safe components do not have to be
isolated prior to working on them.
8. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit
without
IMPORTANT SAFETY INSTRUCTIONS
7
ensuring that this will not exceed the
permissible voltage and current
permitted for the equipment in use.
Intrinsically safe components are the only
types that can be worked on while live in
the presence of a flammable atmosphere.
The test apparatus shall be at the correct
rating. Replace components only with
parts specified by the manufacturer.
Other parts may result in the ignition of
refrigerant in the atmosphere from a leak.
9. Cabling
Check that cabling will not be subject to
wear, corrosion, excessive pressure,
vibration, sharp edges or any other
adverse environmental effects. The check
shall also take into account the effects of
aging or continual vibration from sources
such as compressors or fans.
10.Detection of flammable refrigerants
Under no circumstances shall potential
sources of ignition be used in the
searching for or detection of refrigerant
leaks. A halide torch (or any other
detector using a naked flame) shall not be
used.
The following leak detection methods are
deemed acceptable for systems
containing flammable refrigerants.
Electronic leak detectors shall be used to
detect flammable refrigerants, but the
sensitivity may not be adequate, or may
need
re-calibration.
(Detection
equipment shall be calibrated in a
refrigerant-free area). Ensure that the
detector is not a potential source of
ignition and is suitable for the refrigerant
used. Leak detection equipment shall be
set at a percentage of the LFL of the
refrigerant and shall be calibrated to the
refrigerant employed and the appropriate
percentage of gas (25 % maximum) is
confirmed. Leak detection fluids are
suitable for use with most refrigerants but
the use of detergents containing chlorine
shall be avoided as the chlorine may react
with the refrigerant and corrode the
copper pipe-work. If a leak is suspected,
all naked flames shall be removed/extinguished. If a leakage of
refrigerant is found which requires
brazing, all of the refrigerant shall be recovered from the system, or
isolated (by means of shut off valves) in a part of the system remote from the
leak. Removal of refrigerant shall be according to Removal and evacuation.
11. Removal and evacuation
When breaking into the refrigerant circuit to make repairs or for any other
purposeconventional procedures shall be used. However, for flammable
refrigerants it is important that best practice be followed, since
flammability is a consideration. The following procedure shall be adhered to:
a) safely remove refrigerant following local and national regulations;
b)purge the circuit with inert gas; c) evacuate (optional for A2L); d)purge
with inert gas (optional for A2L);
e) open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders
if venting is not allowed by local and national codes. For appliances
containing flammable refrigerants, the system shall be purged with oxygen-free
nitrogen to render the appliance safe for flammable refrigerants. This process
might need to be repeated several times. Compressed air or oxygen shall not be
used for purging refrigerant systems. For appliances containing flammable
refrigerants, refrigerants purging shall be achieved by breaking the vacuum in
the system with oxygen-free nitrogen and continuing to fill until the working
pressure is achieved, then venting to atmosphere, and finally pulling down to
a vacuum (optional for A2L). This process shall be repeated until no
refrigerant is within the system (optional for A2L). When the final oxygen-
free nitrogen charge is used, the system shall be vented down to atmospheric
pressure to enable work to take place. Ensure that the outlet for the vacuum
pump is not close to any potential ignition sources and that ventilation is
available.
8
IMPORTANT SAFETY INSTRUCTIONS
12.Charging procedures
In addition to conventional charging procedures, the following requirements
shall be followed. Ensure that contamination of different refrigerants does
not occur when using charging equipment. Hoses or lines shall be as short as
possible to minimise the amount of refrigerant contained in them. Cylinders
shall be kept in an appropriate position according to the instructions. Ensure
that the refrigeration system is earthed prior to charging the system with
refrigerant. Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system. Prior to
recharging the system it shall be pressure tested with OFN. The system shall
be leak tested on completion of charging but prior to commissioning. A follow
up leak test shall be carried out prior to leaving the site.
13. Decommissioning
Before carrying out this procedure, it is essential that the technician is
completely familiar with the equipment and all its detail. It is recommended
good practice that all refrigerants are recovered safely. Prior to the task
being carried out, an oil and refrigerant sample shall be taken in case
analysis is required prior to re-use of reclaimed refrigerant. It is essential
that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b)Isolate system electrically.
c) Before attempting the procedure ensure that: Mechanical handling equipment
is available, if required, for handling refrigerant cylinders; All personal
protective equipment is available and being used correctly; The recovery
process is supervised at all times by a competent person; Recovery equipment
and cylinders conform to the appropriate standards.
d)Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes
place.
g)Start the recovery machine and operate in accordance with instructions.
h) Do not overfill cylinders. (No more than 80% volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even
temporarily.
j) When the cylinders have been filled correctly and the process completed,
make sure that the cylinders and the equipment are removed from site promptly
and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration
system unless it has been cleaned and checked.
14. Labelling
Equipment shall be labelled stating that it has been de-commissioned and
emptied of refrigerant. The label shall be dated and signed. Ensure that there
are labels on the equipment stating the equipment contains flammable
refrigerant.
15. Recovery
When removing refrigerant from a system, either for servicing or
decommissioning, it is recommended good practice that all refrigerants are
removed safely. When transferring refrigerant into cylinders, ensure that only
appropriate refrigerant recovery cylinders are employed. Ensure that the
correct number of cylinders for holding the total system charge is available.
All cylinders to be used are designated for the recovered refrigerant and
labelled for that refrigerant (i.e. special cylinders for the recovery of
refrigerant). Cylinders shall be complete with pressure relief valve and
associated shut-off valves in good working order. Empty recovery cylinders are
evacuated and, if possible, cooled before recovery occurs.
IMPORTANT SAFETY INSTRUCTIONS
9
The recovery equipment shall be in good working order with a set of
instructions concerning the equipment that is at hand and shall be suitable
for the recovery of flammable refrigerants. In addition, a set of calibrated
weighing scales shall be available and in good working order. Hoses shall be
complete with leak-free disconnect couplings and in good condition. Before
using the recovery machine, check that it is in satisfactory working order,
has been properly maintained and that any associated electrical components are
sealed to prevent ignition in the event of a refrigerant release. Consult
manufacturer if in doubt. The recovered refrigerant shall be returned to the
refrigerant supplier in the correct recovery cylinder, and the relevant Waste
Transfer Note arranged.
Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to
be removed, ensure that they have been
evacuated to an acceptable level to make
certain that flammable refrigerant does
not remain within the lubricant. The
evacuation process shall be carried out
prior to returning the compressor to the
suppliers. Only electric heating to the
compressor body shall be employed to
accelerate this process. When oil is
drained from a system, it shall be carried
out safely.
Non-duct
connected
appliances
containing A2L refrigerants with the
supply and return air openings in the
conditioned space may have the body of
the appliance may be installed in open
areas such as false ceilings not being used
as return air plenums, as long as the
conditioned air does not directly
communicate with the air of the false
ceiling.
CAUTION: Risk of fire flammable materials
IMPORTANT NOTE: Read this manual carefully before installing or operating your
new air conditioning unit. Make sure to save this manual for future reference.
CAUTION
This symbol shows that the operation manual should be read carefully.
CAUTION
This symbol shows that information is available such as the operating manual or installation manual.
CAUTION
This symbol shows that a service personnel should be handling this equipment with reference to the installation manual.
10 IMPORTANT SAFETY INSTRUCTIONS
Wiring Diagram
16020100001654 Notes: Display and Fan’s conntors must be match the actual indicates.
Notes: This symbol indicates the element is optional,
FAN CAPACITOR
BLUE
BROWN Y/G
PUMP
RED
BLACK(or BLUE)
OPTIONAL
CN2
CN1
DC POWER
BOARD
FAN
TOP M STEP
TOUCH/LIGHT PANEL
WIFI
CN5 DISPLAY BOARD
CN11 CN10
(or CN13)
CN12
WATER PIPE HUMI. SWITCHTEMP. SENSOR
WIFI
SWITCH SWITCH
RED BLACK(or BLUE)
WHITE
the actual
shape shall
prevail
BLUE
Y/G ION
RED
BLACK
COMP.
BLUE BLACK
~ M M
SC
Y/G
COMP.
OverLoad
CAPACITOR
Protector
WHITE(OR BLUE OR BLACK)(N)
P4 P9 P6
P10
CN4 CN3 CN2 CN1 CN10 CN7 CN6B
MAIN BOARD CN5
(or CN6/CN6A/CN6B/CN6C/CN10)
P7 P2 P1 CN14
P8
13
CN15 12
Y/G(or GREEN)
POWER
RED
BLACK(OR BROWN OR RED)(L)
3 POWER 1 1 BOARD 2
CN1 CN2
11 LOCATION & HOW IT WORKS
Location
How It Works
Selecting a Location
IMPORTANT:
1. Dehumidifier must be operated in an enclosed area to be most effective.
Close all doors, windows, and other outside openings to the room. The
effectiveness of the dehumidifier depends on the rate at which new moisture-
laden air enters the room.
2. Place dehumidifier in a location that does not restrict the airflow of the
air intake and air outlet.
3. A dehumidifier operating in a basement will have little or no effect in
drying an adjacent enclosed storage area, such as a closet, unless there is
adequate circulation of air in and out of the area. lt may be necessary to
install a second dehumidifier in the enclosed area for satisfactory drying.
4. The dehumidifier must be installed on a level floor that will support it
with a full bucket of water.
5. There should be a minimum of 12 inches clearance around the dehumidifier.
The unit will produce heat while in operation and should not be operated in an
enclosed small space like a closet.
When the unit is started, the fan begins to pull moisture-laden air across the
dehumidifying coils. The coils condense or draw moisture from the air, and air
flows through the air outlet louvers into the room as dry, warm air. Moisture
removed from air is collected in a bucket on the front of the dehumidifier.
The unit is designed to operate between 41°F (5°C), and 89°F (32°C) and
between 30%(RH) and 80%(RH). The unit will not work properly if the
temperature is out of this temperature range, or the performance of the unit
will fall greatly.
The “Compressor” circuit has an automatic 3 minute time delayed start if the
unit is turned off and on quickly. This prevents overheating of the compressor
and possible circuit breaker tripping. Make sure the tank is fitted correctly
otherwise unit will not turn on.
Do not Block at least 24″
12″ 12″
12 DEHUMIDIFIER FEATURES & OPERATING INSTRUCTIONS
Dehumidifier Features
ELECTRONIC CONTROL Before you begin, thoroughly familiarize yourself with the control panel and all its functions (as shown below).
B
C
A
G
A Check Filter Reset Button B Bucket Full Indicator C Displays Humidity D Turns Unit On Or Off
F
E
D
E Sets Fan Speed F Adjusts Humidity G Sets Timer
Operating Instructions
Allow the unit to reach room temperature before operating. To begin operating
the dehumidifier, follow these steps:
NOTE
Unit must be upright for one hour prior to operating.
1. Plug the power cord into a properly grounded 115 volt AC outlet.
NOTE
2. To turn the unit on, press the ON/OFF button. The unit will run in the factory setting of CONTINUOUS and high fan speed. In the CONTINUOUS mode, the unit will only display CO and not the room humidity. It is recommended you leave the unit running in the CONTINUOUS setting for the first three or four days until the sweating and dampness odors have stopped.
If the “BUCKET FULL” light is on, remove the bucket and re-install to reset the float switch.
13 OPERATING INSTRUCTIONS
3. After a few days when the Relative Humidity has declined, press the
HUMIDITY ( ) or ( ) buttons to choose a value between 35% to 85%, so the room
is kept at a comfortable humidity. Pressing the ( ) or ( ) buttons will change
the humidity selection in 5% increments. 5 seconds after you have set the
desired humidity, the readout will display the actual room humidity. If at any
time you want to return to the CONTINUOUS Mode, pressing the HUMIDITY ( )
button will lower the Relative Humidity through 5% decrements until the
display reads CO.
4. You can also use the FAN SPEED button to change the fan speed to Hi, Med
or Lo. The indicator light will show the setting you have selected. A higher
fan speed will result in quicker moisture removal.
6. The TIMER function enables you to either Delay Start or Delay Stop the unit in the choice from 0.5 hour to 24 hours. If the unit is running, then selecting Timer will turn the unit off in the hours that will be set (Delay Stop). If the unit is off, then selecting Timer will turn the unit on in the hours that will be set (Delay Start). TIMER setting: First press TIMER button, then adjust timer setting, by tapping or holding the ( ) or ( ) button to change the delay timer at 0.5 hour increments, up to 10 hours, then by 1 hour increments up to 24 hours. The control will count down the time remaining (8h, 7.5h, 7h etc.) until the unit either starts or stops. For the Delay Start, the fan speed and humidity maintained will be the same as previous setting. After TIMER setting finishes, pressing TIMER button again at any time will stop the TIMER function. The Delay Start/Stop Feature will work until the unit either starts or stops. Once that happens the above steps have to be repeated.
5. The Filter reset light will illuminate after 250 hours of operation. At this time refer to the care and cleaning section to remove and clean the filter. Once the filter has been cleaned and replaced, simply press the Filter reset button to extinguish the light.
NOTE
1. Before entering TIMER setting, make sure power is being supplied to the
unit.
2. Before entering TIMER setting, make sure pressing HUMIDITY ( ) or ( )
button sets one desired room humidity first.
7. To shut the unit down, press the ON/OFF button.
Note: After a power outage, the unit will memorize the last setting and return the unit to the same setting once power is restored.
14 OPERATING INSTRUCTIONS
Fault Codes
1. If the display reads “AS” or “ES” , a sensor has failed. Contact your
Authorized Frigidaire® Service Center.
b. Do not move the unit at this time otherwise water may spill on the floor.
c. Press sides of bucket gently to unclip the bucket from the unit.
d. Remove the bucket as shown in the photographs below and empty the bucket.
2. If the display reads “EC” , check the following operating conditions. Outlet voltage should be 115V±10% and the surrounding temperature should be with in the range of 41 °F to 89 °F. Unplug the unit and plug it in again under normal operating conditions. If the “EC” code persists, contact your Authorized Frigidaire® Service Center.
3. If the display reads “E4″, the communication between display PCB and main control PCB is faulty. Contact your Authorized Frigidaire® Service Center.
Removing Collected Water
1. Emptying the Bucket: a. When the bucket is full, the unit will shut
down and the BUCKET FULL indicator will illuminate.
15 OPERATING INSTRUCTIONS
WARNING
Discard water from bucket. Water is not potable and cannot be used for
drinking.
e. Replace the empty bucket back into the unit and once seated correctly, the
unit will start up again.
f. You should hear a click when the bucket is in the correct position.
If the bucket full light does not extinguish, check that the float is
correctly snapped in place.
fig. 1
c. Insert the female threaded end of the hose onto the drain connector of the
unit. (fig.2)
2. Continuous Drainage:
a. For continuous drainage operation, you will need a garden hose and a drain
nearby to discharge the water into.
b. Unscrew the drain cap on the back side of the unit. (fig.1)
fig. 2
d. Screw the garden hose onto the threaded portion of the drain connector.
(fig.3)
16 OPERATING INSTRUCTIONS & CARE AND CLEANING
NOTE
1. Check the seal between the hose and the drain connector. If there is a
small leak then replace the hose gasket and re-tighten the hose.
2. It is recommended that a Dehumidifier Drain Hose – 1/2” (12.7 mm) or
larger be used. Make sure there are no kinks or elevations in the hose.
3. When a hose is not attached to the drain connector, please ensure drain
cap is screwed securely to the connector to prevent leakages.
fig. 3
e. Make sure the hose is secure so there are no leaks.
f. Direct the hose toward the drain, making sure that there are no kinks that
will stop the water flowing.
g. Place the end of the hose into the drain. (fig.4)
Care and Cleaning
1. Filter Clean the filter every two weeks based on normal operating
conditions. To remove the filter: a. Open the back grille.
b. Detach the filter from the back of the grille by pressing the tabs as shown
below.
fig. 4
h. Select the desired humidity setting and fan speed on the unit for
continuous draining to start.
17 STORAGE & NORMAL SOUNDS
Normal Sounds
2
3
Tabs
c. Wash the filter with clean water then dry. d. Re-install the filter.
2. Cabinet a. Dust cabinet with an oil-free cloth, or using
a damp cloth. b. Vacuum grill using brush attachment. 3. Water Bucket Clean
the Water Bucket every two weeks based on normal operating conditions. a.
Clean bucket with warm water and
detergent.
Storage
When unit is not in use, unplug and use the cord wrap shown for your model
type.
1
4
1 Dripping Sound The sound of dripping water may be heard during the
dehumidification cycle.
2 Sound of Rushing Air At the top of the unit, you may hear the sound of
rushing air being moved by the fan.
3 Gurgle/Hiss “Gurgling or hissing” noise may be heard due to refrigerant
passing through evaporator during normal operation.
4 High pitched Chatter Today’s high efficiency compressors may have a high
pitched chatter during the dehumidification cycle.
18 BEFORE YOU CALL
Before calling for service, review this list. It may save you time and expense. This list includes common occurrences that are not the result of defective workmanship or materials in this appliance.
OCCURRENCE
Dehumidifier does not operate.
Dehumidifier runs too much.
Dehumidifier is operating but room is not dry enough.
Frost appears on coils behind the filter Fan noise.
SOLUTION
· Wall plug disconnected. Push plug firmly into wall outlet. · House fuse
blown or circuit breaker tripped. Replace fuse with time delay
type or reset circuit breaker. · The dryness level you selected has been
reached. Dehumidifier automatically
shuts off when selected amount of moisture has been removed from the air. If
you want to remove more moisture, Select ‘CONTINUOUS’ by using the humidity
button or knob. After the dehumidifier starts, reset the control to the
desired setting. · Bucket not installed properly. See “Removing Collected
Water”. · Water in the bucket has reached its preset level. Dehumidifier
automatically turns off when this occurs. Empty bucket and return bucket to
position. · Dehumidifier is not turned on. Turn unit on. · “BUCKET FULL” light
is on. Remove bucket, empty water and re-install correctly.
· Windows or doors near dehumidifier are open to outdoors. Close all windows
or doors to outside.
· Area to be dehumidified is too large. Check with your dealer to see if
capacity is adequate.
· Air movement through dehumidifier is blocked. Grill may be dirty. Use brush
attachment of vacuum cleaner to clean grill. See “Care and Cleaning”.
Dehumidifier must be placed in a space that does not restrict air flowing into
the rear coil or out of the front grill.
· Dehumidifier has been installed or restarted recently. The higher the
moistuire in the room, the longer the dehumidifier will operate.
· Dehumidifier is in the CONTINUOUS mode and will remain on in this mode, use
the humidity button or knob to set a RH% higher level.
· Humidity setting is too high. Press the HUMIDITY button or rotate knob to a
lower setting or choose CONTINUOUS for maximum dryness.
· Dehumidifier has been installed or restarted recently. The higher the
moisture in the room air, the longer it takes for the room air to become dry.
· Dehumidifier does not have sufficient clearance to operate. Air flow to the
air outlet is blocked. See “Selecting a Location”.
· Room temperature is too low. Unit will not operate satisfactorily if the
room temperature is below 41°F(5°C). See “Operating Conditions”.
· Refer to causes under DEHUMlDIFIER RUNS TOO MUCH.
· Dehumidifier has been turned on recently. This is normal due to refrigerant
rushing through the coil. Frost will usually disappear within 60 minutes.
· Room Temperature is too low. All models will operate satisfactorily at
temperatures greater than 41°F (5°C).
· Air is moving through the dehumidifier. This is a normal sound.
If These Solutions Fail, Call 1-800-944-9044(US)/1-800-265-8352(Canada) For Frigidaire® Service.
19 MAJOR APPLIANCE LIMITED WARRANTY
Your appliance is covered by a limited one-year warranty for functional
repairs only. For one year from your original date of purchase, Electrolux
will pay all costs for repairing or replacing any parts of this appliance that
prove to be defective in materials or workmanship when such appliance is
installed, used and maintained in accordance with the provided instructions.
After one year from your original date of purchase, the consumer will be
responsible for diagnostic, labor and parts costs as well as any removal,
transportation and reinstallation expenses which are incurred during service
on components.
Exclusions This warranty does not cover the following:
1. Products with original serial numbers that have been removed, altered or
cannot be readily determined. 2. Product that has been transferred from its
original owner to another party or removed outside the USA or Canada. 3. Rust
on the interior or exterior of the unit. 4. Products purchased “as-is” are not
covered by this warranty. 5. Food loss due to any refrigerator or freezer
failures. 6. Products used in a commercial setting. 7. Service calls which do
not involve malfunction or defects in materials or workmanship, or for
appliances not in ordinary household use or used other than in accordance with
the provided instructions. 8. Service calls to correct the installation of
your appliance or to instruct you how to use your appliance. 9. Expenses for
making the appliance accessible for servicing, such as removal of trim,
cupboards, shelves, etc., which are not a part of the appliance when it is
shipped from the factory. 10. Service calls to repair or replace appliance
light bulbs, air filters, water filters, other consumables, or knobs, handles,
or other cosmetic parts. 11. Surcharges including, but not limited to, any
after hour, weekend, or holiday service calls, tolls, ferry trip charges, or
mileage expense for service calls to remote areas, including the state of
Alaska. 12. Damages to the finish of appliance or home incurred during
installation, including but not limited to floors, cabinets, walls, etc. 13.
Damages caused by: services performed by unauthorized service companies; use
of parts other than genuine Electrolux parts or parts obtained from persons
other than authorized service companies; or external causes such as abuse,
misuse, inadequate power supply, accidents, fires, or acts of God.
DISCLAIMER OF IMPLIED WARRANTIES; LIMITATION OF REMEDIES
CUSTOMER’S SOLE AND EXCLUSIVE REMEDY UNDER THIS LIMITED WARRANTY SHALL BE PRODUCT REPAIR OR REPLACEMENT AS PROVIDED HEREIN. CLAIMS BASED ON IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED TO ONE YEAR OR THE SHORTEST PERIOD ALLOWED BY LAW, BUT NOT LESS THAN ONE YEAR. ELECTROLUX SHALL NOT BE LIABLE FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES SUCH AS PROPERTY DAMAGE AND INCIDENTAL EXPENSES RESULTING FROM ANY BREACH OF THIS WRITTEN LIMITED WARRANTY OR ANY IMPLIED WARRANTY. SOME STATES AND PROVINCES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, OR LIMITATIONS ON THE DURATION OF IMPLIED WARRANTIES, SO THESE LIMITATIONS OR EXCLUSIONS MAY NOT APPLY TO YOU. THIS WRITTEN WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS THAT VARY FROM STATE TO STATE.
If You Need Keep your receipt, delivery slip, or some other appropriate payment record to establish the
Service
warranty period should service be required. If service is performed, it is in your best interest to
obtain and keep all receipts. Service under this warranty must be obtained by contacting
Electrolux at the addresses or phone numbers below.
This limited warranty only applies in the USA and Canada. In the USA, your appliance is warranted by
Electrolux Major Appliances North America, a division of Electrolux Home Products, Inc. In Canada, your
appliance is warranted by Electrolux Canada Corp. Electrolux authorizes no person to change or add to any
obligations under this warranty. Obligations for service and parts under this warranty must be performed by
Electrolux or an authorized service company. Product features or specifications as described or illustrated are
subject to change without notice.
USA 1.800.944.9044 Electrolux Major Appliances 10200 David Taylor Drive Charlotte, NC 28262
Canada
1.800.265.8352
Electrolux Canada Corp. 5855 Terry Fox Way
Mississauga, Ontario, Canada L5V 3E4
home welcome
Our home is your home. Visit us if you need help with any of these things:
owner support
accessories
service
registration
(See your registration card for more information.)
Frigidaire.com 1-800-944-9044
Frigidaire.ca 1-800-265-8352
16120300A28953 (July 2019)
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>