Installation Manual
Type EB3L-N Relay Barrier (alias Lamp Barrier)
For Intrinsically Safe System II(1)G [Ex ia Ga]IIC, II(1)D [Ex ia
Da]IIIC
Draw. No. B-2272-3 (0)
Rev.H
Oct.4, 2022
ATEX Certificate No. DEKRA 21ATEX0103
UKCA Certificate No. CSAE 22UKEX1312
When installing an IDEC Type EB3L-N Relay Barrier (thereafter, called Barrier), make sure it conforms to the following drawings and descriptions as well as all applicable requirements.
EN IEC 60079-0:2018, EN 60079-11:2012, EN 60079-25:2010, EN 60079-14:2014
All intrinsically safe systems must have “EB3L-N” in the part number. Barrier
must be located in a safe area (non-hazardous area).
The intrinsically safe apparatus, such as the Contact certificated, approved
or considered to be a “simple apparatus” such as the Switch specified by
standard, may be located in the hazardous area.
- Servicing – Replacement and Repairs: Inspection and replacement of Barrier shall not be made until power is disconnected and shall not be connected again until all replacement Barrier are properly re-assembled. All electrical components, including the interconnecting wiring, shall be kept in safe condition. Defective Barrier should be returned to the factory for repair.
Warning ! Substitution of components or unauthorized repair may impair
intrinsic safety of apparatus.
To maintain intrinsic safety, the Signal output terminal (Pn-Nn) may only be
connected to intrinsically safe circuits where both the wiring and the
connected equipment maintain 500 V isolation to the hazardous area
earthing/bonding connections.
- Mounting: All bolts, nuts, screws, and other means of fastening, including the unused wiring screws, shall be fastened in place, properly tightened and secured. Mount Barrier on a 35mm track or directly mount on a panel surface using screws.
- Certified Barrier: Type EB3L-abcdeN “EB3L-…N”= Series type
a = Output S: for Supper LED b = channels 01, 02, 03, 05,
06, 08, 08C, 10, 16C ( C: common wiring only)
c = Signal type K: Sink, S: Source d = Power supply A:
100~240Vac, D: 24Vdc e = connection Blank: Terminal, -C:
Connector
- Rating and Parameters of I.S.
Ta= 60°C, Um= 250V, Uo=13.2V, Io= 14.2mA, Po= 46.9mW at each channel Pn-Nn, Io=227.2mA, Po= 750mW at max 16 channels Pn-Nn
-
Typical Installation: Install Barrier must be according to the above Ratings and Parameters of I.S. and descriptions.
To avoid electrical shock, install Barrier in a tool-accessible enclosure. Layout and wiring must be done to prevent the inductive or capacitive induction to the intrinsically safe circuit. For example, separate intrinsically safe circuits from non-intrinsically safe circuits, by a minimum space of 50mm or using a full height metal separator. If color-coding is required use for the intrinsic safe components and terminals, use only cables and terminals with light blue markings. Interconnection between the Barriers to setting Common Wiring: connect two independent wires in parallel at each two ” N ” terminals between adjacent the Barrier inside the panel. Maintain at least 3 mm clearance between the external connection terminals and the grounded metal part. -
Dielectric Strength: Between intrinsically safe circuit and non-intrinsically safe circuit 1526.4V AC.
Example of connections: The marks indicate the samples of single intrinsic safe circuits, and marks indicate IS apparatus.
Common Wiring (e.g. Io=227.2mA with 16 channels)
Separate Wiring (e.g. Io=14.2mA with 1 channel)
- Operating rating
Power input | EB3L-…A. | Terminal L -N | 100 ~ 240V AC |
---|---|---|---|
EB3L-…D. | Terminal + — | 24V DC | |
Signal | output | EB3L-S… | Terminal Pn -Nn |
input | EB3L-..S. | Terminal / Connector |
Sn,-Cn
| 24V DC, 10mA (source)
EB3L-..K.| 24V DC, 10mA (sink)
- Lot No.
a : Production base
b, c : Year (example : 22 → 2022)
d : Month
e, f : Date
g : Number of product
IDEC CORPORATION
Manufacturer: IDEC CORPORATION 2-6-64, Nishimiyahara, Yodogawa-ku,
Osaka532-0004, Japan
EU Authorized Representative : APEM SAS
55, Avenue Edouard Herriot BP1, 82303 Caussde Cedex, France
EU DECLARATION OF CONFORMITY
We, IDEC CORPORATION 2-6-64, Nishimiyahara, Yodogawa-ku, Osaka532-0004, Japan
declare under our sole responsibility that the product:/Description : Lamp
Barrier / Model No : EB3L-N to which this declaration relates is in conformity
with the EC Directive on the following standard(s) or other normative
document(s). In case of alteration of the product, not agreed upon by us, this
declaration will lose its validity.
Applicable EC Directive : ATEX Directive ( 2014 / 34 / EU ) / EMC Directive (
2014 / 30 / EU )
/RoHS Directive(2011/65/EU and (EU) 2015 / 863)
Applicable Standard(s) : EN60079-0, EN60079-11 ( ATEX ) / EN60947-5-1 ( EMC )
/EN IEC 63000(RoHS)
UK Authorized Representative : APEM COMPONENTS LIMITED
Drakes Drive, Long Crendon, Buckinghamshire, HP18 9BA, UK
UKCA DECLARATION OF CONFORMITY
declare under our sole responsibility that the product:/Description : Lamp
Barrier / Model No : EB3L-N to which this declaration relates is in conformity
with on the following standard(s)
or other normative document(s). In case of alteration of the product, not
agreed upon by us, this declaration will lose its validity.
Applicable Standard(s) : EN60079-0, EN60079-11 ( S.I. 2016 No.1107 )
/ EN60947-5-1 ( S.I. 2016 No. 1091)/ EN IEC 63000 (S.I. 2016 No.3303))