STAUBLI PV-CZM Multi-Contact MC4 Crimp Tool Instruction Manual
- June 4, 2024
- STAUBLI
Table of Contents
STAUBLI PV-CZM Multi-Contact MC4 Crimp Tool
Safety instructions
These assembly instructions and the assembly steps and instructions described are an integral part of and prerequisite for certification by TÜV Rheinland and UL.
Installation, electrotechnical expertise
The products may be assembled and installed by electrically skilled or instructed persons duly observing all applicable safety regulations.
Caution, risk of electric shock
Work in a de-energized state
Follow the five safety rules, when working on electrical installations.
After the respective electrical installations have been identified, the
following five essential requirements shall be undertaken in the specified
order unless there are essential reasons for doing otherwise:
- disconnect completely;
- secure against re-connection;
- verify absence of operating voltage;
- carry out grounding and short-circuiting;
- provide protection against adjacent live parts
Any person engaged in this work activity shall be electrically skilled or instructed, or shall be supervised by such a person Source: EN 50110-1:2013
Protection against electric shock shall be checked in the end-use applications too.
Caution
Each time the connector is used, it should previously be inspected for
external defects. If there are any doubts as to its safety, a specialist must
be consulted.
Use only in accordance with the specification provided in the technical data
(see product catalog).
The wearing of suitable protective equipment or the performance of the
relevant work is the responsibility of the user.
Components and packaging materials are not toys; small parts can pose a
choking hazard if swallowed. Packaging material can pose a risk of
suffocation.
Proper disposal of products and packaging materials after use.
Do not disconnect under load
Disconnect Under Load: PV plug connections must not be disconnected while
under load.
During no-load operation plugging and unplugging when live is permitted (by switching off the DC/AC converter or breaking the AC circuit).
Explanation for MC4
(ill. 1)
Crimping pliers incl. locator and built-in crimping die
PV-KBT/10…,
PV-KST/10…
| PV-KBT4/8II-UR, PV-KST4/8II-UR| PV-KBT4/5…-UR,
PV-KST4/5…-UR| PV-KBT4/6…-UR,
PV-KST4/6…-UR| PV-KBT4/2,5…-UR,
PV-KST4/2,5…-UR| Typ Type
---|---|---|---|---|---
10 mm2| 8 AWG| 10 AWG| 12 AWG| 14 AWG| 10 AWG| 6 mm2| 12 AWG| 4 mm2| 14 AWG|
2.5 mm2| Leiterquerschnitt Conductor cross section
•| | | | | •| •| •| •| •| •| Offener Crimpkontact (B-Crimp) Open crimp
contacts (B-Crimp)
| •| •| •| •| | | | | | | Geschlossener Crimpkontakt (O-Crimp) Closed crimp
contacts (O-Crimp)
| | | | | | | •| •| •| •| PV-CZM-18100 32.6020-18100| Crimpzangen Crimping
pliers
| | | | | •| •| •| •| •| •| PV-CZM-19100 32.6020-19100
| •| | | | •| •| •| •| | | PV-CZM-22100 32.6020-22100
| •| •| •| •| | | | | | | PV-CZM-23100 32.6020-23100
•| | | | | | | •| •| | | PV-CZM-20100 32.6020-20100
•| | | | | •| •| | | | | PV-CZM-21100 32.6020-21100
| | | | | | | •| •| •| •| PV-ES-CZM-18100 32.6021-18100| Crimpeinsätze
Crimping dies
| | | | | •| •| •| •| •| •| PV-ES-CZM-19100 32.6021-19100
| •| | | | •| •| •| •| | | PV-ES-CZM-22100 32.6021-22100
| •| •| •| •| | | | | | | PV-ES-CZM-23100 32.6021-23100
•| | | | | | | •| •| | | PV-ES-CZM-20100 32.6021-20100
•| | | | | •| •| | | | | PV-ES-CZM-21100 32.6021-21100
•| | | | | •| •| •| •| •| •| PV-LOC 32.6040| Lokator Locator
| •| | | | •| •| •| •| | | PV-LOC-B 32.6055
| •| •| •| •| | | | | | | PV-LOC-D 32.6074
Individual parts
(ill. 2 + 3 + 4 + 5 + 6) Interchangeable crimping dies
Pos. | Leiterquerschnitt Cable cross section | geeignet für suitable for |
---|---|---|
mm2 | AWG | |
1 | 1,5 | 14 |
2 | 2,5 | |
3 | 4 | 12 |
(ill. 2)
Crimpbereich Crimping range | Typ Type | Bestell-Nr. Order No. |
---|---|---|
mm2 | AWG | |
1,5 / 2,5 / 4 | 14 / 12 | PV-ES-CZM-18100 |
Pos. | Cable cross section | suitable for |
--- | --- | --- |
mm2 | AWG | |
4 | 2,5 |
PV-KBT4/2.5…-UR
5| 4| 12| PV-KST4/6…-UR
PV-KBT4/6…-UR
6| 6| 10| PV-KST4/6…-UR
PV-KBT4/6…-UR
(ill. 3)
Crimpbereich Crimping range | Typ Type | Bestell-Nr. Order No. |
---|---|---|
mm2 | AWG | |
2,5 / 4 / 6 | 12 / 10 | PV-ES-CZM-19100 |
Pos. | Cable cross section | suitable for |
--- | --- | --- |
mm2 | ||
7 | 4 | PV-KST4/6…-UR |
PV-KBT4/6…-UR
8| 10| PV-KST4/10…-UR
PV-KBT4/10…-UR
(ill. 4)
Crimping range | Type | Order No. |
---|---|---|
mm2 | AWG |
4 / 10 PV-ES-CZM-20100
32.6021-20100
| | |
Pos.
| Leiterquerschnitt Cable cross section| geeignet für suitable for
---|---|---
| mm2|
9| 6| | PV-KST4/6…-UR
PV-KBT4/6…-UR
10| 10| | PV-KST4/10…-UR
PV-KBT4/10…-UR
| | 10|
| | 9|
| | | 5
(ill. 5)
Crimpbereich Crimping range | Typ Type | Bestell-Nr. Order No. |
---|---|---|
mm2 |
6 / 10 PV-ES-CZM-21100
32.6021-21100
Pos.| Leiterquerschnitt Cable cross section| geeignet für suitable for
---|---|---
| AWG|
11| 8| PV-KST4/8II-UR PV
KBT4/8II-UR
12| 10| PV-KST4/6…-UR
PV-KBT4/6…-UR
13| 12| PV-KST4/6…-UR
PV-KBT4/6…-UR
(ill. 6)
Crimpbereich Crimping range | Typ Type | Bestell-Nr. Order No. |
---|---|---|
AWG | ||
Pos. | Leiterquerschnitt Cable cross section | geeignet für suitable for |
--- | --- | --- |
AWG | ||
14 | 8 | PV-KST4/8II-UR PV-KBT4/8II-UR |
15 | 10/12 | PV-KST4/5…-UR |
PV-KBT4/5…-UR
16| 14| PV-KST4/5…-UR
PV-KBT4/5…-UR
****(ill. 7)
Crimpbereich Crimping range | Typ Type | Bestell-Nr. Order No. |
---|---|---|
AWG |
(ill. 8)
Locator PV-LOC Order No: 32.6040 (ill. 9)
Locator PV-LOC-B Order No: 32.6055
Note: When using the crimping pliers PV-CZM-22100, use the locator PV- LOC-B.
(ill. 10)
Locator PV-LOC-D Order No: 32.6074
Note: When using the crimping pliers PV-CZM-23100, use the locator PV- LOC-D.
Explanation for MC4-Evo 2
(ill. 11)
Crimping pliers incl. locator and built-in crimping die
Typ Type| Leiterquerschnitt Conductor cross section| Offener Crimpkontakt
(B-Crimp) Open crimp contacts (B-Crimp)| Geschlossener Crimpkontakt (O-Crimp)
Closed crimp contacts (O-Crimp)| Crimpzangen Crimping pliers| Crimpeinsätze
Crimping dies| Lokator Locator
---|---|---|---|---|---|---
PV-CZM-40100 32.6020-40100
|
PV-CZM-41100 32.6020-41100
|
PV-CZM-42100 32.6020-42100
|
PV-ES-CZM-40100 32.6021-40100
|
PV-ES-CZM-41100 32.6021-41100
|
PV-ES-CZM-42100 32.6021-42100
|
PV-LOC-C 32.6056
PV-KST-EVO 2/2.5…-UR PV-KBT-EVO 2/2.5…-UR| 2.5 mm2| •| | •| •| | •| •| | •
14 AWG| •| | •| •| | •| •| | •
PV-KST-EVO 2/6…-UR,
PV-KBT-EVO 2/6…-UR
| 4 mm2| •| | •| •| •| •| •| •| •
12 AWG| •| | •| •| •| •| •| •| •
6 mm2| •| | •| •| •| •| •| •| •
10 AWG| •| | •| •| •| •| •| •| •
PV-KST-EVO 2/10…-UR, PV-KBT-EVO 2/10…-UR| 10 mm2| •| | | | •| | | •| •
8 AWG| •| | | | •| | | •| •
Individual parts
(ill. 12 + 13 + 14) Interchangeable crimping dies
Pos.
| Leiterquerschnitt Cable cross section| geeignet für suitable for
---|---|---
| mm2| AWG|
1| 1,5| | PV-KST4-EVO 2/2,5…-UR
PV-KBT4-EVO 2/2,5…-UR
2| 2,5| 14| PV-KST4-EVO 2/2,5…-UR
PV-KBT4-EVO 2/2,5…-UR
3| 4| 12| PV-KST4-EVO 2/6…-UR PV-KBT4-EVO 2/6…-UR
| 1| |
| 2| |
| 3| |
| | | 12
(ill. 12)
Crimpbereich Crimping range | Typ Type | Bestell-Nr. Order No. |
---|---|---|
mm2 | AWG | |
1,5 / 2,5 / 4 | 14 / 12 | PV-ES-CZM-40100 |
Pos. | Leiterquerschnitt Cable cross section | geeignet für suitable for |
--- | --- | --- |
mm2 | AWG | |
4 | 2,5 | 14 |
PV-KBT4-EVO 2/2,5…-UR
5| 4| 12| PV-KST4-EVO 2/6…-UR PV-KBT4-EVO 2/6…-UR
6| 6| 10| PV-KST4-EVO 2/6…-UR PV-KBT4-EVO 2/6…-UR
(ill. 13)
Crimpbereich Crimping range | Typ Type | Bestell-Nr. Order No. |
---|---|---|
mm2 | AWG | |
2,5 / 4 / 6 | 14 / 12 / 10 | PV-ES-CZM-41100 |
Pos. | Leiterquerschnitt Cable cross section | geeignet für suitable for |
--- | --- | --- |
mm2 | AWG | |
7 | 4 | 12 |
8 | 10 | 8 |
(ill. 14)
Crimpbereich Crimping range | Typ Type | Bestell-Nr. Order No. |
---|---|---|
mm2 | AWG | |
4 / 10 | 12 / 8 | PV-ES-CZM-42100 |
(ill. 15)
Locator PV-LOC-C Order no: 32.6056
Exchanging the crimping die
Removing the crimping die
(ill. 16)
Close the crimping pliers.
(ill. 17)
Remove completely both mounting screws: the long S and the short S1. Open the
crimping pliers (press com-pletely together and release)
(ill. 18)
Remove the upper crimping die
(ill. 19)
Remove the lower crimping die.
Fitting the crimping die
(ill. 20)
- Open the crimping pliers (press com-pletely together and release).
- Insert both crimping dies.
- The markings must be on the same side as the marking on the crimping pliers.
- Close crimping pliers and screw both crimping dies.
- But take care not to strip screw heads and to put each screw in its proper location.
(ill. 21)
Affix locator onto the guide pin.
(ill. 22)
Rotate the locator (held magnetically)
(ill. 23)
Lock the locator.
Crimping
(ill. 24)
- Open and hold clamp (K).
- Place the contact in the appropriate cross-section range.
- Turn the crimping flaps (C) upwards.
- Release clamp (K).
- The contact is fixed.
(ill. 25)
Verify if the crimping flaps are still correctly aligned.
Press the pliers gently together until the crimping flaps are properly located
with-in the crimping die.
(ill. 26)
Insert the stripped cable end until the cable strands come up against the
clamp.
Completely close the crimping pliers.
(ill. 27)
Visually check the crimp according to the criteria written in IEC 60352-2:2006
- A1:2013
Confirm that:
- All of the strands have been captured in the crimp sleeve
- The crimp sleeve is not deformed or missing any portion of the crimp flaps
- That the crimp is symmetrical in form
- A “brush” of conductor strands are visible on the contact side of crimp.
Verify crimp height. Typical values for the crimp height for Stäubli PV cable Flex-Sol-Evo TX and Flex-Sol-Evo DX are listed below:.
MC4| MC4-Evo 2| mm2| AWG| Offener Crimpkontakt (B-Crimp) Open crimp contacts
(B-Crimp)| Geschlossener Crimpkontakt (O-Crimp) Closed crimp contacts
(O-Crimp)| Kabel Cable| Crimphöhe Crimp height
---|---|---|---|---|---|---|---
PV-KBT4/2,5…-UR| PV-KST4-EVO 2/2.5…-UR PV-KBT4-EVO 2/2.5…-UR
PV-KST4-EVO 2/6…-UR PV-KBT4-EVO 2/6…-UR
PV-KST4-EVO 2/6…-UR PV-KBT4-EVO 2/6…-UR
PV-KST4-EVO 2/10…-UR PV-KBT4-EVO 2/10…-UR
| 2.5
4.0
6.0
10
| 14
12
10
8
14
12
10
8
|
- Flex-Sol-Evo TX 2,5 Flex-Sol-Evo DX 2,5
- Flex-Sol-Evo TX 4,0 Flex-Sol-Evo DX 4,0
- Flex-Sol-Evo TX 6,0 Flex-Sol-Evo DX 6,0
- Flex-Sol-Evo TX 10 Flex-Sol-Evo DX 10
- Flex-Sol-Evo DX 2,5
- Flex-Sol-Evo DX 4,0
- Flex-Sol-Evo DX 6,0
- Flex-Sol-Evo DX 10
| 1.80
2.15
2.40
3.02
2.20
2.50
2.50
3.12
PV-KST4/2,5…-UR
PV-KBT4/6…-UR
PV-KST4/6…-UR
PV-KBT4/6…-UR
PV-KST4/6…-UR
PV-KBT/10…
PV-KST/10…
PV-KBT4/5…-UR
PV-KST4/5…-UR
PV-KBT4/5…-UR
PV-KST4/5…-UR
PV-KBT4/5…-UR
PV-KST4/5…-UR
PV-KBT4/8II-UR
PVKST4/8II-UR
Good crimp
Bad crimp:
- Stamped parts bent wrongly
- Material flow outwards
- Open crimp wings
- Not included strands
Hersteller/Producer:
Stäubli Electrical Connectors AG
Stockbrunnenrain 8
4123 Allschwil/Switzerland
Tel. +41 61 306 55 55
Fax +41 61 306 55 56
mail ec.ch@staubli.com
www.staubli.com/electrical