IDEC EB3C-01N Relay Barrier Installation Guide

June 2, 2024
IDEC

IDEC EB3C-01N Relay Barrier

Product Specifications

  • Product Name: Type EB3C-N Relay Barrier
  • ATEX Certificate No.: DEKRA 21ATEX0103
  • UKCA Certificate No.: CSAE 22UKEX1312
  • Certified for: Intrinsically Safe System II(1)G [Ex ia Ga]IIC,II(1)D [Ex ia Da]IIIC
  • Standards: EN IEC 60079-0:2018, EN 60079-11:2012, EN 60079-25:2010, EN 60079-14:2014
  • Power Supply: A: 100~240Vac, D: 24Vdc
  • Connection: Blank: Terminal, -C: Connector
  • Temperature Rating (Ta): 60°C
  • Max Voltage (Um): 250V

Product Usage Instructions

Installation
When installing the EB3C-N Relay Barrier, ensure it conforms to the provided drawings and descriptions as well as all relevant requirements.

Location
The Barrier must be placed in a safe area (non-hazardous area). Intrinsically safe apparatus can be located in the hazardous area.

Maintenance
Defective Barriers should be returned to the factory for repair. Avoid unauthorized repairs or component substitutions.

Connection
The Signal input terminal (Pn-Nn) should only be connected to intrinsically safe circuits with proper isolation to the hazardous area.

Mounting
Mount the Barrier on a 35mm track or directly on a panel surface using screws. Ensure all fastening means are properly tightened and secured.

Certification Information
Certified Barrier types are classified based on output, channels, signal type, power supply, and connection type.

Type EB3C-N Relay Barrier
For Intrinsically Safe System II(1)G [Ex ia Ga]IIC, II(1)D [Ex ia Da]IIIC

INTRODUCTION

When installing an IDEC Type EB3C-N Relay Barrier (thereafter, called Barrier), make sure it conforms to the following drawings and descriptions as well as all applicable requirements.
EN IEC 60079-0:2018, EN 60079-11:2012, EN 60079-25:2010, EN 60079-14:2014
All intrinsically safe systems must have “EB3C-N” in the part number. Barrier must be located in a safe area (non-hazardous area).
The intrinsically safe apparatus, such as the Contact certificated, approved or considered to be a “simple apparatus” such as the Switch specified by standard, may be located in the hazardous area.

  • Servicing – Replacement and Repairs: Inspection and replacement of Barrier shall not be made until power is disconnected and shall not be connected again until all replacement Barrier are properly re-assembled. All electrical components, including the interconnecting wiring, shall be kept in safe condition. Defective Barrier should be returned to the factory for repair.

Warning ! Substitution of components or unauthorized repair may impair intrinsic safety of apparatus.
To maintain intrinsic safety, the Signal input terminal (Pn-Nn) may only be connected to intrinsically safe circuits where both the wiring and the connected equipment maintain 500 V isolation to the hazardous area earthing/bonding connections.

Mounting: All bolts, nuts, screws, and other means of fastening, including the unused wiring screws, shall be fastened in place,properly tightened and secured. Mount Barrier on a 35mm track or directly mount on a panel surface using screws.

Certified Barrier: Type EB3C-abcdeN “EB3C-…N”= Series type

a = Output R: Relay, T: Transistor b = channels 01, 02, 03, 05, 06, 08, 08C, 10, 16C(C: common wiring only)
c = Signal type K: Sink, S: Source (for 08C, 16C) d = Power supply A: 100~240Vac, D: 24Vdc e = connection Blank: Terminal, -C: Connector

Rating and Parameters of I.S

Ta= 60C, Um= 250V, Uo=13.2V, Io= 14.2mA, Po= 46.9mW at each channel Pn-Nn, Io=227.2mA, Po= 750mW at max 16 channels Pn-Nn

IDEC-EB3C-01N-Relay-Barrier-1

Typical Installation

Install Barrier must be according to the above Ratings and Parameters of I.S. and descriptions.

To avoid electrical shock, install Barrier in a tool-accessible enclosure. Layout and wiring must be done to prevent the inductive or capacitive induction to the intrinsically safe circuit. For example, separate intrinsically safe circuits from non-intrinsically safe circuits, by a minimum space of 50mm or using a full height metal separator. If color-coding is required use for the intrinsic safe components and terminals, use only cables and terminals with light blue markings. Interconnection between the Barriers to setting Common Wiring: connect two independent wires in parallel at each two “ N “ terminals between adjacent the Barrier inside the panel. Maintain at least 3 mm clearance between the external connection terminals and the grounded metal part.

Dielectric Strength: Between intrinsically safe circuit and non- intrinsically safe circuit 1526.4V AC.

Example of connections: The marks indicate the samples of single intrinsic safe circuits, and marks indicate IS apparatus.

Common Wiring (e.g. Io=227.2mA with 16 channels)

IDEC-EB3C-01N-Relay-Barrier-3

Separate Wiring (e.g. Io=14.2mA with 1 channel)

IDEC-EB3C-01N-Relay-Barrier-4

Operating rating

Power input| EB3C- …A.| Terminal

LN

| 100 ~ 240V AC
---|---|---|---
EB3C- …D.| Terminal

+

| 24V DC
Signal| input| EB3C- | Terminal

PnNn

| 12V DC, 10mA (source)
output| EB3C- R…| Terminal / Connector An ,- Cn| 250V, 3A

(but Connector 30V, 1A)

EB3C- T…| 24V DC, 100mA

Note common terminal/connector pin: 8A / 1A

Lot No.

  • a: Production base
  • b, c : Year (example: 22 → 2022)
  • d: Month
  • e, f: Date
  • g: Number of product

IDEC CORPORATION

Manufacturer: IDEC CORPORATION 2-6-64, Nishimiyahara, Yodogawa-ku, Osaka532-0004, Japan EU Authorized Representative: APEM SAS 55, Avenue Edouard Herriot BP1, 82303 Caussde Cedex, France

EU DECLARATION OF CONFORMITY
We, IDEC CORPORATION 2-6-64, Nishimiyahara, Yodogawa-ku, Osaka532-0004, Japan declare under our sole responsibility that the product:/Description: Relay Barrier / Model No: EB3C-N to which this declaration relates is in conformity with the EC Directive on the following standard(s) or other normative document(s). In case of alteration of the product, not agreed upon by us, this declaration will lose its validity.

  • Applicable EC Directive: ATEX Directive ( 2014 / 34 / EU ) / EMC Directive ( 2014 / 30 / EU )/RoHS Directive(2011/65/EU and (EU) 2015 / 863)
  • Applicable Standard(s) : EN60079-0, EN60079-11 ( ATEX ) / EN60947-5-1 ( EMC )/EN IEC 63000(RoHS)
  • UK Authorized Representative: APEM COMPONENTS LIMITED
    Drakes Drive, Long Crendon, Buckinghamshire, HP18 9BA, UK

UKCA DECLARATION OF CONFORMITY
declare under our sole responsibility that the product:/Description: Relay Barrier / Model No : EB3C-N to which this declaration relates is in conformity with on the following standard(s) or other normative document(s). In case of alteration of the product, not agreed upon by us, this declaration will lose its validity.
Applicable Standard(s) : EN60079-0, EN60079-11 ( S.I. 2016 No.1107 ) / EN60947-5-1 ( S.I. 2016 No. 1091) / EN IEC 63000 (S.I. 2016 No.3303) )

http://www.idec.com

Draw. No. B-2270-3 (0) Rev.G
Oct. 4, 2022
ATEX Certificate No. DEKRA 21ATEX0103
UKCA Certificate No. CSAE 22UKEX1312

Frequently Asked Questions (FAQ)

What should I do if I encounter a defective Barrier?

Defective Barriers should be returned to the factory for repair to ensure intrinsic safety is maintained.

Can I substitute components or perform unauthorized repairs?

No, substitution of components or unauthorized repairs may impair the intrinsic safety of the apparatus.

Where should the Barrier be located?

The Barrier must be located in a safe area (non-hazardous area) while intrinsically safe apparatus can be placed in the hazardous area.