ACV 25 C Evo Heat Master Instruction Manual
- May 15, 2024
- ACV
Table of Contents
- ACV 25 C Evo Heat Master
- Product Information
- Product Usage Instructions
- FAQs
- General Information
- USING THE CONTROL PANEL
- IN CASE OF PROBLEM
- EZ Setup
- COMBUSTION CHARACTERISTICS
- CALCULATION OF THE FLUE PIPE LENGTH
- Installation
- Commissioning
- Maintenance
- Troubleshooting
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
ACV 25 C Evo Heat Master
Product Information
Specifications
- Product Name: HeatMaster 25 C Evo
- Language: English
- Table of Contents Included
- General Information, User’s Guide, Technical Specifications, Installation, Maintenance Sections Available
Product Usage Instructions
General Information
This manual contains important information for the installation, starting up, and maintenance of the appliance. It must be provided to the user for careful reading and safekeeping.
Safety Instructions
Follow these essential safety instructions:
- If you smell gas, immediately isolate the gas supply, ventilate the area, and notify your gas supplier or installer.
- Avoid storing flammable or corrosive products near the appliance.
- Children and individuals with reduced capabilities should be supervised when using the appliance.
- Install carbon monoxide detectors in recommended areas for safety.
Installation
Follow these steps for installation:
- Check required tools for starting up.
- Perform checks before starting up.
- Fill the system as instructed.
- Start up the boiler and check/adjust the burner if
necessary.
Maintenance
Regular maintenance is essential. Follow these steps:
- Refer to the maintenance section in the manual for detailed instructions.
- Perform scheduled maintenance tasks to ensure optimal performance.
- Keep the appliance clean and well-maintained.
FAQs
- What should I do if I smell gas?
- If you smell gas, immediately isolate the gas supply, ventilate the area, and contact your gas supplier or installer for assistance.
- Can children use the appliance?
- Children aged 8 years and above can use the appliance under supervision and with proper instruction on safety precautions.
- Where should carbon monoxide detectors be installed?
- ACV recommends installing at least two hard-wired carbon monoxide detectors with alarms and battery back-up, one in the mechanical room and another in the living area outside the bedroom(s).
“`
HeatMaster
25 C Evo
Installation, Operation & Maintenance
A1010445-664Y8200 · B
Instructions for the User and the Installer
EN
General Information
We accept no liability should any damage result from the failure to comply with the instructions contained in this technical manual.
This manual contains important information with respect to the installation,
the starting up and the maintenance of the appliance.
This manual must be provided to the user, who will read it carefully and keep
it in a safe place.
Essential instructions for safety
· It is prohibited to carry out any modifications to the appliance without the
manufacturer’s prior and written agreement.
· The product must be installed by a qualified engineer, in accordance with
applicable local standards and regulations.
· The installation must comply with the instructions contained in this manual
and with the standards and regulations applicable to heating systems.
· Failure to comply with the instructions in this manual could result in
personal injury or a risk of environmental pollution.
· The manufacturer declines all liability for any damage caused as a result of
incorrect installation or in the event of the use of appliances or accessories
that are not specified by the manufacturer.
Essential instructions for the correct operation of the appliance
· In order to ensure that the appliance operates correctly, it is essential to
have it serviced by a certified installer or maintenance contractor every
year.
· In case of anomaly, please call your service engineer.
· Faulty parts may only be replaced by genuine factory parts.
General remarks
· The availability of certain models as well as their accessories may vary
according to markets.
· The manufacturer reserves the right to change the technical characteristics
and features of its products without prior notice. Please check for an updated
version of this manual in the documentation page on the website www.acv.com.
· In spite of the strict quality standards that ACV applies to its appliances
during production, inspection and transport, faults may occur. Please
immediately notify your approved installer of any faults.
GENERAL SAFETY INSTRUCTIONS FOR GAS APPLIANCES
If you smell gas:
– Immediately isolate the gas supply.
– Open windows and doors to ventilate the area.
– Do not use any electrical appliances and do not operate any switches.
– Immediately notify your gas supplier and/or your installer.
Do not store any flammable or corrosive products, paint, solvents, salts,
chloride products and other detergent products near the appliance.
This appliance can be used by children aged from 8 years old and above and
persons with reduced physical, sensory or mental capabilities or lack of
eXperience and knowledge, if they have been given supervision or instruction
concerning the use of the appliance in a safe way and understand the hazards
involved.
Cleaning and user maintenance shall not be performed by children without
supervision.
Children shall not play with the appliance.
A byproduct of any gas fired appliance is carbon monoXide. ACV recommends the
installation of a minimum of two (2) hard-wired carbon monoXide detectors with
an alarm and battery back-up; one in the mechanical room where the boiler is
located and another installed in the living area outside the bedroom(s) for
all installations.
EN A1010445-664Y8200 · B
3
General Information
MEANING OF SYMBOLS
Symbols on the packaging Fragile
Keep dry
Keep standing, up
Danger of tipping over
Hand truck or pallet truck required for transport
Symbols on the appliance Domestic Hot Water circuit Primary circuit
Electricity
Symbols in the manual Essential instruction for safety (of persons and
equipment) Essential instruction for electrical safety (electrical hazard)
Essential instruction for the correct operation of the appliance or the system
General remark Safety valve connected to the sewage system Connection to the
sewage system
WHAT TO CHECK ON A REGULAR BASIS
ACV recommends to check the system at least every 6 months as follows:
· Check that the system water pressure is at least 0.1 MPa (1 bar) when cold.
If the pressure drops below 0.07 MPa (0.7 bar), the built-in pressure sensor
blocks the appliance until the pressure exceeds 0.12 MPa (1.2 bar).
· If it is required to top up the system to maintain the minimum recommended
water pressure, always turn the appliance off and only add small amounts of
water at a time. If a large amount of cold water is added in a hot boiler, the
boiler can be damaged definitively.
· If the system needs to be refilled repeatedly with water, please contact
your installer.
· Check that there is no water on the floor under the boiler. If there is,
please call your installer.
· If a condensate neutralisation system is installed, check it and have it
cleaned regularly.
· Check regularly that there is no error message (lockout) on the screen.
Refer also to the Troubleshooting table in “In case of Problem…” on page 7 or
call your installer as required.
General remarks
· The end user is only allowed to carry out the basic set-up operations mentioned in “Controller Set-up Guide” on page 8, after he has received all relevant instructions from the installer. Any other set-up must be carried out by an approved installer.
· If the end user misuses the installer code to access installer-specific parameters and makes changes that cause a system failure, any warranty claim will be void.
· To
get
additional
information on how to use
the ACVMax interface, refer
to the Installer’s Handbook
available at www.acv.com.
END OF THE PRODUCT LIFE
At the end of the service life of the product, do not dispose of the product
as solid urban waste. Hand it over to a differentiated waste collection
centre.
Please contact your installer or your ACV representative for the removal and
disposal of your appliance.
4
EN A1010445-664Y8200 · B
User’s Guide
USING THE CONTROL PANEL
1 – ACVMax Touch control panel – It is comprised of an LCD display and soft
keys reacting to the touch
2 – ACVMax LCD Display – It is the setup interface of the boiler and indicates
the parameter values, the error codes and the set-up status of the parameters.
It displays a series of screens, each showing information and/or icons. The
main icons are detailed on the following page.
3 – Installer function – By touching simultaneously the up and down arrow keys
for 3 seconds, the installer can open the access code window of the ACVMax
controller and set up the system once the code has been filled in.
4- Arrow touch soft keys and OK/Reset touch key To browse through the screens
and menus of the ACVMax controller, set up the appliance, increase and
decrease the displayed values and validate the selections. The OK/Reset key is
also used to RESET the appliance after a blocking (following the instructions
on the screen).
5- Sleeping mode soft key – To put the unit in a sleeping mode.
When touching the soft key, the unit is in a sleeping mode but is not isolated
from power supply. Therefore, live current is still present in the unit. For
your safety, disconnect electrical power supply to the unit before maintenance
or making any electrical connections to avoid possible electric shock hazard.
Failure to do so can cause serious injury, or death.
· When putting in sleeping mode using the soft key, the appliance will not
react to any heat demand. However, the basic appliance protection functions
(such as frost protection, etc.) remain active.
· In addition, the arrow soft keys are no longer illuminated, and the soft key
lighting is dimmed.
6- ON/OFF Master switch – To turn the appliance ON and OFF. When in OFF
position, no power is supplied to the appliance.
The ACVMax navigation is performed through soft keys that react to the touch
and emit a short beep when tapped.
Exert a light and short touch (tap) on the soft keys to activate their
function. Holding the touch too long will not generate any reaction from the
ACVMax Touch, unless it is a combination of soft keys meant to be touched
simultaneously for a determined duration, as instructed in this manual. The
arrow keys can also be held longer to increase or decrease values faster.
Navigation through the menus and selection of items/ modification of values is
performed through four arrow soft keys , , , . The center soft key is used for
validation (and for Reset in some cases).
The installer is provided with full access to all available features after
simultaneously touching the and soft keys for 3 seconds and entering a code.
1
2
3
4
5
6
1 HeatMaster
2
84°C
CH
DHW
61°C
P3
P4
Target = 85°C
Boiler Protection
EN A1010445-664Y8200 · B
5
User’s Guide
HOME SCREEN
The Home Screen presents status information in a very user-friendly way so
that the current state of the boiler can be quickly accessed.
· Screen backlight – it will illuminate when any soft key is touched, and
remain illuminated for five minutes.
· Screen brightness – it can be adjusted at the Home screen by touching and
holding simulta-
neously the and soft keys for 2 seconds. Touch the and soft key to increase or
de-
crease the contrast. Touch to end the process.
Main Icons of the ACVMAX Touch display
CH – indicates information related to Central/space Heating.
DHW – indicates information related to Domestic Hot Water.
Home – to go back to the home screen.
Back – to go back to the previous screen.
Warm Weather Shutdown – displays on the home screen when the outdoor
temperature reaches the Warm Weather Shutdown temperature.
Reset – to reset the system to the factory settings.
Settings – to access controller settings (languages, units, etc.).
Easy Setup – to quickly adjust the most common settings.
CH/DHW operation – to enable/disable the central/ space heating or Domestic
Hot Water functions
Information – to get information on the boiler.
STAND-BY SCREEN
This screen is displayed at start-up. It indicates that the HeatMaster is
ready to respond when a demand is received.
HeatMaster
84°C
61°C
Target = —
Stand-by
LOCKOUT SCREEN
If a problem occurs, the Lockout screen replaces the Home screen. The
backlight also remains on as long as the problem is not solved. Pressing any
arrow button will return to the Home screen. Using the code located in the
right bottom corner of the screen, troubleshoot the problem, either with the
table located in paragraph “In case of Problem…” on page 7, or with the
Lockout code table in the Installer’s Handbook (for the installer only).
Low Water
Water pressure has fallen below 0.7 bar. Increase pressure to normal range.
If problem persists, call for service
E37
Lockout message. Refer to “In case of Problem…” on page 7 for more
information.
Body text. The first sentence describes the lockout, the second sentence gives
a possible cure, and the third tells how to reset the lockout.
Lockout reference code. Refer to “In case of Problem…” on page 7 for more
information.
The appliance is represented in the center of the Home Screen. Basic operating information such as supply and return temperatures are displayed as well as current burner status.
Radiator icon: indicates that a central heating call has been received. A
small number 1 or 2 indicates which CH calls are active
A flame symbol is displayed when the unit is fired. The flame size changes to
indicate the current firing rate.
Basic information: The user can toggle through items using the and soft keys
to view Target, Supply, Return, Domestic, Outdoor and System temperatures, and
System pressure.
1 HeatMaster
2
84°C
CH
DHW
61°C
P3
P4
Target = 85°C
Boiler Protection
Tap icon: indicates that a DHW call has been received. Circulator icons:
indicate which circulators are currently powered.
Status line: displays the current operating state of the boiler. See next
page.
6
EN A1010445-664Y8200 · B
User’s Guide
STATUS MESSAGES
· Stand-by – Indicates that the HeatMaster is ready to respond when a demand
is received.
· CH Demand – A central heating call has been received.
· DHW Demand – A domestic hot water call has been received.
· CH / DHW Demand – Central heating and domestic hot water calls are being
received simultaneously. Both calls are being satisfied simultaneously because
domestic hot water priority has been disabled.
· DHW Priority – Central heating and domestic hot water calls are being
received simultaneously. Domestic hot water call is being satisfied first
because it has priority over central heating calls.
· Priority Timeout – Central heating and domestic hot water calls are being
received simultaneously. The domestic hot water priority time limit has been
exceeded. Priority will now switch back and forth between central heating and
domestic hot water calls until one call is satisfied.
· External Demand – An external modulation call has been received.
· Manual Operation – The burner or circulators have manually been enabled in
the Installer Menu.
· CH Burner Delay – The burner will not fire until the call blocking time has
elapsed.
· DHW Burner Delay – The burner will not fire until the call blocking time has
elapsed.
· CH Setpoint Reached – The burner is not fired because the supply/system
water temperature exceeds the setpoint. The central heating circulator
continues to operate and the burner will fire again once the supply/system
water temperature drops below the setpoint.
· DHW Setpoint Reached – The burner is not fired because the supply/system
water temperature exceeds the setpoint. The built-in circulator continues to
operate and the burner will fire again once the supply/ system water
temperature drops below the setpoint.
· CH Post Pump – The central heating circulator is running to remove heat from
the HeatMaster at the completion of a call.
· DHW Post Pump – The domestic hot water circulator is running to remove heat
from the HeatMaster at the completion of a call.
· Freeze Protection – The burner is fired because the freeze protection
feature has been activated. Freeze protection will end once the supply/system
water temperature is raised to 15°C.
· Boiler Protection – The burner firing rate is being reduced because of an
excessive difference between the boiler supply and return temperatures. The
firing rate will begin increasing once the temperature difference is less than
25°C.
· Lockout Description – The lockout which currently has the HeatMaster shut
down is displayed.
IN CASE OF PROBLEM
Check the list of faults and corresponding codes below to get the solution(s). If no solution is provided here, please contact your installer who will determine the correct solution by referring to”Troubleshooting” on page 45.
Fault code
Problem
Possible Cause(s)
Solution
The appliance does not turn – on when pressing the ON/OFF No power supply
Master switch
Check the power supply and that the appliance power plug is connected to the network.
E 01 Failed ignition
The burner failed to light after 5 ignition attempts
Check gas supply to the boiler.
E 13 Reset limit reached
Resets are limited to 5 every 15 minutes
Turn unit OFF and ON to resume normal operation.
E 34 Low voltage E 37 Low Water E 94 Internal Display Fault
Line voltage has fallen below an accept- The boiler will automatically reset once line
able operating level
voltage returns to normal.
Water pressure has fallen below an Refill the system to reach a normal range
acceptable operating level (0.07 MPa pressure. The boiler will automatically reset
[0.7 bar])
once water pressure returns to normal.
Display memory error
Turn appliance off and on to resume normal operation.
EN A1010445-664Y8200 · B
7
User’s Guide
CONTROLLER SET-UP GUIDE Starting from the Home screen :
1 HeatMaster
2
84°C
CH
DHW
61°C
P3
P4
Target = 85°C
Boiler Protection
· To navigate on the screen, use the UP, DOWN, LEFT and RIGHT soft keys
,
· Use the OK key to validate a selection.
· To increase/decrease values, use the UP and DOWN keys, or LEFT and RIGHT, according to the situation
EZ Setup
CH / DHW Operation
Select Language
Boiler Information
Heating enabled
English
Français Nederlands Español Italiano Deutsch
Boiler Information
aababbcccddedeeffbfbbbbbbb b
aaabbbcccdddeeefffbbbbbbbbbb
b b
Lockout History
aaabbbcccdddeeeffbfbbbbbbb b
aaabbbcccdddeeefffbbbbbbbb
b b
Heating EZ Setup
DHW EZ Setup
EZ Setup Reset
Display EZ Setup
8
EN A1010445-664Y8200 · B
User’s Guide
HEATING EZ SETUP
Heating EZ Setup allows the installer to quickly customize the central heating
settings for the application.
Select CH Demand (No outdoor sensor connected)
EZ Setup
Heating EZ Setup
Select CH Demand
Thermostat & Setpoint Constant & Setpoint 0 – 10 V Power Modulation 0 – 10 V
Temp. Modulation
Select CH Demand prompts the installer to select how a CH Demand is generated. Thermostat & Setpoint – A central heating call from a thermostat or zone panel will enable the HeatMaster and the setpoint will be fixed for central heating calls. After Thermostat & Setpoint is selected, the CH1 Setpoint screen appears. (see below).
Select CH Demand
Thermostat & Outd. Curve Constant & Outdoor Curve Constant & Setpoint 0 – 10 V
Power Modulation
0 – 10 V Temp. ModulatCioHn1 Setpoint
82°C
20°C
87°C
CH2 Setpoint
60°C
20°C
87°C
EZ Setup Complete
Heating EZ setup is complete. Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
Constant & Setpoint – The HeatMaster will maintain setpoint without an
external CH call from a thermostat or zone panel. The setpoint will be fixed
for CH calls. After Constant & Setpoint is selected, the CH1 Setpoint screen
appears.
CH1 Setpoint prompts to enter the fixed setpoint for a CH1 heating call when a
Setpoint option is chosen in Select CH Demand.
Touch the or soft keys to adjust the temperature set-
point then touch to store the setting. The CH2 Setpoint screen then appears.
CH2 Setpoint prompts to enter the fixed setpoint for a CH2 heating call when a
Setpoint option is chosen in Select CH Demand.
Touch the or
point then touch Heating EZ Setup.
soft keys to adjust the temperature setto store the setting and complete the
CH1 Default: 82°C CH2 Default: 60°C
Select CH Demand
Thermostat & Setpoint Constant & Setpoint 0 – 10 V Power Modulation 0 – 10 V
Temp. Modulation
EZ Setup Complete
Heating EZ setup is complete. Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
0 – 10V Power Modulation – This option allows the HeatMaster firing rate to be
controlled by an external control system.
0 – 10V Temp. Modulation – This option allows the appliance CH temperature to
be controlled by an external control system.
Refer to the Installer’s Handbook for Evo Appliances for more information.
EN A1010445-664Y8200 · B
9
User’s Guide
Select CH Demand (Outdoor sensor connected)
EZ Setup
Heating EZ Setup
Select CH Demand
Thermostat & Outd. Curve Constant & Outdoor Curve Constant & Setpoint 0 – 10 V
Power Modulation 0 – 10 V Temp. Modulation
Select CH Demand prompts the installer to select how a CH Demand is generated.
There are several Select CH Demand options, among which the installer must
make a selection.
Thermostat & Outd. Curve This option is only displayed when the outdoor
temperature sensor is connected. A central heating call from a thermostat or
zone panel will enable the boiler and the setpoint will vary with the outdoor
temperature for central heating calls. After Thermostat & Outd. Curve is
selected, the Select CH1 Reset Curve screen appears (see below).
Select CH Demand
Thermostat & Outd. Curve Constant & Outdoor Curve Constant & Setpoint
0 – 10 V Power MSodeulelactitoCnH1 Outd. Curve
0 – 10 V Temp. M82o°Cdulation MAX
27°C
Select CH2 Outd. Curve
186°C0°C
-12°C
Current Settings
Warm Weather Shutdown
27°C
Off
18°C
-12°C
Current Settings
Off
EZ Setup C25o°Cmplete
Heating EZ setup is complete. Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
Constant & Outdoor Curve – This option is only displayed when the outdoor
temperature sensor is connected. The HeatMaster will maintain the setpoint
without an external call from a thermostat or zone panel. The setpoint will
vary with the outdoor temperature for central heating calls. Select CH1 Outd.
Curve prompts to select an outdoor curve for a CH1 heating call when an
Outdoor Reset option is chosen in Select CH Demand. Outdoor curve presets are
available to cover most applications. The outdoor curve can also be adjusted
to any desired settings in the Installer Menu (refer to Installer’s Handbook).
Touch the or soft keys to select the outdoor reset curve appropriate for the
type of
heating system, then touch to store the setting. The Select CH2 Reset Curve
screen then appears. Default: Systems with a temperature between 27°C and 82
°C.
Select CH2 Outd. Curve – prompts to select an outdoor curve for a CH2 heating
call when an Outdoor Reset option is chosen in Select CH Demand. Outdoor curve
presets are available to cover most applications. The outdoor curve can also
be adjusted to any desired settings in the Installer Menu (refer to
Installer’s Handbook)..
Touch the or soft keys to select the outdoor reset curve appropriate for the
type of
heating system, then touch to store the setting. The Warm Weather Shutdown
screen then appears. Default: Systems with a temperature between 27°C and 60
°C
Warm Weather Shutdown allows to enter an optional outdoor temperature at which
to disable the central heating function. The HeatMaster will continue to
respond to a domestic hot water call or a 0- 10V Modulation Signal when the
outdoor temperature exceeds the Warm Weather Shutdown Temperature setting.
Touch the or soft keys to adjust the Warm Weather Shutdown Temperature then
touch the soft key to store the setting and complete Heating EZ Setup.
The Warm Weather Shutdown icon ( ) is displayed on the home screen when the
outdoor temperature reaches the Warm Weather Shutdown temperature. Default:
OFF.
10
EN A1010445-664Y8200 · B
User’s Guide
DHW EZ SETUP
EZ Setup DHW EZ Setup
Select DHW Demand
Thermostat Sensor
DHW Boiler Setpoint
75°C
35°C
87°C
DHW EZ Setup
Select DHW Demand
Thermostat Sensor
DHW Setpoint 60°C
20°C
75°C
Select DHW Demand prompts the installer to select how a DHW Demand is
generated. There are two Select DHW Demand options, among which the installer
must make a selection. When Thermostat is selected in Select DHW Demand, a
domestic hot water call from an aquastat or dry contact switch will enable the
HeatMaster with a fixed setpoint for a domestic hot water call.. When Sensor
is selected in Select DHW Demand, it operates with the Indirect Water Heater
Sensor. The HeatMaster monitors the DHW storage temperature and generates a
DHW call whenever the temperature drops below the DHW storage setpoint by 3°C.
Default : Sensor DHW Boiler Setpoint prompts to enter the fixed boiler
setpoint temperature during a hot water call when the Thermostat option is
selected.
Touch the or soft keys to adjust the required temperature setpoint then touch
to store the setting. Default: 75°C.
DHW Setpoint prompts to enter the DHW storage setpoint temperature. Touch the
or soft keys to adjust the required temperature setpoint then touch store the
setting. Default: 60°C.
The DHW storage setpoint will automatically be set 15°C higher than the DHW
Setpoint setting.
DHW Priority Timeout Off
Off
120 min.
EZ Setup Complete
DHW EZ setup is complete. Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
DHW Priority Timeout prompts to enter an optional time limit that a domestic
hot water call has priority over central heating call.
Touch the or soft keys to adjust the required timeout value, if required, then
touch to store the setting and complete the DHW setting.
Default: Off
EN A1010445-664Y8200 · B
11
EASY SETUP RESET
EZ Setup
EZ Setup Reset
EZ Setup Reset
Press OK to restore factory settings, any other button to keep current
settings.
User’s Guide
EZ Setup Reset allows to reset all EZ setup settings back to the original
factory defaults. Follow the on-screen instructions to reset all EZ setup
settings.
DISPLAY EASY SETUP
EZ Setup Display EZ Setup
English
Français Nederlands Español Italiano Deutsch
Select Unit
Fahrenheit Celsius
Display EZ Setup allows to select the interface language (Nine different
languages: English, French, Dutch, Spanish, Italian, German, Czech, Polish and
Russian).
Touch the or soft keys to select the required language then touch to store the
setting.
Display EZ Setup allows to select the interface temperature unit.
Touch the or soft keys to select the required unit then touch to store the
setting.
12
EN A1010445-664Y8200 · B
CH/DHW OPERATION
CH / DHW Operation Heating enabled DHW enabled
User’s Guide
CH/DHW Operation provides a simple way to enable/disable either the CH or the
DHW function of the HeatMaster. Touch the or soft keys to select the object
(CH or DHW icon), then touch to toggle between the enabled/disabled status.
The status of the circuit is displayed at the top of the screen. Using the
arrow keys, select the HOME or RETURN icon at the bottom of the screen to go
back either to the home page or to the previous screen respectively. Default:
BOILER INFORMATION
Boiler Information
Boiler Information
aababbcccddedeeffbfbbbbbbb b
aaabbbcccdddeeefffbbbbbbbbbb
Boiler Information
Boiler Status Heating Call DHW Call Boiler Firing Rate Ionization current Boiler Setpoint
Standby No No -A —
b b
Lockout History
aaabbbcccdddeeeffbfbbbbbbb b
abc abc abc
dddeeefffbbbbbbbb
b b
Lockout History
1. Blower speed
5h ago
2. DHW Sensor Open 2h ago
3. Sensor Drift 4. No error
25 h ago 27 h ago
5. No error 6. No error
2L7ohckaogout Details
27 hBalogwoer speed
Boiler Status Heating Call DHW Call Boiler Firing Rate Ionization current
—44% 44A
Boiler Information screen provides real time operating information of the
HeatMaster. Each line contains an information item followed by its current
value. Six lines are displayed on the screen at one time. Touch the or soft
keys to scroll through the items. For more information, refer to the
Installer’s Handbook of the HeatMaster boilers.
Lockout History records the last eight lockouts. Six lines are displayed on
the Lockout History screen at one time. Each line contains a lockout
description followed by how long ago the lockout occurred. Touch the or soft
keys to scroll through the items then touch
to select any of them and get more details through the Lockout Details screen.
For more information, refer to the Installer’s Handbook of the HeatMaster
boilers.
EN A1010445-664Y8200 · B
13
User’s Guide
APPLIANCE DESCRIPTION HEATMASTER® 25 C EVO
The HeatMaster® 25 C Evo is a condensing combination boiler. The boiler
combines ACV’s “Tank-inTank” concept with a double primary circuit to reach
the high performance of a TOTAL CONDENSATION, double-circuit boiler. Also
refer to ML Book for component views.
The HeatMaster® 25 C Evo model is equipped with a high efficiency charging
pump and with an ACV air/ gas premix burner with low NOx emissions. During
operation, the burner starts automatically as soon as the boiler temperature
gets lower than the preset temperature and stops as soon as the preset
temperature is reached.
The HeatMaster® 25 C Evo features a built-in frost protection mechanism: as
soon as the flow temperature [NTC1 probe] drops below 7°C, the central heating
pumps are activated. As soon as the flow temperature is at 5°C, the burner
starts up until the flow temperature rises above 15°C. The pumps continue to
run for around 10 minutes. The function can be enabled or disabled through the
installer menu. When the frost protection is disabled, only the pumps operate.
An anti-freeze function is also available if an outdoor temperature sensor is
connected, the pumps are activated when the outside temperature drops below
the threshold defined through the Freeze protection function in the installer
menu. In order to enable the HeatMaster boiler to protect the whole system
against freezing, all the valves of the radiators and the convectors should be
completely open.
Configuration in a system
The HeatMaster® 25 C Evo boiler can be set up in different types of systems,
either high or low temperature, or both, with or without external Domestic Hot
Water tank. The HeatMaster® 25C Evo boilers can also be set up in a cascade
system, using an external controller. Refer to “Configuration and system set-
up” on page 34 for more information.
It is up to the installer to determine the best solution and reach the results
the user is expecting.
One basic configuration is shown in this manual (see “Configuration and system
set-up” on page 34), with the required accessories, required electrical
connections and ACVMax setup using the EZ setup function.
Additional configurations requiring a more advanced setup are shown in the
Installer’s Handbook of the appliance. The setup of those systems must be made
exclusively by the installer using the installer code.
For any other configuration that is not mentioned in either manuals, please
contact your ACV representative.
14
EN A1010445-664Y8200 · B
Technical Specifications
COMBUSTION CHARACTERISTICS
Main Characteristics
Input (PCI)
Output at 100%
Efficiency at 100% Efficiency at 30% load (EN677) Combustion efficiency
NOx (Class 6) i.a.w. EN15502-1+A1:2016
CO
CO2 Max gas flow rate G20/G25
max min (80/60°C) (50/30°C) (80/60°C) (50/30°C)
at 100% Max. output Min. output Weighted Max. output Min. output Max. output
Min. output 20 mbar 25 mbar
Max. gas flow rate G31
30/37/50 mbar
Normal
Temp of flue gases
Max.
Min.
Average temp. of combustion products
DHW mode
Mass flow rate* of flue gases
Normal Min. output
Standby loss
T = 45 K T = 30 K
- Mass flow rate values were calculated for G20 and G31 with an air factor of 1.3.
ELECTRICAL CHARACTERISTICS
Also refer to ML Book for Wiring Diagrams.
kW kW kW kW % % % %
mg/kWh
mg/kWh
mg/kWh
ppm ppm %CO2 %CO2 m³/h m³/h m3/h Kg/h °C °C °C °C g/s g/s
W W
HM 25 C Evo
G20/G25
G31
25.0 5.0 24.3 26.0 98.0 103.9 109.0 97.5 64 12 26.3 27 6 8.8 8.3 2.66 2.96 — — 62.0 120 32.9 52.6 11.6 2.45 124 79
25.0 5.0 24.3 26.0 98.0 103.9 109.0 97.5 — — — — — 10.1 9.3 — — 0.98 1.95 57.7 120 32.9 52.6 11.6 2.54 124 79
Main Characteristics
Rated voltage Rated frequency
Electrical consumption
V~ Hz Max. W Min. W
Electrical consumption at 30% load
W
Electrical consumption in standby
W
Rated current (Fuse)
A
Class
HM 25 C Evo 230 50 95 19
24
3 16 IP 20
EN A1010445-664Y8200 · B
15
Technical Specifications
ErP DATA (ECODESIGN)
Boiler type and model
HeatMaster
Condensing boiler Low temp boiler
Combination heater Useful heat output
at 30% of rated heat output
P1
kW
at rated output and high-temp re- P4 gime
kW
Useful efficiency
at 30% of rated heat output
1
%
at rated output and high-temp re- 4 gime
%
Auxiliary electricity consumption
At full load At part load
elmax
W
elmin
W
In standby mode Standby heat loss
PSB
W
Pstby
W
Product Fiche Data (i.a.w. Commission Delegated Regulation 811/2013)
Medium temperature application
Declared load profile for water heating
Seasonal space heating energy efficiency class
Water heating efficiency class
Rated heat output
kW
Annual energy consumption for space heating
kWh
Annual energy consumption for water heating
kWh
Seasonal space heating efficiency
%
Water heating efficiency
%
Sound power level indoors LWA
dB
Able to work only during off- peak hours
Y/N
25 C Evo
7.9 24.3
98.2 87.6
95 19 3 92
Condensation XXL A B 24 12031 8151 94 74 60 N
16
EN A1010445-664Y8200 · B
Technical Specifications
HYDRAULIC CHARACTERISTICS
Main Characteristics
Capacity (primary)
L
Capacity (DHW)
L
Water pressure drop (primary circuit) (t = 20 K) mbar
HeatMaster 25 C Evo 120 80
3
HYDRAULIC PRESSURE DROP CURVE OF THE BOILER (PRIMARY)
Pressure drop (mbar)
18
16
14
12 HeatMaster® 45 TC
10
8 HeatMaster® 35 TC
6
4 HeatMaster® 25 TC
2
0
0
500
1000
1500
2000
2500
3000
Water flow rate (l/h)
DHW PERFORMANCE
Domestic hot water performance* (cold drink water at 10°C)
Operating conditions at 80°C
Constant flow at
40 °C [T = 30 K] L/h 60 °C [T = 50 K] L/h
Peak flow at
40 °C [T = 30 K] 60 °C [T = 50 K]
L/10′ L/10′
Peak flow 1st hour at
40 °C [T = 30 K] 60 °C [T = 50 K]
L/60′ L/60′
Reheat time from 10°C to 80°C
min.
DHW efficiency at T = 30 K
%
HeatMaster 25 C Evo 617 400
233.5 145 748 478 27 99.2
MAXIMUM OPERATING CONDITIONS
Maximum Service Pressure (tank full of water) * – Primary circuit :
……………………………………..0.3 MPa (3 bar) – DHW circuit : ………………………………….. 0.86 MPa (8.6
bar)
Maximum Operating Temperatures – Maximum temperature (primary) : ……………………….. 87°C – Maximum temperature (DHW) : …………………………… 75°C
Water Quality See “Recommendations for the Prevention of Corrosion and Scaling in Heating Systems” on the following page.
- The hydraulics of the boiler have been tested according to EN-15502, and the boiler is classified as a pressure class 3 appliance.
EN A1010445-664Y8200 · B
17
Technical Specifications
RECOMMENDATIONS FOR THE PREVENTION OF CORROSION AND SCALING IN HEATING SYSTEMS
How oxygen and carbonates can affect the heating system
Oxygen and dissolved gasses in the water of the primary circuit contribute to
the oxidation and the corrosion of the system components that are made of
ordinary steel (radiators, …). The resulting sludge is then deposited in the
appliance exchanger.
The combination of carbonates and carbon dioxide in the water results in the
formation of scale on the hot surfaces of the installation, including those of
the appliance exchanger.
These deposits in the heat exchanger reduce the water flow rate and thermally
insulate the exchange surfaces, which is likely to damage them.
Sources of oxygen and carbonates in the heating circuit
The primary circuit is a closed circuit; the water it contains is therefore
isolated from the mains water. When maintaining the system or filling up the
circuit, water renewal results in the addition of oxygen and carbonates in the
primary circuit. The larger the water volume in the system, the larger the
addition.
Hydraulic components without an oxygen barrier (PE pipes and connections)
admit oxygen into the system.
Prevention Principles
1. Clean the existing system before installing a new appliance
Before the system is filled, it must be cleaned in accordance with standard
EN14336. Chemical cleaning agents can be used.
If the circuit is in bad condition, or the cleaning operation was not
efficient, or the volume of water in the installation is substantial (e.g.
cascade system), it is recommended to separate the appliance from the heating
circuit using a plate-to-plate exchanger or equivalent. In that case, it is
recommended to install a hydrocyclone or magnetic filter on the installation
side.
2. Limit the fill frequency
Limit fill operations. In order to check the quantity of water that has been
added into the system, a water meter can be installed on the filling line of
the primary circuit.
Automatic filling systems are not recommended unless the fill frequency is
monitored and the scale and corrosion inhibitor remain at the correct levels.
If your installation requires frequent water refilling, make sure your system
is free of water leaks.
Inhibitors may be used in accordance with standard EN 14868.
3. Limit the presence of oxygen and sludge in the water
A deaerator (on the appliance flow line) combined with a dirt separator
(upstream of the appliance) must be installed according to the manufacturer’s
instructions.
ACV recommends using additives that keep the oxygen in solution in the water,
such as Fernox (www.fernox.com) and Sentinel (www.sentinel-solutions.net)
products.
The additives must be used in accordance with the instructions issued by the
manufacturer of the water treatment product.
4. Limit the carbonate concentration in the water
The fill water must be softened if its hardness is higher than 20° fH (11,2°
dH).
Check regularly the water hardness and enter the values in the service log.
Water hardness table :
Water hardness Very soft Soft Fairly hard Hard Very hard
°fH 0 – 7 7 – 15 15 – 25 25 – 42 > 42
°dH 0 – 3.9 3.9 – 8.4 8.4 – 14 14 – 23.5 > 23.5
mmolCa(HCO3)2 / l 0 – 0.7 0.7 – 1.5 1.5 – 2.5 2.5 – 4.2 > 4.2
5. Control the water parameters
In addition to the oxygen and the water hardness, other parameters of the
water must be checked.
Treat the water if the measured values are outside the range.
Acidity Conductivity Chlorides Iron Copper
6,6 < pH < 8,5 < 400 S/cm (at 25°C)
< 125 mg/l < 0,5 mg/l < 0,1 mg/l
18
EN A1010445-664Y8200 · B
Technical Specifications
CHIMNEY CHARACTERISTICS
Main Characteristics
concentric
mm
Air/flue pipe Ø
parallel
mm
HM 25 C Evo 80/125 80/80
Max. allowed flue pipe pressure drop
Pa
95
Max recommended length of concentric flue pipe (corresponding length in meters
of straight pipes) Ø 80/125, terminal included Max recommended length of
concentric flue pipe (corresponding length in meters of straight pipes) Ø
100/150, terminal included Max recommended length of dual flow (corresponding
length in meters of straight pipes) *
Available connection types
60
130***
Rigid Ø 80
Flex. Ø 80
56
26
B23 – B23P – C13(x) – C33(x) – C43(x) – C53(x)** – C63(x) – C83(x), C93(x)
- See page 21 to calculate the flue pipe length. ** A C53 connection requires an optional accessory. *** Not recommended – For more information, please contact your ACV representative.
It is mandatory to ventilate the boiler room. The high or low air vent opening
dimensions depend on the boiler power and the boiler room size. Refer to the
local regulations in force.
Make sure that the air inlet openings remain unobstructed at all times and
that air and flue pipe connections are tight and secure.
B23 C33
C43
C43
C43
C43
C13
C33
B23P
C93
C43
C43
C53
EN A1010445-664Y8200 · B
19
Technical Specifications
FLUE PIPE CONNECTION TYPES
It is mandatory to use ACV flue systems to connect the appliance.
B23p B23 C13(x)
C33(x)
C43(x)
C53(x) C63(x)
Connection to a combustion product exhaust system designed to operate with
positive pressure.
Connection to an exhaust duct that discharges the combustion products outside
the room where it is installed, with the combustion air being drawn directly
from the boiler room.
Connection using pipes fitted with a horizontal terminal that simultaneously
takes in combustion air for the burner and discharges combustion products
outside through openings that are either concentric or close enough together
to be subjected to similar wind conditions, i.e. openings shall fit inside a
square of 50 cm for boilers up to 70 kW and inside a square of 100 cm for
boilers above 70 kW.
Connection using pipes fitted with a vertical terminal that simultaneously
takes in fresh air for the burner and discharges combustion products outside
through openings that are either concentric or close enough together to be
subjected to similar wind conditions , i.e. openings shall fit inside a square
of 50 cm for boilers up to 70 kW and inside a square of 100 cm for boilers
above 70 kW.
Connection using two pipes to a collective duct system serving more than one
appliance; this system of collective ducts features two pipes connected to a
terminal unit that simultaneously takes in fresh air for the burner and
discharges the combustion products outside through openings that are either
concentric or close enough together to be subjected to similar wind
conditions. C43(x) boilers are suitable for a connection to a natural draught
chimney only.
Connection to separate ducts for supplying combustion air and discharging
combustion products; these ducts may end in zones with different pressure
levels, but are not allowed to be installed on opposite walls of the building.
Type C boiler meant to be connected to a system for supplying combustion air
and discharging combustion products, that is approved and sold separately
(Prohibited in some countries (e.g.
Belgium) – refer to local regulations and standards in force). Terminals for
the supply of combustion air and for the evacuation of combustion products are
not allowed to be installed on opposite walls of the building. See also the
following additional specifications:
· Maximum allowable draught is 200 Pa.
· Maximum allowable pressure difference between combustion air inlet and flue
gas outlet (including wind pressures) is 95 Pa.
· Condensate flow is allowed into the appliance.
· Maximum allowable recirculation rate of 10% under wind conditions.
C83(x) C93(x)
Connection using a single or double duct system. The system is made of a
normal exhaust flue duct that discharges the combustion products. The
appliance is also connected through a second duct fitted with a terminal, that
supplies the burner with fresh outdoor air. Please contact your ACV
representative for the meters of flue pipes that can be used to connect the
appliance(s).
Connection using an individual system whose combustion product exhaust duct is
installed in an exhaust duct that is integral with the building. The
appliance, the exhaust duct and the terminal units are certified as an
inseparable assembly. Minimum usable diameter for the vertical duct supplying
the combustion air is 100 mm.
The C93 configuration enables airtight operation in a pre-existing chimney. The combustion air crosses the space between the tubing and the pre-existing chimney. Make sure to clean the pre-existing chimney thoroughly prior to installation, especially if there is soot or tar residue. Make sure that there is a clearance area for the combustion air at least equivalent to the area that would have been provided by separate concentric ducts or air intake ducts.
20
EN A1010445-664Y8200 · B
Technical Specifications
CALCULATION OF THE FLUE PIPE LENGTH
When connecting the flue pipes, make sure not to exceed the maximum flue pipe length, recommended for the product, or the system pressure might decrease.
The flue pipe length can be calculated using the method shown below. Please refer to the tables below indicating the values in meters, applied to each of the connection components. Then compare the calculation result to the recommended maximum flue pipe length indicated in the table on previous page.
The equivalent length for pipes equipped with a measuring unit is equal to a 1 meter straight pipe
1 m straight pipe 90° elbow 45° elbow
Flue pipe length (L) (corresponding length in meters of straight pipe)
Concentric flue pipe Ø 80/125 mm (Terminal incl.)
Parallel flue pipe Ø 80 mm
(Terminal incl.)
1 m
1 m
2 m
2.3 m
1 m
1 m
1000 mm
L
2000 mm
2000 mm
1000 mm
L C33
L C13
Example of verification of the flue pipe length (L) in a concentric flue pipe
system for HeatMaster 25 C Evo (80/125):
The figure above shows an assembly is comprised of: 1 pipe with a measurement
unit + 3 x 90° elbows + 6 meters of straight pipes + 2 x 45° elbows
a) Using the above table, calculate the length in meters of the whole flue
pipe assembly: 1 + (3 x 2) + (6 x 1) + (2 x 1) = 15 m
b) Compare the resulting value with the maximum length (60 m).
This flue pipe length is within the recommended range.
Concentric connection
L C33
Parallel connection
EN A1010445-664Y8200 · B
21
Technical Specifications
CASCADE : CALCULATION OF THE MAXIMUM LENGTH OF FLUE PIPES
HeatMaster 25 C Evo cascade in a C43 chimney connection configuration
HeatMaster 25 C Evo cascade in a B23 chimney connection configuration
Make sure to install an external non-return valve on the flue connection and/or an approved flue cascade kit, as required. Please contact your ACV representative for the correct accessory.
Qty
Appliance type*
Maximum length in M.
2 to 6
HM 25 C Evo
Dn 150 30
Dn 150/200** 30
Dn 200 30
- This table is for systems built with boilers of identical power. For any other configuration, please contact your ACV representative.
**Dn 150/200 : Hor. = 150 mm, Vert.=200 mm
Elbow type
45° [M] 90° [M]
150
200
Equivalent Length
1.7m
3.8m
4.0m
5.8m
22
EN A1010445-664Y8200 · B
Technical Specifications
APPROVED CHIMNEY COMPONENTS
EN A1010445-664Y8200 · B
Connection type
Material / Ø mm
Terminals
Pipes
C93
PP Flex Ø 80
1. Set C93 Ø 80/125
13. Flexible PP PP Ø 80, 25 m
Extensions —
Components *
Bends
Measurement and condensate
recovery
Accessories
50. Connection
sheath for Ø
80/125, Ø 80
—
—
51. Connector FlexFlex PP Ø 80
Adapters —
2. Roof Terminal 14. Length 250 mm 30. Sliding extension, 34.43° – 45°
3. Wall terminal kit 15. Length 500 mm
straight + 50 to 35.87° – 90°
4. Wall terminal Kit 16. Length 1000 mm
130 mm
C13 C33
PP – Galva Ø 80/125
17. Length 2000 mm
44.Measuring tube 45.Measuring
T-piece with inspection
52. Weather Slate Steep
53. Bracket Ø 125 mm
54. Weather salte, flat roof Ø 390 mm
60. Expander SST/ Alu Ø 80/125 mm – 2 x Ø 80 mm
61. Expander PP/ ALU, Ø 60/100 mm – Ø 80/125 mm
- ACV/Groupe Atlantic references are provided in a separate crossreference table attached to this manual. Also refer to the latest ACV/Groupe Atlantic Price list for more information and the correct references.
23
Installation
SAFETY INSTRUCTIONS FOR THE INSTALLATION
Essential instructions for safety
· The connections (electrical, flue pipe, hydraulic) must be carried out in
accordance with local standards and regulations in force.
· Install the appliance on level base or vertically plumb support made of non-
combustible materials and of sufficient strength to support its weight.
· Use extreme care not to drop the appliance or cause bodily injury while
lifting or mounting the appliance onto the wall bracket or base. Once mounted,
verify that the appliance is securely attached to the bracket and wall or
safely set on its base.
· Do not use or store any flammable or corrosive products, such as paint,
solvents, salts, chloride products and other detergent products near the
appliance.
· Make sure that the condensate outlet is never obstructed and that a
condensate neutralisation system is installed if required.
· Make sure that all air vents are unobstructed at all times.
Essential instructions for the electrical safety
· Only an approved installer is authorized to carry out the electrical
connections.
· Make sure that the appliance is connected to the earth.
· Install a 2-way switch and a fuse or circuit breaker of the recommended
rating outside the appliance, so as to be able to shut power down when
servicing the appliance or before performing any operation on it.
· Isolate the external electrical supply of the appliance before performing
any operation on the electrical circuit.
· This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless supervised or unless they have been given instruction
concerning the use of the appliance by a person responsible for their safety.
Essential instructions for the correct operation of the appliance
· The appliance must be installed in a dry and protected area, with an ambient
temperature comprised between 0 and 45°C.
· Install the appliance to ensure easy access at all times.
· If the appliance contains a stainless steel DHW production tank, connect it
directly to the earth to prevent corrosion.
· If works need to be performed (in the boiler room or close to the air
vents), make sure to turn off the appliance to prevent dust from entering and
accumulating in the appliance heating system.
TOOLS REQUIRED FOR THE INSTALLATION
24
EN A1010445-664Y8200 · B
Installation
PACKAGE CONTENTS
At product reception and after removal of packaging, check the package
contents and that the appliance is free of damages.
· Boiler · Installation, Operation and Maintenance Instruc-
tions · Orifice for the natural gas to propane conversion
+ stickers + procedure (Except in Belgium) · Ball condensate trap to be
installed. · A primary safety valve Ø 1/2″ (F) to be installed
HANDLING INSTRUCTIONS
· The boiler weighs more than 180 kg, which could present a risk of injury.
Ask for help to handle it and use an appropriate lifting means.
· If using a pallet truck to transport the boiler, remove the bottom front
panel (see ML book for instructions).
· Bring the appliance as close as possible to the installation location before
removing the packaging.
· If necessary and to make transport easier, the boiler casing can be removed
for transportation to the final installation location. Refer to ML book for
the correct procedure.
· Before removing the packaging, ensure that the installation area is clear
and that there are no obstacles making the handling and installation difficult
or unsafe.
REMOVING THE PACKAGING
1. Remove the plastic wrapping. 2. Remove the protection pieces and discard
in ac-
cordance with applicable local regulations.
BOILER PREPARATION
· Close the circulation tube end tap (1) (access from the bottom of the
boiler)
1
The circulation tube is equipped with an end tap that is open when the boiler
is delivered (to prevent test water from being stuck in the circuit and
freezing during transport). Make sure that you close the tap before filling
the system with water. · Install the ball condensate trap, then the bottom
front panel (to be clipped in)
Fit the condensate trap, complete with the ball, making sure to install the
items in the correct sequence and connect the hose to the drain using a
connection that can be inspected. Fill the trap with clean water. Make sure to
prevent the condensates from freezing. Refer to the procedure provided with
the condensate trap, or get it from www.acv.com (See page 4 for an access with
QR code). · Install the safety valve : primary circuit safety valve at the
back of the boiler
· Remove the bottom panel stored at the back of the boiler for transport. Install on the appliance when the boiler is in its final position. Refer to the ML Book for the correct installation procedure.
· Perform the gas conversion to propane as required. Refer to “Conversion to Propane” on page 32.
EN A1010445-664Y8200 · B
25
Installation
SAFETY INSTRUCTIONS – HYDRAULIC CIRCUITS
Essential instructions for safety
· If the appliance is not equipped with one, the heating circuit of the system
must be fitted with an approved safety pressure relief valve, according to the
pressure mentioned on the type plate.
· Please refer to the applicable local regulations for the installation of the
required safety accessories in the hydraulic circuits. Please contact your ACV
representative for more information.
· Use a two-wrench method when tightening field piping onto the appliance
piping connections. Use one wrench to prevent the appliance connections from
turning and the second to tighten field piping. Failure to support the
appliance piping connections could damage piping or cause a leak.
· In the event of small amounts of hot water repeatedly being drawn off, a
stratification effect can develop in the tank. The upper hot water layer may
then reach very high temperatures.
· Hot water can cause scalding! The temperature of the domestic hot water can
be adjusted up to 75 °C in the appliance. However, the temperature of the
domestic hot water at the drawing off point must comply with local
regulations.
· ACV recommends therefore the installation of a pre-set thermostatic mixing
valve in order to provide hot water at a maximum of 60°C.
· The risk of developing bacteria exists, including “Legionella pneumophila”,
if a minimum temperature of 60°C is not maintained in both the DHW tank and
the hot water distribution network.
· In order to avoid exposure to extremely hot water that can cause serious
burns, never leave children, old people, disabled or handicapped people in the
bath or shower alone. Never allow young children to turn on the hot water or
fill their own bath.
Essential instructions for the correct operation of the appliance
· Make sure that the mains water used to fill the appliance has a minimum
pressure of 0.12 MPa (1.2 bar).
· Make sure to install a pressure reducing valve set at 0.45 MPa (4.5 bar) if
the mains supply pressure is in excess of 0.6 MPa (6 bar).
· Flush the system before connecting the domestic hot water circuit. Refer to
the installation instructions.
· If the appliance is not equipped with one, make sure to install an expansion
vessel in the primary circuit, which is adapted to the appliance power/ size
and the type of system.
· It is recommended to install an expansion vessel in the DHW circuit to
prevent the safety valve from opening constantly and reduce the water hammer
effect in the system.
· If the appliance is used as a domestic hot water preparation tank, a primary
expansion vessel adapted to the boiler power/size and to the type of system
must be fitted in the heating circuit (if there is no built-in expansion
vessel, or if the builtin expansion vessel size is not sufficient).
General remark
· If the water drawing off point is far from the tank, installing an auxiliary
DHW loop can allow to get hot water more quickly at all times.
· The circuit illustrations are basic principle diagrams only.
General remark
· At installation of domestic piping, ensure that the boiler connection elbow
is correctly tightened before installing the pipes. Retighten as required.
· At commissioning and once the system is under pressure, check that there are
no water leaks. Retighten as required.
26
A1010445-664Y8200 · B
Nm
MAX: 70 Nm
EN
Installation
G3 REQUIREMENTS AND GUIDANCE – UK ONLY
In the UK, for installation of Evo model appliances directly onto the mains
supply of water, ACV offer bespoke unvented kits which have been sized to the
requirements of each individual appliance, and contain all of the mandatory
components you need to comply with Building Regulations.
Unvented kits provided for ACV Evo models include:
· a 25L expansion vessel & mounting bracket, · a 28mm combined pressure
reducing valve
(0.35 MPa [3.5 bar]) & expansion relief valve (0.6 MPa [6 bar]), · a tundish,
· a flexi hose.
For discharge pipe arrangements not covered by G3 Guidance advice should be
sought from your local Building Control Officer.
Main characteristics : · Any discharge pipe connected to the pressure relief
devices (Expansion Valve and Temperature/Pressure Relief Valve) must be
installed in a continuously downward direction and in a frost free
environment. · Water may drip from the discharge pipe of the pressure relief
device. · This pipe must be left open to the atmosphere. · The pressure relief
device is to be operated regularly to remove lime deposits and to verify that
it is not blocked.
Discharge pipe from safety valves
The Building Regulation G3 requires that any discharge from an unvented system
is conveyed to where it is visible, but will not cause danger to persons in or
about the building.
The tundish and discharge pipes should be fitted in accordance with the
requirements and guidance notes of Building Regulation G3.
Essential instructions for safety
· The temperature/pressure relief valve should only be replaced by a competent
person.
· No control or safety valves should be tampered with or used for any other
purpose.
· The discharge pipe should not be blocked or used for any other purpose.
· The tundish should not be located adjacent to any electrical components.
CONNECTION OF THE DHW CIRCUIT
Typical installation with internal DHW tank
Description 1. Isolating valve 2. Pressure reducing valve 3. Check valve 4. DHW expansion vessel 5. Safety valve (internal) 6. Drain valve 7. Grounding 8. Draw-off tap 9. Thermostatic mixing valve
This appliance is equipped from
factory with a Temperature and
Pressure safety valve installed on
the DHW circuit. In the UK, make
sure to comply wiCtholdG3wareteqruire-
ments. above.
Also
referHtootiwnfaotremration
8 9 1
1 23
5
4
6 7
Cold water Hot water
EN A1010445-664Y8200 · B
27
Installation
For additional system configurations, refer to “Configuration and system set- up” on page 34 and to the Installer’s Handbook.
Typical connection – high temperature
Description
1. Isolating valve
2. Heating pump
3. Filling valve
4. Check valve
8
5. Safety valve (provided)
6. Expansion vessel
7. Drain valve
8. Automatic air vent (built-in)
9. Manometer
5
7
Cold water Hot water
1
9
3
4 6
1
2
Optional accessories Room thermostat High temperature kit DN 25
Description
Includes a heating pump, two isolating valves, a check valve and two
thermometers.
28
EN A1010445-664Y8200 · B
Installation
Typical connection – low temperature
Description 1. Isolating valve 2. 3-way mixing valve 3. Heating pump 4. Safety
valve (provided) 5. Filling valve 6. Check valve 7. Expansion vessel 8. Drain
valve 9. Automatic air vent (built-in) 10. Manometer
6
5
9
10 4
7
8
12
1
3
Accessory Room thermostat Contact thermostat Low temperature kit DN 25
Servomotor
Description
Mandatory to protect all floor heating circuits. Includes a heating pump, two
isolating valves, a check valve, two thermometers, a 3-way valve with built-in
bypass and a servomotor. Motor for the 3-way valve provided with the low
temperature kit.
EN A1010445-664Y8200 · B
29
Installation
CHIMNEY CONNECTION
General Recommendations and Safety Instructions
Essential instructions for safety
· Do not install the boiler into a common flue piping with any other gas or
oil appliances. This will cause flue gas spillage or appliance malfunction.
· Verify installed combustion air and flue piping are sealed gas tight and
meet all provided instructions and applicable codes and standards.
· Failure to properly support the flue system can cause the flue system to
fail, resulting in substantial property damage, serious injury, or death.
· A byproduct of any gas/oil fired appliance is carbon monoxide. Failure to
install carbon monoxide detectors with alarms can result in serious injury, or
death. Refer to applicable local regulations.
2,0 m
4
2,0 m
4 1
3
1,0 m
1 1,0 m
Slope = 3° 2
0,25 m
2,0 m
4
2
0,25 m
· Install the horizontal flue pipes with a slight slope of 5 cm per meter
(3°), so that the acid condensation water flows to a condensate recovery
container and does not damage the heating body.
· If the appliance is provided with a condensate drain assembly, make sure to
install the complete assembly on the boiler. If the assembly is incomplete,
replace the entire assembly.
· Make sure that the condensate drain assembly is filled with water before
starting up the boiler and check regularly the water level. Fill with water as
necessary.
· It is mandatory to ventilate the boiler room. The high or low air vent
opening dimensions depend on the boiler power and the boiler room size. Refer
to the local regulations in force.
· If the combustion air inlet is located in an area likely to cause or contain
contamination, or if products which could contaminate the air cannot be
removed, the combustion air must be repiped and terminated at another
location.
· Pool, laundry, common household, and hobby products often contain fluorine
or chlorine compounds, which can form strong acids and corrode the internal
components and flue system.
· In the case of parallel flue systems, make sure to maintain sufficient
distance (at least 40 mm) between the boiler flue piping and combustible
materials, and between the flue pipe and air inlet pipe if the latter is made
of plastic material.
· Do not use screws to fasten together any flue pipe elements or any PP air
inlet elements.
· Do not bond piping elements together using glue (e.g. silicone) or foam
(e.g. PUR).
General remark
0,5 m
0,25 m
0,25 m
1. Each elbow and straight element will be secured at the sleeve.
2. In case the straight element before or after the first elbow is shorter
than 25 cm, secure the straight element after the elbow using a bracket.
3. In case a straight (horizontal or sloped) element is longer than 1 m,
support the element in its center using a clamp, making sure to allow free
movement of the pipe.
4. Secure with a clamp every 2 meters in vertical piping/1 meter in
horizontal/sloped piping, making sure to distribute the clamps evenly on the
length of piping.
Essential instructions for the correct operation of the appliance · A
condensation outlet connected to the sewer
must be fitted close to the boiler to prevent the condensation products from
the flue pipe from running into the boiler. · Install a condensate
neutralisation system if required by national and/or local regulations and
have it cleaned regularly. · Only use flue system components from the same
manufacturer to connect this appliance and ensure that the pipe and connection
diameters all match. · Make sure to secure the flue piping to a solid
structure. · Exclusively use provided brackets to support the flue system.
· For safety reasons and to make assembly easier, it is recommended to prefer
the use of concentric flue pipes when possible.
· It is recommended to isolate the flue piping in damp rooms to prevent
condensation water from forming on the piping and drip.
· When cutting the pipes to dimension, make sure to cut squarely and deburr
the edges to prevent seals from being incorrect or damaged.
· To make piping assembly easier, exclusively use a mixture of water and soap
(1%) on the extremity of the pipe to be fit in.
· When fitting metal flue pipes, make sure to always fit the pipe into the
sleeve to the end stop.
· When fitting plastic flue pipes, make sure to allow material expansion by
leaving about 10 mm between the pipe end and the sleeve end stop.
· Make sure to install the piping without any strain. · Make sure to install
an inspection opening in the flue
system. · When connecting the flue pipes, make sure not to
exceed the maximum length recommended for the product, otherwise the system
power might decrease. · ACV-approved components will be used for the chimney
connection. Failure to do so will make any warranty claim void. · For C63
connection type (not allowed in Belgium), make sure to use the correct piping
material according to the resistance to temperature, pressure, chemical
composition of flue, condensation and soot. A code (as explained in EN 1443),
marked on the pipe, allows to determine if the material complies with the flue
system requirements.
Perform Chimney installation according to the data available in section “Chimney Characteristics” on page 19
30
EN A1010445-664Y8200 · B
Installation
GAS CONNECTION
RECOMMENDATIONS FOR GAS CONNECTION
Essential recommendations for safety
· The gas connection must comply with all applicable local standards and
regulations, and the circuit will be equipped with a gas pressure regulator as
required.
· Do not check for gas leaks with an open flame. Use a gas detection device or
bubble test.
· The gas burners are factory preset for use with natural gas [equivalent to
G20]. Do not adjust or attempt to measure gas valve outlet pressure. The gas
valve is factory-set for the correct outlet pressure and requires no field
adjustment.
· The natural gas to propane conversion or the reverse is not authorized in
certain countries such as Belgium. Refer to the table of gas categories in the
technical characteristics of this manual.
· In Belgium, a conversion kit is available as a separate accessory and the
conversion process must be carried out by Groupe Atlantic Belgium. Please
contact Groupe Atlantic Belgium for gas conversion.
· The gas orifice installed on the boiler must never be modified or replaced
with a different size orifice, except in the case of a gas conversion process,
which shall be performed by a qualified professional according to the provided
procedure and requirements.
·
TsuhpepClyOp2a, rgaamsetfelorws
rate, air flow rate and air/gas are factory-preset and may not
be modified in Belgium, except for type I 2E(R)
boilers.
· Do not change the OFFSET (A) setting of the gas valve: it is factory-preset and sealed.
Essential recommendations for the correct operation of the appliance
· Refer to the technical characteristics of this manual or to the burner
documentation to know the connection diameters.
· Bleed the gas duct and check thoroughly if all the boiler tubes, both
internal and external, are tight.
· Check that the gas type and pressure from the distribution network are compatible with the appliance settings. Refer to the product type plate.
· Check the boiler electrical connection, the boiler room air vent system, the
tightness of flue gas outlet pipes and of the burner chamber plate.
· Control the gas pressure and consumption at appliance start up.
·
Check the adjustment
pbrooicleerduCreO2anaddtjuhsetmteecnhtnic(raelfderatato).
the
A
EN A1010445-664Y8200 · B
31
Installation
CONVERSION TO PROPANE
General remark
According to the indication on the type plate, the boiler is factory preset to
operate with natural gas (G20/G25). Converting the boiler to propane is done
through the installation of an orifice and adjustments and shall be performed
by a qualified professional. In Belgium, this conversion procedure can only be
carried out by Groupe Atlantic Belgium personnel. Please contact Groupe
Atlantic Belgium for further information.
Set-up conditions · External power supply isolated · Gas supply closed · Upper
front panel and top cover of the boiler
open, refer to ML manual.
Evo Models 25 kW
Gas nat. orifice dia. (mm) —
Propane orifice dia. (mm) 5.2
Procedure of orifice installation
1. Release the gas pipe. 2. Remove the power supply plug from the gas valve
(1). 3. Disconnect the compensation hose (7) from the gas
valve and air inlet. Retain for reinstallation. 4. Disconnect the air inlet
(2) from the venturi (3). 5. Remove the gas valve/venturi assembly from the
fan
by releasing two screws (5). Retain the screws for reinstallation. 6. Remove
the gas valve (1) from the venturi (3) by releasing three screws (4). Retain
the screws for reinstallation. 7. Install the orifice in the center of the
O-ring (6).
Make sure you position the O-ring correctly.
8. Reassemble the gas valve/venturi assembly, following the same procedure in
reverse order, and torque the three gas valve screws (4) and the 2 venturi
screws (5) at 3.5 to 4 Nm.
9. Reinstall the air inlet (2). 10. Reconnect the compensation hose (7) to
the gas
valve and air inlet. 11. Reconnect the gas pipe connection. 12. Reconnect the
power supply plug(s) to the gas
valve. 13. Install the conversion stickers, see next page.
1 7
6
2
5
4
3
HM 25 – 35 – 45 – 70 – 85 TC Evo
32
EN A1010445-664Y8200 · B
Installation
Sticker Placement Make sure to place the stickers as requested. Failure to
comply can cause injuries or damage to the equipment.
· Stick the yellow sticker at the back of the boiler and check the box to
indicate the type of gas now used with the appliance.
· Stick the provided G31 data plate on the existing data plate (back of the
appliance), or the corrective stickers (Belgium only).
Follow-on tasks 1. Start the boiler. Refer to “Starting up the Boiler” on
page 39. 2. Change the boiler code through the Installer menu,
refer to the “Installer’s handbook” 3. Carry out the CO2 adjustment, See
“Checking and Adjusting
the Burner” on page 39. 4. Reseal the offset and the throttle on the gas
valve, as
required. 5. Close all open panels, see the ML Book.
EN A1010445-664Y8200 · B
33
Installation
CONFIGURATION AND SYSTEM SET-UP Basic Configuration – HeatMaster 25 C Evo:
High Temperature Heating Circuit Controlled by Room Thermostat and Optional
Outdoor Sensor.
2 1
3
ACVMax
BLOCK DIAGRAM
The heating system (radiators) is controlled by an On/Off room thermostat.
In this configuration, the boiler constantly adapts its operation to the
outdoor temperature, if an outdoor temperature sensor is connected.
The heating pump is triggered as soon as the room thermostat generates a heat
demand.
The priority of the internal domestic hot water tank of the boiler (DHW
circuit not shown here) is always active.
ITEM
DESCRIPTION
QTY
ELECT. TERMINALS TO CONNECT TO**
1 Room thermostat
1
2 Outdoor temperature sensor, 12k
1
4321
X6 3&4
X6
X6 1&2
20 NTC 4
2
1
1
2 circuit manifold :
Max power : 70 kW, With built-in wall
1
—
mounts.
High temperature kit :
3
Includes: a circulator pump, two isolation valves, a check valve and two thermom-
2
eters.
By-pass kit :
To read the flow rate more easily. To be in-
1
stalled in the HT or LT circuit, as required.
87654321
LN
6
X100
Br
B
230 V
Y/Gr
B
Br
X100 3 to 8 —
- The illustrations are for information only. For more details on the required accessories, refer to the latest ACV price list.
** Refer to the ML book for the correct Wiring Diagrams, and to “Electrical Characteristics” on page 15.
On the ACVMax Touch, set as follows:
EZ Setup
Heating EZ Setup
Select CH Demand
Thermostat & Outd. Curve Constant & Outdoor Curve Constant & Setpoint 0 – 10 V
Power Modulation 0 – 10 V Temp. Modulation
34
EN A1010445-664Y8200 · B
Installation
Cascade Configuration, Controlled by EBV Controller
The control Unit (EBV Controller) is used to control a HeatMaster 25 C Evo
Cascade. The connection is made through the EBV Clip-in wiring provided with
the Control Unit. Please connect on ACVMax board X18 and route wires to EBV
equipment.
For additional information and specific system configurations, please contact
your ACV representative.
15
123
123
16
12345 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
17
4
6
123
123456
W
W
W
W
W
W
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
W
Bk
R
W
W
W
W
W
W
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
W
R
Bk
10 11 12 13 14
7
X2
13 14
1 2 3 4 5 6 7 8 9 10
12345
X11
6 7 8 9 10
123456
123
X15
456
X16
ax
EBV Clip-in wiring
24
X18
X7
X4
Bk R
X6
X5
12 34
321
4321
21
321
Bus A
18 Bus – Ground
Bus B
19 NTC 3 20 NTC 4
1 21
22 0-10 Volt – Input
0-10 Volt – Ground
EN A1010445-664Y8200 · B
35
Installation
Applications with Water Hammer Effect (e.g. car wash)
When the appliance is used in applications where water hammer effect can be
severe due to the frequent and sudden opening/closing of valves, (e.g. car
wash systems, etc.), devices should be installed in the system to counter this
effect and prevent damage from occurring to the piping/appliance.
The water hammer effect is caused by shock waves running through the system
when the flow rate is changed suddenly (e.g. when a valve is closed/opened
suddenly). This induces a surge/sudden fall in pressure, which creates noise
and sometimes movement in the system piping.
The pressure wave created in these circumstances can be up to three times
greater than the standing system pressure. This can damage the piping and the
appliance.
It is therefore strongly recommended to install shock arrestor absorber and/or
water hammer arrestor devices in the hydraulic system.
To determine the correct devices to be installed in the system for your
application type and size, please contact your ACV representative.
Expansion vessel Draw-off tap Ball valve
Thermostatic mixing valve Pneumatic valve Check valve
Cold water Hot water
Pressure reducing valve Safety valve
Piston water hammer arrestor Shock arrestor absorber
Primary filling valve with disconnection
ACV/Groupe Atlantic shall not be liable for any special, indirect, incidental or consequential damages if the recommendations herein are not complied with at installation of the appliance in such systems.
36
EN A1010445-664Y8200 · B
Commissioning
SAFETY INSTRUCTIONS FOR STARTING UP
Essential instructions for safety
· The components inside the control panel may
only be accessed by an approved installer.
· Set the water temperature in accordance with usage and local plumbing codes.
· Make sure that the heating circuit filling valve is closed once the starting
up process is complete.
· If there is a drain assembly, make sure that the condensate drain assembly
is filled with water before starting up the boiler. Fill with water as
necessary.
· Make sure that all connections are made and tight.
General remark
In normal operation, the burner starts automatically as soon as the boiler
temperature drops below the preset temperature.
TOOLS REQUIRED FOR STARTING UP
GAS pressure (mbar)
CHECKS BEFORE STARTING UP
Essential recommendation for safety · Check the tightness of the flue pipe
connections.
Essential recommendation for the correct operation of the appliance · Control
the tightness of the hydraulic circuit
connections.
EN A1010445-664Y8200 · B
37
Commissioning
FILLING THE SYSTEM
Put the DHW tank under pressure before pressurizing the heating (primary) circuit.
Set-up conditions
2
· External power supply isolated
1
DHW circuit filling procedure
1. Open the isolating valves (1) and the draw-off tap (2).
1
2. Once the water flow rate has stabilized and the
air is totally evacuated from the system, close the
draw-off tap (2).
3. Check all the connections for leaks.
Cold water Hot water
Heating circuit filling procedure
1. Open boiler front panel (refer to applicable procedure in the manual).
2. Open the isolating valves (1).
3. Make sure that the drain valve (3) is tightly closed.
4. Open the filling valve (2).
5. Once the system is bled from air, bring the pressure to the static
pressure between 0.15 and 0.2 MPa (1.5 and 2 bar).
6. Close the filling valve (2).
7. Disconnect filling device from water supply.*
Follow-on tasks
1. Check there is no leak.
3
The drain valve is located underneath and the front cover of the base needs to be removed to get access to it.
- UK specific reference G24.1 & G24.2 of the Water Regulations Guide.
38
A1010445-664Y8200 · B
1 2
1
EN
Commissioning
STARTING UP THE BOILER
Set-up conditions
· All connections made · Gas conversion carried out as required · Condensate
trap full of water · Electrical power supply on · Gas supply open · Hydraulic
circuit(s) full of water
Procedure
Before operating the appliance, make sure that the primary circuit is full of
water and has the minimum recommended pressure, even if no heating circuit is
installed. Failure to comply can damage the equipment.
1. Check that there is no gas leak. 2. Depress the ON/OFF master switch ( ).
3. If a room thermostat is installed, possibly increase the tem-
perature set-point to generate a demand. 4. Check the gas pressure and allow
the boiler to heat up for
a few minutes 5. Check and adjust the burner according to local standards
and regulations, refer to the procedure on the right. 6. Set the central
heating temperature to the required val-
ue using the control panel. Refer to “Controller Set-up Guide” on page 8 and
to the Installer’s Handbook. 7. After 5 minutes of operation, bleed the
heating circuit until all air is evacuated and restore a 0.15 MPa (1.5 bar)
pressure. 8. Bleed the central heating circuit once again and top it up with
water to get the required pressure, if necessary. 9. Make sure that the
central heating system is properly balanced and, if needed, adjust the valves
to prevent certain circuits or radiators from getting a flow rate that is far
above or below the set rate.
Follow-on tasks
1. Close the heating circuit filling valve and disconnect the filling
connection as required.
2. Check that there are no leaks. 3. Check that the flow rate in the
appliance is sufficient as
follows : · Operate the boiler at maximum power · Once the temperatures are
stable, read out the supply
and return temperatures · Check that the difference between the supply and re-
turn temperature is equal or less than 20k. · If the Delta T is higher than
20k, check the pump set-
tings/specifications.
CHECKING AND ADJUSTING THE BURNER
When the burner operates at full power, the CthOe2treacthenmicuasltcbheawraicthteinritshtiecslim, (sitesem”eCnotmiobnuesdtioinn characteristics” on page 15).
Set-up conditions · Front top panel and top panel removed. See ML Book. · Operating boiler
Procedure
1. Check if the ACVMAX parameters are set to meet the us-
er’s requirements (refer to “Controller Set-up Guide” on page 8), and change them if required.
2. Put the boiler to maximum power mode (Refer to the Install-
er’s Handbook).
3. Using a pressure tester, check that the dynamic gas pres-
sure at the gas valve is at least 18 mbar.
4. Allow the appliance to heat for a few minutes until it reach-
es at least 60°C.
5. Measure the burner combustion by placing the flue gas
analyzer probe in the measurement unit port on the flue
pthipoeseainnddiccoamtepdairnetthheecCoOmbaunsdtiConOc2 hvaarluaectsedriisstpiclasyteadblew.ith
IafdtjhuestCmOe2nvt amlueentdioifnfeerds
by more than 0.3%, carry in the procedure below.
out
the
7. Then put the boiler to the minimum power mode (Refer to
the Installer’s Handbook). Allow the boiler to stabilize for a
few minutes.
8. Measure the burner combustion and compare the CO
aconmd bCuOst2iovnalcuheasradcitseprliastyiecsd
with table.
those
indicated
in
the
9. IcfutshteomCOer2’svasluupepdoirftfe. rs by more than 0.3% , contact ACV’s
CO2 Adjustment Procedure
To adjust the CO2 rate, rotate the throttle screw (1) in small steps : on the
HM 25 C Evo:
· to the left (counterclockwise) to increase the CO2 rate. · to the right
(clockwise) to decrease the CO2 rate.
1
Follow-on tasks Reinstall all removed access panels. See ML book
EN A1010445-664Y8200 · B
39
Maintenance
SAFETY INSTRUCTIONS FOR MAINTENANCE
Essential instructions for the electrical safety
· Before opening the boiler for maintenance, turn off the boiler by pushing on
the ON/OFF master switch.
· Isolate the external power supply of the appliance before performing any
operation, unless it is required to take measurements or perform system setup.
Essential instructions for safety
· Water flowing out of the drain valve may be extremely hot and could cause
severe scalding.
· Do not use solvents to clean any of the burner components. The components
could be damaged, resulting in unreliable or unsafe operation.
· Check the tightness of the flue pipe connections.
Essential instructions for the correct operation of the appliance
· It is recommended to have the boiler and the burner serviced at least once a
year or every 1,500 hours by a qualified technician, preferably at the start
of the heating season. More frequent servicing may be required depending on
boiler use. Please consult your installer for advice.
· The boiler and burner maintenance will be carried out by a qualified
engineer, and the defective parts may only be replaced by genuine factory
parts.
· Make sure to replace any gaskets or seals on the removed components before
reinstalling them.
· To ensure maximum efficiency and reliability of the unit, it is recommended
that the end-user perform the periodic checks mentioned in the Safety section
of this manual.
· Control the tightness of the hydraulic circuit connections.
· Make sure to apply the correct torque value when tightening components,
according to the table below.
TORQUE VALUES
Description Burner flange screws Electrode screws Venturi screws Gas valve
screws
Tightening torque (Nm)
Min.
Max
5
6
3
3.5
3.5
4
3.5
4
40
EN A1010445-664Y8200 · B
Maintenance
TOOLS REQUIRED FOR MAINTENANCE
BOILER SHUT DOWN FOR MAINTENANCE
1. Switch the boiler off using the ON/OFF master switch and isolate the
external power supply.
2. Close the gas supply valve of the boiler.
GAS pressure (mbar)
PERIODIC BOILER MAINTENANCE TASKS
Tasks
Periodic inspection
End-user
1. Make sure that the primary water pressure is at least 0.1 MPa (1 bar) when cold. Top
up the system if necessary, adding small quantities of water at a time. In case of
X
repeated fills, call your installer.
2. Check that there is no water on the floor under the boiler. Call your installer if there is.
X
3. Check that no error code is displayed on the control panel. Call your installer if necessary.
X
4. Check that all gas, hydraulic and electrical connections are correctly fastened and tight.
5. Check the flue gas exhaust: correct fastening, correct installation, no leaks or clogging.
6. Check that there is no discoloured or cracked area on the burner chamber plate .
7. Check the combustion parameters (CO and CO2), see “Checking and Adjusting the Burner” on page 39.
8. Check visually the heating body: no evidence of corrosion, soot deposits or damages. Carry out all required cleaning tasks, repairs and replacements that might be required.
9. Check the electrode, see “Removal, Check and Installation of the Burner Electrode” on page 44.
10. Remove the burner and clean the exchanger, see “Removal and Installation of the Burner” on page 43 and “Cleaning the Exchanger” on page 44.
11. Check that the condensate trap is not clogged. If it is, remove it, clean it, and reinstall it i.a.w. “boiler Preparation” on page 25.
12. If a condensate neutralisation system is installed, check it and have it cleaned.
X
Frequency 1 year 2 years
Professional X
X X X X X X
X
X
X X X
EN A1010445-664Y8200 · B
41
Maintenance
DRAINING THE BOILER
Essential instructions for safety
· Before draining the DHW tank, drain the heating (primary) circuit or bring
its pressure to 0 bar. · Water flowing out of the drain valve may be extremely
hot and could cause severe scalding. Keep
people away from the hot water discharge.
Set-up conditions
· Boiler switched off using the ON/OFF master switch
· External power supply isolated · Fuel/gas supply closed
Heating circuit draining procedure
1. Close the isolating valves (1).
1
2. Connect the drain valve (2) to the sewer with a hose.
3. Open the drain valve (2) to empty the heating circuit
of the boiler.
4. Close the drain valve (2) once the heating circuit of
the boiler is empty.
Cold water
2
1
Hot water
DHW circuit draining procedure
Before draining the DHW tank, make sure that the heating (primary) circuit
pressure is null.
1. Open fully a draw-off tap (3) for about 60 minutes to make sure that the
DHW tank has cooled down.
2. Close the isolating valves (1). 3. Connect the drain valve (2) to the
sewer with a
hose. 4. Open the drain valve (2) and drain the DHW tank
water to the sewer. 5. Open the draw-off tap (3) to accelerate the
draining process. If it is located lower than the tank connection, open a
draw-off tap located higher in the system. 6. Close the drain valve (2) and
the draw-off tap (3) once the DHW tank of the boiler is empty.
The drain valve is located underneath and the front cover of the base needs to
be removed to get access to it. Refer to “boiler Preparation” on page 25 for
more information.
3
1
2
42
EN A1010445-664Y8200 · B
Maintenance
REMOVAL AND INSTALLATION OF THE BURNER
Set-up conditions
· Boiler shut down · External power supply isolated · Gas supply closed ·
Front and top panels removed (refer to ML Book). · Electrode removed or
electrode grounding cable and ig-
nition cable disconnected (refer to “Removal, Check and Installation of the
Burner Electrode” on page 44) .
Removal procedure
1. Disconnect all plugs from the fan assembly (11) and the gas valve (2) and
any grounding cable, as required.
2. Disconnect the air inlet elbow (3). 3. Release the gas connection (1). 4.
Using a socket wrench, release the burner hood (8)
attaching hex. screws and retain them for reinstallation. 5. Lift the burner
assembly and pull it out of the exchanger. 6. If required, clean the
exchanger, see “Cleaning the Exchanger” on page 44. 7. If not removed
previously, remove, check and reinstall the electrode, refer to “Removal,
Check and Installation of the Burner Electrode” on page 44.
Installation procedure
1. Reinstall the burner assembly with its insulation block into the
exchanger.
2. Install the retaining screws of the burner hood (8) and fasten them in a
crosswise pattern at the required tightening torque (refer to “Torque Values”
on page 40).
3. Reconnect the gas connection (1).
When connecting the air inlet, make sure that the check valve (4) is correctly
located at the elbow (3) end.
4. Reconnect the air inlet elbow (3).
5. Reconnect the plugs to the gas valve (2) and the fan assembly (11), and
any disconnected grounding cable.
Follow-on tasks
1. Install the electrode, or reconnect the electrode grounding cable and
ignition cable, as required. Refer to “Removal, Check and Installation of the
Burner Electrode” on page 44.
Detail of the burner compo-
11
nents
1
1. Gas connection
2
2. Gas valve
3. Air inlet elbow(s)
4. Air inlet check valve
5. Venturi 10
6. Burner tube
7. Insulation
3
8. Burner hood
9
9. Burner hood insulation 5
8
10. Electrode 4
11. Fan assembly
7
6
EN A1010445-664Y8200 · B
43
Maintenance
REMOVAL, CHECK AND INSTALLATION OF THE BURNER ELECTRODE
Remove the electrode to control it in case of ignition problems.
Set-up conditions
· Boiler shut down · External power supply isolated · Gas supply closed ·
Front and top panel open, refer to ML Book.
Removal procedure
1. Disconnect the electrode grounding cable from the electrode.
2. Disconnect the electrode ignition cable from the electrical box.
3. Remove two mounting screws (1) and retain them for reinstallation.
4. Remove the electrode (2) and the gasket (3). 5. Check the correct
alignment of the electrode
ends and that the gap corresponds to the values indicated on the figure below.
6. If the electrode is in bad condition, replace it.
Installation procedure
1. Install a new gasket (3). 2. Install the electrode (2) using the two
screws (1),
torque i.a.w. “Torque Values” on page 40.
Follow-on tasks
1. Reconnect the grounding cable to the electrode. 2. Reconnect the ignition
cable to the electrical
box.
1
2
Min. 3 mm
Max. 4 mm
3
CLEANING THE EXCHANGER
Set-up conditions
· Boiler shut down · External power supply isolated · Gas supply closed ·
Burner removed i.a.w. procedure “Removal and In-
stallation of the Burner” on page 43. · Front and top panels open, refer to ML
Book .
Procedure
1. Brush and vacuum clean the chamber. 2. Pour some water in the chamber to
flush away
any foreign deposits that may be present in the heat exchanger. 3. Remove and
clean the condensate trap. 4. Reinstall the condensate trap, refer to “boiler
Preparation” on page 25.
Follow-on tasks
1. Reinstall the burner according to procedure “Removal and Installation of
the Burner” on page 43.
2. Restart the boiler in accordance with the next procedure.
RESTARTING AFTER MAINTENANCE
Set-up conditions
· All removed components reinstalled · All connections made · Power supply · Gas supply open · Hydraulic circuit(s) full of water
Procedure
1. Make sure there is no gas leak at the gas connections.
2. Switch the appliance on using the ON/OFF master switch.
3. Set the appliance at maximum power and check the absence of gas and flue gas leaks.
Check the gas pressure and in accordance with “Checking
CO2 adjustment and Adjusting the
Burner” on page 39.
Follow-on tasks
None
44
EN A1010445-664Y8200 · B
Troubleshooting
Codes E 01 E 02 E 03
E 05
E 07 E 08 E 09 E 12 E 13 E 15 E 16
E 17
E 18 E19 E 21
Description of the fault
Failed ignition: The burner failed to light after 5 ignition attempts.
False flame: Flame detected prior to ignition. High Boiler temp. : The
appliance temperature exceeds 105°C
Blower speed: Blower speed not correct or speed signal is not received by
ACVMax.
High Flue temp.: Flue temperature exceeds high limit.
Flame Circuit Error: Flame circuit test failed
Gas valve circuit error: Gas valve circuit test failed. Internal Fault: EEPROM
misconfiguration Reset limit reached: Resets are limited to 5 every 15
minutes. Sensor Drift: Supply or return sensor reading has drifted.
Supply Sensor Stuck: Supply sensor reading is not changing.
Return Sensor Stuck: Return sensor reading is not changing.
Sensor Failure: Supply or return sensor reading changed very rapidly.
Flame Failure: Flame failure during start up phase
Internal Control Fault: A / D conversion error.
Solution for the fault
1. Check gas supply to appliance. 2. Check Ignition cable connection in
control box. 3. Check electrode for defects, and distance between the pins. 4.
Check gas valve and electrical connections to gas valve.
1. Check good electrical ground connection to unit. 2. Check electrode for
pollution and deposition of dirt.
Correct condition which caused high temperature or limit to open. 1. Check
water flow in the system (radiator valves). 2. Check Pump and pump electrical
connections. 1. Check blower and wiring harness. 2. Under normal condition if
actual fan speed is 1000 rpm different from set
fan speed an error is displayed (after 60sec in running and after 30 sec. at
startup). 3. Only exception when actual fan speed > 3000 rpm at max. PWM. 1.
Heat exchanger may require cleaning. 2. Appliance will automatically reset
once flue temperature returns to normal range. 1. Turn appliance off. 2. Check
and clean the electrode. 3. Check ignition and grounding cables are firmly
connected. 1. Check the gas valve and wiring harness. 2. If the problem
persists replace the “ACVMax” circuit board. 1. Turn unit off and on to resume
normal operation. 2. If the problem persists replace the “ACVMax” circuit
board. 1. Turn unit off and on to resume normal operation. 2. If the problem
persists replace the “ACVMax” circuit board.
Check supply and return temperature sensors and wiring harness.
1. Check supply temperature sensor and wiring harness for shortcuts or other
defects.
2. Check waterflow and the temperature balance in the system, because primary
supply temperature does not change.
1. Check return temperature sensor and its position, check wiring harness for
shortcuts or other defects.
2. Check waterflow and the temperature balance in the system, because primary
return temperature does not change.
3. Failure may happen at low output capacity when supplying from a big tank !
Check supply and return temperature sensors and wiring harness.
Flame loss after start up of the appliance. 1. Check the flue system for
blockage and check the adjustment of the appli-
ance. 2. Also check the Ignition / Ionisation rod (distance to the burner /
pollution)
Turn unit off and on then press OK to resume normal operation.
E 25 Internal Control Fault: CRC check error.
Turn unit off and on to resume normal operation.
E 30
Supply Sensor Shorted: A short circuit has been detected in the appliance supply temperature sensor circuit
1. Check supply temperature sensor and wiring harness for a short circuit. 2.
If necessary replace the sensor, or the wire harness. 3. After fixing the
problem, reset the appliance and resume normal opera-
tion.
1. Check supply temperature sensor, connectors and wiring harness for an
Supply Sensor Open: An open circuit has
open circuit.
E 31 been detected in the appliance supply
2. If necessary replace the sensor, or the wire harness.
temperature sensor circuit
3. After fixing the problem reset the appliance and resume normal opera-
tion.
DHW Sensor Shorted: A short circuit has E 32 been detected in the DHW
temperature
sensor circuit
1. Check DHW temperature sensor and wiring harness for a short circuit. 2. If
necessary replace the sensor, or the wire harness. 3. After fixing the problem
reset the appliance and resume normal opera-
tion.
EN A1010445-664Y8200 · B
45
Troubleshooting
Codes E 33 E 34 E 37 E 43 E 44 E 45 E 46 E47 E 76
Description of the fault
DHW Sensor Open: An open circuit has been detected in the DHW temperature
sensor circuit
Low Voltage: Line voltage has fallen below an acceptable operating level. Low
Water: Water level has fallen below 0.07 MPa (0.7 bar). Return Sensor Shorted:
A short circuit has been detected in the appliance return temperature sensor
circuit.
Return Sensor Open: An open circuit has been detected in the appliance return
temperature sensor circuit.
Flue Sensor Shorted: A short circuit has been detected in the appliance flue
temperature sensor circuit
Flue Sensor Open: An open circuit has been detected in the appliance flue
temperature sensor circuit.
Water pressure sensor error: Water pressure sensor is disconnected or broken
Gas pressure switch open
External Limit Open: An external automatic reset appliance limit has opened.
Solution for the fault
1. Check DHW temperature sensor, connectors and wiring harness for an open
circuit.
2. If necessary replace the sensor, or the wire harness. 3. After fixing the
problem reset the appliance and resume normal opera-
tion.
The appliance will automatically reset once line voltage returns to normal.
1. Increase pressure to normal range. 2. The appliance will automatically
reset once water level returns to normal.
1. Check return temperature sensor and wiring harness for a short circuit. 2.
If necessary replace the sensor, or the wire harness. 3. After fixing the
problem, reset the appliance and resume normal opera-
tion. 1. Check return temperature sensor, connectors and wiring harness for an
open circuit. 2. If necessary replace the sensor, or the wire harness. 3.
After fixing the problem, reset the appliance and resume normal opera-
tion. 1. Check flue temperature sensor and wiring harness for a short circuit.
2. If necessary replace the sensor, or the wire harness. 3. After fixing the
problem reset the appliance and resume normal opera-
tion. 1. Check flue temperature sensor, connectors and wiring harness for an
open
circuit. 2. If necessary replace the sensor, or the wire harness. 3. After
fixing the problem reset the appliance and resume normal opera-
tion. 1. Check water pressure sensor, connectors and wiring harness. 2. If
necessary replace the sensor, or the wire harness. 3. After fixing the problem
reset the appliance and resume normal opera-
tion. 1. Check both the static and the dynamic gas pressures. 2. Correct
condition which caused the pressure switch to open 3. Appliance will
automatically reset once the pressure switch is closed.
1. Correct condition which caused limit to open. 2. Appliance will
automatically reset once external limit closes
E 77 High temperature mixing circuit
Check if the mixing valve functions correctly.
E 78 Mix circuit sensor shorted E 79 Mix-circuit sensor Open
1. Check Mix circuit temp. sensor and wiring harness for a short circuit.
2. If necessary replace the sensor, or the wire harness.
3. After fixing the problem reset the appliance and resume normal opera-
tion.
1. Check Mix circuit temp. sensor and wiring harness for an open circuit. 2.
If necessary replace the sensor, or the wire harness. 3. After fixing the
problem reset the appliance and resume normal opera-
tion.
E 80
Return > Supply: Return temperature is higher than supply temperature.
Confirm water flows in appliance return and out appliance supply.
1. Check water is flowing through appliance.
E 81
Sensor Drift: Supply and return temperatures are not equal.
2. Wait a few minutes for the water to equalise the temperature, the
appliance will automatically reset once temperatures become equal.
3. If appliance doesn’t reset, check the NTC’s and check the wire harness,
replace if necessary.
E82
Delta T protection blocking – Delta T too high
1. Verify flow in the system. 2. Check pump for blockage and obstructions,
unblock it as required. Re-
place if necessary.
E83
Delta T protection Lock-out – Lock-out due to Delta T value.
1. Verify flow in the system. 2. Check pump for blockage and obstructions,
unblock it as required. Re-
place if necessary.
E 85
Pump operation: warning – Appliance pump is running out of limits.
Pump is running out of its limits. Check pump for blockage and obstructions, replace if necessary
E 86 Pump hard fault: Pump Failure
Pump Failure, check if pump PWM-feedback wire is properly connected, replace pump when necessary
46
EN A1010445-664Y8200 · B
Troubleshooting
Codes E 87 E88 E 89 E 90 E 91
E 92
E 93 E 94 E 95
E 96 E 97 E 98 E 99
Description of the fault
Solution for the fault
External Limit Open: An external appliance 1. Correct condition which caused limit to open, then reset appliance.
limit has opened.
2. The appliance needs to be reset once external limit closes.
Pump Blocking: Pump attempts to restart.
Check pump for blockage and obstructions, unblock it as required. Replace if necessary.
Incorrect Setting: A parameter setting is outside the settings range.
1. Review primary/CH & DHW settings and correct as necessary. 2. The appliance will automatically reset once corrected.
Firmware Mismatch: Control module and display firmware versions are
incompatible.
System Sensor Shorted: A short circuit has been detected in the system
temperature sensor circuit
System Sensor Open: An open circuit has been detected in the system
temperature sensor circuit.
Outdoor Sensor Shorted: A short circuit has been detected in the outdoor
temperature sensor circuit.
Internal Display Fault: Display memory error
Supply Sensor Error: Supply sensor reading is invalid
Outdoor Sensor Open: An open circuit has been detected in the outdoor
temperature sensor circuit.
Cascade Mismatch: Cascade configuration has changed.
Cascade Bus Error: Communication with other appliances has been lost.
Controller Bus Error: Communication between appliance display and control
module has been lost.
One or several components are not compatible with the system. Replace
mismatched component(s).
1. Check system temperature sensor and wiring for a short circuit. 2. If
necessary replace the sensor, or the wire harness. 3. After fixing the problem
reset the appliance and resume normal opera-
tion. 1. Check system temperature sensor and wiring for an open circuit. 2. If
necessary replace the sensor, or the wire harness. 3. After fixing the problem
reset the appliance and resume normal opera-
tion. 1. Check outdoor temperature sensor and wiring for a short circuit. 2.
If necessary replace the sensor, or the wire harness. 3. After fixing the
problem reset the appliance and resume normal opera-
tion.
Turn unit off and on to resume normal operation.
1. Check wiring between display and control module. 2. If necessary replace
the sensor, or the wire harness. 3. After fixing the problem reset the
appliance and resume normal opera-
tion. 1. Check outdoor temperature sensor and wiring for an open circuit. 2.
If necessary replace the sensor, or the wire harness. 3. After fixing the
problem reset the appliance and resume normal opera-
tion. 1. Run autodetection if change was intentional, or else check wiring be-
tween appliances. 2. Appliance will automatically reset once repaired.
1. Check wiring between appliances. 2. Appliance will automatically reset
once repaired.
1. Check wiring between components. 2. Appliance will automatically reset
once repaired.
References
- ACV Excellence in hot water - ACV
- Que Faire de mes Déchets ? Découvrez les solutions pour tous vos déchets et nos conseils pour en produire moins.